FUJI EDSX6-137H

SMALL FLANGE REMOTE SEAL TYPE
DIFFERENTIAL PRESSURE TRANSMITTER
FKX...5
DATA SHEET
The FCX -AIII small fl ange remote seal type differential
pressure transmitter accurately measures differential
pressure, liquid level or gauge pressure and transmits a
proportional 4 to 20mA signal. The transmitter utilizes a
unique micromachined capacitance silicon sensor with stateof-the-art microprocessor technology to provide exceptional
performance and functionality. Totally welded construction
of the seals assures excellent reliability in high temperature
and highly corrosive process conditions.
FEATURES
1.
2.
3.
4.
5.
6.
7.
Directly connectable to 1-1/2 in and 2in flanges
The transmitter is connectable to 1-1/2 in and 2in pipes
without a reducer.
Flow measurement without impulse piping
1/2 in and 3/4 in flange size is also available. This differential pressure transmitter allows connection to 1/2 in
and 3/4 in flanges of a general size for the orifice tap,
which eliminates the need of using a impulse piping.
Problems with the impulse piping, such as clogging,
leaks or corrosion can be solved. In addition, the following process connection is also available.
Screw connection 1/2-14NPT, 3/4-14NPT, Rc 1/2, Rc 3/4
Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
Fuji/HART® bilingual communications protocol
FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX -AIII.
Application flexibility
Various options that render the FCX -AIII suitable for
almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5 -digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum seals
Programmable output Linearization Function
In addition to Linear and Square Root, output signal can
be freely programmable.
(Up to 14 compensated points at approximation.)
Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
8. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Static pressure
Span limit [kPa]
(m bar}
Min.
F KX
3
F KX
5
F KX
6
Up to
flange rating
3
{ 30}
13
{130}
50
{500}
Max.
32
{ 320 }
130
{ 1300 }
500
{5000 }
Range limit
[kPa] {m bar}
+/− 32
{+/− 320}
+/− 130
{+/− 1300}
+/− 500
{+/− 5000}
Maximum static pressure limit for screw connction
type: 4.2MPa
− Lower limit of static pressure (vacuum limit),
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: Atmospheric pressure
− The maximum span of each sensor can be converted
to different units using factors as below.
1MPa =103kPa=10bar=10.19716kgf/cm2
=145.0377psi
1kPa=10mbar=101.976mmH2O=4.01463H2O
−
EDSX6-137h
Date
Aug. 10, 2011
FKX...5
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
1500
Temperature limit:
Ambient: −15 to + 65°C
(−15 to + 60°C for arrester option)
(−10 to + 60°C for fluorinated oil fill transmitter)
(−10 to + 60°C for silicone oil “H”, “S”)
(−15 to + 45°C for capillary length more than 7m)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
1474Ω
R=
E-10.5
(Imax+0.9)x10-3
13th digit of
“Code symbols”
Process
temperature
Fluorinated oil
W, A and D
−20 to 120°C
Silicone oil
H
577Ω
−40 to 180°C
0
24V
10
45V
16.35
10.5V
Power voltage (DC)
50
E[ V ]
Note: For communication with HHC(1) (Model: FXW), min. of 250 is
required.
Hazardous locations: SEE TABLE2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
−100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure,
the analog signal will be driven to either
“Output Hold”, “Output Overscale” or
“Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC(1)
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
0 to 250°C
S
Operating
area
250
3.2
0 to 250°C
Y and G
1000
500
Probable over range
Output limits conforming to NAMUR NE43 by order.
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA by
HHC(1).
Lower limit
of
static press.
