SMALL FLANGE REMOTE SEAL TYPE DIFFERENTIAL PRESSURE TRANSMITTER FKX...5 DATA SHEET The FCX -AIII small fl ange remote seal type differential pressure transmitter accurately measures differential pressure, liquid level or gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with stateof-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. 2. 3. 4. 5. 6. 7. Directly connectable to 1-1/2 in and 2in flanges The transmitter is connectable to 1-1/2 in and 2in pipes without a reducer. Flow measurement without impulse piping 1/2 in and 3/4 in flange size is also available. This differential pressure transmitter allows connection to 1/2 in and 3/4 in flanges of a general size for the orifice tap, which eliminates the need of using a impulse piping. Problems with the impulse piping, such as clogging, leaks or corrosion can be solved. In addition, the following process connection is also available. Screw connection 