Atmospheric
pressure
2.7kPa abs
{20mmHg
abs}
Storage: −40 to +70°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than 7.0
(or FXW
1− 4), for FCX–AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Linear
v
v
v
v
Square root
v
v
v
v
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
Output mode
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326-1: 2006
(Note)
2
Fill fluid
(1) HHC: Hand Held Communicator
Static pressure effect:
Zero shift; 0.2% of URL/1MPa (10 bar)
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4
to 20mA analog output in linear mode and capillary length 3m.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: 0.25% of span
For spans below 1/10 of URL:
0.1 x URL
± 0.17+0.08
% of span
Span
(
)
(Option) (Code; 21th digit H,K)
For spans greater than 1/10 of URL: 0.1% of span
For spans below 1/10 of URL:
0.1 x URL
± 0.05+0.05
% of span
Span
(
)
Stability:
±0.2% of upper range limit (URL) for 10
years.
Temperature effect:
Effects per 28°C change between the
limits of −15°C and +65°C
Zero shift: ±0.5%/28°C
(x equal to 1/2 URL or more)
URL
Zero shift; ± (0.5 2 x
)%/28°C
Span shift: −0.2% of calibrated span /1MPa
Overrange effect: Zero shift; 0.1% of URL for flange rating
pressure
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
Update rate:
60 msec
Step response: (without electrical damping)
Time constant (at 23°C)
1.7 s
Dead time
0.12 s
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
(x less than 1/2 URL)
Total shift; ±0.75%/28°C
(x less than 1/2 URL or more)
Total shift; ±(0.25 + 0.5 URL )%/28°C
2x
(x less than 1/2 URL)
(option) (Code; 21th digit J,K)
Zero shift: ±0.5%/28°C
(x equal to 1/6.5 URL or more)
URL
Zero shift; ± (0.5
)%/28°C
6.5 x
(x less than 1/6.5 URL)
Total shift; ±0.75%/28°C
(x equal to 1/6.5 URL or more)
URL
Total shift; ±(0.25 + 0.5
)%/28°C
6.5 x
(x less than 1/6.5 URL)
Where, x:
Calibrated span
URL:
Maximum span (Upper Range
Limit)
Note : Above specifications are based on the
conditions that flanges and sensor unit are
at the same temperature and in the same
level. If temperature is different at flanges,
capillary or sensor unit, output variation
may increase.
3
FKX...5
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified.
Process connections:
JIS
10K, 20K, 30K - 40, 50A
10K, 20K, 30K - 15, 20A (with Adapter)
ANSI/JPI
150LB, 300LB -11/2", 2"
150LB, 300LB - 1/2", 3/4" (with Adapter)
Screw connection (with Adapter);
Rc1/2, Rc3/4, 1/2 - 14NPT, 3/4 - 14NPT
Diaphragm extension:
0, 50, 100, 150, or 200mm as specified.
(See model code. Extended diaphragm
is available only with 316L stainless steel
diaphragm)
Process-wetted parts material:
Diaphragm:316L stainless steel, Hastelloy-C,
Monel or Tantalum
Flange face: 316 stainless steel, HastelloyC lining
Monel lining, or Tantalum lining
Extension: 316 stainless steel
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with polyester
coating (standard), or 316 stainless
steel (ASTM CF8M), as specified.
Capillary: In case of 11th code “D. E. L.”,
PE armored stainless steel.
In case of 11th code “Q. R. S”, stainless steel armored stainless steel.
Mounting flange: 304 stainless steel or
carbon steel.
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting
Mass {weight}:
Transmitter approximately 12.7 to 30.7kg
without options.
Add; 0.5kg for mounting bracket
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity: 4kV (1.2 ×
50µs).
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig. 1.
Optional tag plate:
An extra stainless steel tag for customer
tag data is wired to the transmitter.
Coating of cell: Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
Filled liquid:
Silicone (Code Y,G)
[kPa abs]
{m bar abs}
Silicone (Code S)
101
{1010}
Operating pressure
Physical specifications
53.3
{533}
Operating area
13.3
{133}
Non-operating
area
2.7
{27}
–40 0
60 85 120
180
Process temperature
230 250
[°C ]
Fig. 1 Relation between process temperature and
operating pressure
ACCESSORIES
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
4
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Description
<Connections>
<Conduit connection>
<Case type>
G1/2
T type
1/2-14NPT
T type
Pg 13.5
T type
M20 × 1.5
T type
G1/2
L type
1/2-14NPT
L type
Pg 13.5
L type
M20 × 1.5
L type
<Flange>
Material
Size and rating
304 stainless
JIS 10K 40A
steel
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
JIS 63K 40A
JIS 63K 50A
ANSI/JPI 150LB 1 1/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 1 1/2"
ANSI/JPI 300LB 2"
ANSI/JPI 600LB 1 1/2B
ANSI/JPI 600LB 2B
Carbon steel
JIS 10K 40A
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
JIS 63K 40A
JIS 63K 50A
ANSI/JPI 150LB 1 1/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 1 1/2"
ANSI/JPI 300LB 2"
ANSI/JPI 600LB 1 1/2B
ANSI/JPI 600LB 2B
None
40A, 1 1/2B
(Wafer type)
50A, 2B
Direct mounting adapter connection (* 1)
<Span limit [kPa] {m bar}>
3........32(30...320)
13......130(130...1300)
50......500(500...5000)
<Material/diapharagm extension>
Diaphragm
Flange face
Diaphragm extension(mm)
316L stainless steel 316 stainless steel
0
316L stainless steel 316 stainless steel
50
316L stainless steel 316 stainless steel
100
(*2)
316L stainless steel 316 stainless steel
150
316L stainless steel 316 stainless steel
200
316L stainless steel 316 stainless steel
0
+Au coating
Hastelloy-C
316 stainless steel
0
Hastelloy-C
Hastelloy-C
0
0
Monel
Monel
Tantalum
Tantalum
Note 1: (*1)
Note 2: (*2)
Note
F KX
5
9 10 11 12 13
14 15 16 17 18 19 20
21
Digit No.
of code
5
6
7
8
S
T
V
W
Note 1
0
1
2
3
4
5
6
7
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V
W
X
Y
3
5
6
Note 2
V
A
B
C
D
J
W
H
M
T
Direct mounting adapter type is specified at 16th to 20th digit.
Direct mounting adapter is available only for 7th digit code "V".
Diaphragm extension is available only for 2" (50A) flanges.
5
FKX...5
1 2 3 4 5 6 7 8
Digit
9
10
11
12
13
14
Description
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale (*7)
None
Analog, custom scale
None
Analog, double scale(Linear and sq.root)
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale (*7)
Yes
Analog, custom scale
Yes
Analog, double scale(Linear and sq.root)
Yes
Digital, 0 to 100% linear scale
None
Digital, custom scale
None
Digital, 0 to 100% square root
None
Digital, 0 to 100% linear scale
Yes
Digital, custom scale
Yes
Digital, 0 to 100% square root
Yes
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
None
Digital, custom scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% square root scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Yes
Digital, custom scale
(Local configurator unit with LCD display)
Yes
Digital, 0 to 100% square root scale
(Local configurator unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*9)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*12)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*12)
ATEX Flameproof (*11)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*11)
IECEx Scheme, Flameproof (*11)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*12)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof) (*10)
NEPSI, Intrinsic safety (Entity)
NEPSI, Combined of flameproof and intrinsic safety (*10)
<Capillary and mounting bracket>
mounting bracket Capillary
armor of capillary
Stainless steel
1.5m
PE
Stainless steel
3m
PE
Stainless steel
5m
PE
Stainless steel
6m
PE
(*4)
Stainless steel
7m
PE
Stainless steel
8m
PE
Stainless steel
10m
PE
Stainless steel
1.5m
Stainless steel
Stainless steel
3m
Stainless steel
Stainless steel
5m
Stainless steel
Stainless steel
6m
Stainless steel
Stainless steel
7m
Stainless steel
Stainless steel
8m
Stainless steel
Stainless steel
10m
Stainless steel
<Options>
Stainless steel elec. housing Coating of cell
Extra ss tag plate
None
None
None
Yes
None
None
None (*3)
None
Yes
Yes
None
Yes
None
Yes
Yes
(*8)
Yes
Yes
Yes
<Treatment/Fill fluid>
Treatment
Fill fluid
Standard
Silicone oil (for general use)
Fluorinated oil
Standard
Degreasing
Silicone oil
Fluorinated oil (7th digit code "V", "W", "A", "B", "C" and "D")
Oxygen service
Chlorine service
Fluorinated oil (7th digit code "H" and "T")
High temp. 250°C
Silicone oil (7th digit code "V", "W", "A", "B", "C", "D" and "H")
High temp. and vacuum (250°C) Silicone oil (7th digit code "V", "W", "A", "B", "C" and "D")
<Teflon membrane>
None
Yes (Available for 7th digit code "V", "J", "W".
Not available for 5th digit code "Y" and 13th digit code "H", "S".)
Note 3: (*3)
Note 4: (*4)
Note 7: (*7)
6
Note
F KX
9 10 11 12 13
14 15 16 17 18 19 20
5
0
21
Digit No.
of code
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
1
Note7
Note7
2
3
4
5
6
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
Note 9
Note 12
Note 12
Note 11
Note 11
Note 11
Note 12
Note 10
Note 10
D
E
L
F
M
N
P
Q
R
S
T
V
W
X
Note4
Y
B
M
N
P
Q
Note3
Note8
Note8
Y
W
G
A
D
H
S
Note 13
Note 13
Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select "Yes".
Available for 13th digit code "Y", "W", "G", "A" and "D".
In case of squre root output mode,
squre root scale is not available.
Y
C
Note 8:
Note 9:
Note 10:
Note 11:
Note 12:
Note 13:
(*8)
(*9)
(*10)
(*11)
(*12)
(*13)
Not available for 10th digit code "C".
Available for 4th digit code "S".
Not available for 4th digit code "8", "W".
Available for 4th digit code "6", "8", "T", "W".
Available for 4th digit code "6", "T".
Treatment: Standard.
Specifications of Connecting pipe less adapter {for 15, 20A (1/2, 3/4") connection} and others
Note 1. When odering the instrument with connecting pipe less adapter, specify “Y” in the 5th digit of Code Symbol, and
specify 16th digit to 20th digit.
When odering the instrument without connecting pipe less adapter, nothing should be filled in the 16th to 20th digit.
2. Unless otherwise described in the specifications, leave the 21st digit blank.
1 2 3 4 5 6 7 8
Digit
Description
Note
16, 17 <Process connection (connecting pipe less adapter)>
JIS 10K 15A
JIS 10K 20A
JIS 20K 15A
JIS 20K 20A
JIS 30K 15A
JIS 30K 20A
ANSI/JPI 150LB 1/2"
ANSI/JPI 150LB 3/4"
ANSI/JPI 300LB 1/2"
ANSI/JPI 300LB 3/4"
Screw connection Rc1/2
Screw connection Rc3/4
Screw connection Rc1/2 - 14NPT
Screw connection Rc3/4 - 14NPT
18
<Material (connecting pipe less adapter)> (*5)
Note 5
Adapter
Bolts/nuts
(* 5)
316 Stainless Steel
Cr-Mo steel/carbon steel
19
<Vent/drain (for connecting pipe less adapter)>
Standard
Long type
20
<Gasket (for connecting pipe less adapter)>
Standard (Teflon) (Only Y, W, G, A and D can be specified on 13th digit).
For high temperature (spiral gasket) (Only H and S can be
specified on 13th digit).
21
Note 6
<Other options> (*6)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
F KX
5
9 10 11 12 13
14 15 16 17 18 19 20
21
0
Digit No.
of code
1 1
1 2
2 1
2 2
3 1
3 2
1H
1 T
2H
2 T
SR
S 2
SN
ST
W
A
N
1
2
H
J
K
L
T
U
V
Note 5: (*5) For connection of transmitter receiving pressure unit and connecting pipe less adapter
Note 6: (*6) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
7
FKX...5
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is
occurred in the transmitter.
Hold / Overscale / Underscale
Unless otherwise specified, output hold function is supplied.
4. Output mode (linear or square root output)
Unless otherwise specified, output mode is linear.
5. Indication method (indicated value and unit) in case of the
actual scale (code D, H, P, S, 2, 5 on 9th digit).
6. Tag No. (up to 14 alphanumerical characters), if required.
8
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: L type>
IN CASE OF 4TH DIGIT CODE S, V, W
MTG. PIPE JIS 50A (2B)
ZERO ADJ. SCREW
φ81
103
103
φ81
8
10
IN CASE OF 4TH DIGIT CODE T
38
U-BOLT M8
57
B CONDUIT CONN.
37
195
(21)
(11)
4 HOLES 9 DIA.
WITH ANALOG IND.
WITH DIGITAL IND.
N HOLES h DIA
φ
E
P
φ48±1
φF
φ49
φE
φD
INNER OF GASKET
FLANGE
126
t
41
φ15
43
M
L
DETAIL B
(CONDUIT. CONN.)
242
20
EARTH TERMINAL
K
2-M6 SCREW DEPTH 9
INNER OF GASKET
221
Q
20
2-M8×12
S
<WAFER TYPE>
Q
60
71
5th digit of the
code symbols
φD
0, G
1, H
2, J
3, K
4, L
5, M
6, N
7, P
A, Q
B, R
C, S
D, T
E, U
F, V
140
155
140
155
160
165
175
185
127
152
156
165
156
165
φE
105
120
105
120
120
130
130
145
95.4
120.6
114.3
127
114.3
127
62
70
120
φF
CorrosionStandard
resistant
materials
specification materials
specification
Note 1
Note 2
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
t
36
36
38
38
42
42
52
54
37.5
39.5
41
42.5
42.5
45.5
P
N-φh
4-19
4-19
4-19
8-19
4-23
8-19
4-25
8-23
4-16
4-20
4-23
8-20
4-23
8-20
60
71
60
71
60
71
60
71
60
71
60
71
60
71
FLANGE
JIS-10K-40A
JIS-10K-50A
JIS-20K-40A
JIS-20K-50A
JIS-30K-40A
JIS-30K-50A
JIS-63K-40A
JIS-63K-50A
ANSI/JPI-150LB-1 1/2B
ANSI/JPI-150LB-2B
ANSI/JPI-300LB-1 1/2B
ANSI/JPI-300LB-2B
ANSI/JPI-600LB-1 1/2B
ANSI/JPI-600LB-2B
Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W.
Note2) In case of the 7th digit of type code is H, M, T.
CONNECTION DIAGRAM
<SS TAG PLATE>
7th digit of the
code symbols
L
V, W, J, H, M, T
A
B
C
D
0
50
100
150
200
75
12.7
13.7
14.2
14.7
15.2
∼
∼
∼
∼
∼
D, Q
E, R
L, S
1.5
3
5
F, T
6
M, V
conduit conn.
4th digit of the
code symbols
18.2
29.2
29.7
30.2
30.7
S
T
J
K
M
G1/2
18
2
1/2-14NPT 16
V
W
11th digit of the
code symbols S (m)
4
Pg13.5
10.5
4.5
M20×1.5
16
4
TABLE 1
7
N, W
8
P, X
10
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
G1/2
DETAIL C
φ13
−/CK− CK+
19
106
20
MASS. APPROX.
(kg)
17
40A, 1 1/2B
50A, 2B
+
S
H.P.
L.P.
φ33.5
φF
φ49
J
SEE TABLE1
"C" CONDUIT CONN.
G1/2
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
9
FKX...5
<AMP. case: T type>
IN CASE OF 4TH DIGIT CODE 5, 7, 8
(21)
(11)
38
U-BOLT M8
ZERO ADJ. SCREW
φ81
8
100
IN CASE OF 4TH DIGIT CODE 6
10
EARTH TERMINAL
100
MTG. PIPE JIS 50A (2B)
57
37
B CONDUIT CONN.
WITH ANALOG IND.
208
WITH DIGITAL IND.
4 HOLES 9 DIA.
N HOLES h DIA
φ
E
P
φ48±1
φF
φ49
φE
φD
INNER OF GASKET
FLANGE
20
242
t
L
DETAIL B
(CONDUIT. CONN.)
127
φ15
K
M
20
2-M6 SCREW DEPTH 9
J
SEE TABLE1
Q
φ49
φF
248
INNER OF GASKET
20
2-M8×12
S
<WAFER TYPE>
Q
60
71
40A, 1 1/2B
50A, 2B
5th digit of the
code symbols
φD
0, G
1, H
2, J
3, K
4, L
5, M
6, N
7, P
A, Q
B, R
C, S
D, T
E, U
F, V
140
155
140
155
160
165
175
185
127
152
156
165
156
165
φE
105
120
105
120
120
130
130
145
95.4
120.6
114.3
127
114.3
127
62
70
120
φF
CorrosionStandard
resistant
materials
specification materials
specification
Note 1
Note 2
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
73
84
100
84
t
36
36
38
38
42
42
52
54
37.5
39.5
41
42.5
42.5
45.5
P
N-φh
4-19
4-19
4-19
8-19
4-23
8-19
4-25
8-23
4-16
4-20
4-23
8-20
4-23
8-20
60
71
60
71
60
71
60
71
60
71
60
71
60
71
FLANGE
JIS-10K-40A
JIS-10K-50A
JIS-20K-40A
JIS-20K-50A
JIS-30K-40A
JIS-30K-50A
JIS-63K-40A
JIS-63K-50A
ANSI/JPI-150LB-1 1/2B
ANSI/JPI-150LB-2B
ANSI/JPI-300LB-1 1/2B
ANSI/JPI-300LB-2B
ANSI/JPI-600LB-1 1/2B
ANSI/JPI-600LB-2B
Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W.
Note2) In case of the 7th digit of type code is H, M, T.
CONNECTION DIAGRAM
<SS TAG PLATE>
−/CK− CK+
75
+
20
10
S
H.P.
L.P.
7th digit of the
code symbols
L
V, W, J, H, M, T
A
B
C
D
0
50
100
150
200
11th digit of the
code symbols S (m)
D, Q
E, R
L, S
1.5
3
5
F, T
6
M, V
7
N, W
8
P, X
10
MASS. APPROX.
(kg)
12.7
13.7
14.2
14.7
15.2
∼
∼
∼
∼
∼
18.2
29.2
29.7
30.2
30.7
4th digit of the
code symbols
5
6
conduit conn.
J
K
G1/2
18
2
1/2-14NPT 16
4
M
7
Pg13.5
10.5
4.5
8
M20×1.5
16
4
TABLE 1
<AMP. case: L type> with direct mount adaptor (screw connection type)
IN CASE OF 4TH DIGIT CODE S, V, W
ZERO ADJ. SCREW
MTG. PIPE JIS 50A (2B)
38
U-BOLT M8
57
B CONDUIT CONN.
37
WITH ANALOG IND.
(21)
(11)
195
φ81
103
φ81
103
8
10
IN CASE OF 4TH DIGIT CODE T
WITH DIGITAL IND.
4 HOLES 9 DIA.
S
φ84
S
25
LOW PRESS. CONN. ”
D”
HIGH PRESS. CONN. ”
D”
VENT/DRAIN PLUG
20
23
242
126
41
43
DETAIL B
(CONDUIT. CONN.)
φ15
K
M
EARTH TERMINAL
J
4th digit of the
code symbols
S
T
221
SEE TABLE1
2-M8×12
conduit conn.
J
K
G1/2
18
2
1/2-14NPT 16
4
M
V
Pg13.5
10.5
4.5
W
M20×1.5
16
4
62
70
120
11th digit of the
code symbols S (m)
TABLE 1
16th digit of the 17th digit of the
code symbols
code symbols
Press. conn. D
D, Q
E, R
L, S
1.5
3
5
6
S
R
Rc 1/2
F, T
S
N
1/2-14NPT
M, V
7
S
2
Rc 3/4
N, W
8
S
T
3/4-14NPT
P, X
10
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
CONNECTION DIAGRAM
<SS TAG PLATE>
10th digit code C (Cable gland type)
NOTE1)
G1/2
φ33.5
φ13
−/CK− CK+
75
19
106
20
17
+
DETAIL C
"C" CONDUIT CONN.
G1/2
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
11
FKX...5
<AMP. case: T type> with direct mount adaptor (screw connection type)
IN CASE OF 4TH DIGIT CODE 5, 7, 8
IN CASE OF 4TH DIGIT CODE 6
ZERO ADJ. SCREW
φ81
100
100
EARTH TERMINAL
8
10
MTG. PIPE JIS 50A (2B)
(21)
(11)
38
U-BOLT M8
57
B CONDUIT CONN.
37
208
WITH ANALOG IND.
4 HOLES 9 DIA.
WITH DIGITAL IND.
S
φ84
S
25
LOW PRESS. CONN. ”
D”
HIGH PRESS. CONN. ”
D”
VENT/DRAIN PLUG
20
23
242
127
DETAIL B
(CONDUIT. CONN.)
20
248
K
M
φ15
J
SEE TABLE1
4th digit of the
code symbols
5
6
conduit conn.
J
K
M
G1/2
18
2
1/2-14NPT 16
7
8
2-M8×12
4
Pg13.5
10.5
4.5
M20×1.5
16
4
11th digit of the
S (m)
code symbols
TABLE 1
16th digit of the 17th digit of the
code symbols
code symbols
D, Q
E, R
L, S
Press. conn. D
S
R
Rc 1/2
F, T
6
S
N
1/2-14NPT
M, V
7
S
2
Rc 3/4
N, W
8
S
T
3/4-14NPT
P, X
10
CONNECTION DIAGRAM
<SS TAG PLATE>
−/CK− CK+
75
+
20
12
1.5
3
5
62
70
120
<AMP. case: L type> with direct mount adaptor
IN CASE OF 4TH DIGIT CODE S, V, W
ZERO ADJ. SCREW
IN CASE OF 4TH DIGIT CODE T
57
φ81
B CONDUIT CONN.
38
U-BOLT M8
103
φ81
103
8
10
MTG. PIPE JIS 50A (2B)
37
(21)
(11)
195
4 HOLES 9 DIA.
WITH ANALOG IND.
WITH DIGITAL IND.
φ84
t
N HOLES h DIA.
S
S
25
φF φE φD
80
20
VENT/DRAIN PLUG
242
126
41
43
DETAIL B
(CONDUIT. CONN.)
φ15
K
M
EARTH TERMINAL
J
conduit conn.
4th digit of the
code symbols
S
T
J
K
M
G1/2
18
2
11th digit of the
S (m)
code symbols
D, Q
E, R
2-M8×12
1.5
3
4
L, S
V
Pg13.5
10.5
4.5
F, T
6
M, V
7
W
M20×1.5
16
4
1/2-14NPT 16
221
SEE TABLE1
5
N, W
8
P, X
10
62
70
120
TABLE 1
16th digit of the 17th digit of the
code symbols
code symbols
φD
φE
φF
t
N-φh
FLANGE
1
1
95
70
51
12
4-15
JIS-10K-15A
1
2
100
75
56
14
4-15
JIS-10K-20A
2
1
95
70
51
14
4-15
JIS-20K-15A
2
2
100
75
56
16
4-15
JIS-20K-20A
3
1
115
80
55
18
4-19
3
2
120
85
60
18
4-19
JIS-30K-20A
1
H
89
60.3
34.9
11.5
4-16
ANSI/JPI-150LB-1 1/2B
1
T
98
69.9
42.9
13
4-16
ANSI/JPI-150LB-2 3/4B
2
H
95
66.7
34.9
14.5
4-16
ANSI/JPI-300LB-1 1/2B
2
T
117
82.5
42.9
16
4-20
ANSI/JPI-300LB-2 3/4B
JIS-30K-15A
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
CONNECTION DIAGRAM
<SS TAG PLATE>
10th digit code C (Cable gland type)
NOTE1)
G1/2
φ33.5
φ13
−/CK− CK+
75
19
106
20
17
+
DETAIL C
"C" CONDUIT CONN.
G1/2
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
13
FKX...5
<AMP. case: T type> with direct mount adaptor
IN CASE OF 4TH DIGIT CODE 5, 7, 8
8
100
38
U-BOLT M8
57
ZERO ADJ. SCREW
φ81
10
EARTH TERMINAL
100
IN CASE OF 4TH DIGIT CODE 6
MTG. PIPE JIS 50A (2B)
(21)
(11)
37
WITH ANALOG IND.
208
4 HOLES 9 DIA.
B CONDUIT CONN.
φ84
t
WITH DIGITAL IND.
N HOLES h DIA.
S
25
φF φE φD
80
20
VENT/DRAIN PLUG
242
127
DETAIL B
(CONDUIT. CONN.)
21
248
K
M
φ15
J
SEE TABLE1
conduit conn.
4th digit of the
code symbols
5
6
K
M
G1/2
18
2
1/2-14NPT 16
7
8
J
Pg13.5
M20×1.5
10.5
16
2-M8×12
11th digit of the
code symbols S (m)
D, Q
E, R
L, S
4
1.5
3
5
F, T
4.5
4
62
6
M, V
7
70
N, W
8
P, X
10
120
TABLE 1
16th digit of the 17th digit of the
code symbols
code symbols
φD
φE
φF
t
N-φh
FLANGE
1
1
95
70
51
12
4-15
JIS-10K-15A
1
2
100
75
56
14
4-15
JIS-10K-20A
2
1
95
70
51
14
4-15
JIS-20K-15A
2
2
100
75
56
16
4-15
JIS-20K-20A
3
1
115
80
55
18
4-19
3
2
120
85
60
18
4-19
JIS-30K-20A
1
H
89
60.3
34.9
11.5
4-16
ANSI/JPI-150LB-1 1/2B
98
69.9
JIS-30K-15A
1
T
42.9
13
4-16
ANSI/JPI-150LB-2 3/4B
2
H
95
66.7
34.9
14.5
4-16
ANSI/JPI-300LB-1 1/2B
2
T
117
82.5
42.9
16
4-20
ANSI/JPI-300LB-2 3/4B
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
14
S
TABLE 2
Authorities
ATEX
Intrinsic safety
Authorities
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
Tamb
A,B,C,D,J
Y,G,H,S
−40°C to +85°C
L,P,M,1,2,3
Y,G,H,S
−20°C to +80°C
Q,S,N,4,5,6
Y,G,H,S
−20°C to +60°C
E,F,G,H,K
Y,G,H,S
−40°C to +60°C
W,A,D
−10°C to +60°C
-
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester),Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameter:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
NEPSI
ATEX
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
13th digit
9th digit
Note) “Seal Not Required” enclosure is allowed.
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp.=+120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Tamb
Type n
Nonincendive
Authorities
ATEX
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
13th digit
9th digit
Flameproof
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
A,B,C,D,J
Y,G,H,S
−40°C to +85°C
L,P,M,1,2,3
Y,G,H,S
−20°C to +80°C
Q,S,N,4,5,6
Y,G,H,S
−20°C to +60°C
Model code
9th digit
13th digit
E,F,G,H,K
Y,G,H,S
−40°C to +60°C
A,B,C,D,J
Y,G,H,S
−40°C to +85°C
−
W,A,D
−10°C to +60°C
L,P,M,1,2,3
Y,G,H,S
−20°C to +80°C
Q,S,N,4,5,6
Y,G,H,S
−20°C to +60°C
E,F,G,H,K
Y,G,H,S
−40°C to +60°C
−
W,A,D
−10°C to +60°C
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Tamb
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
15
FKX...5
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan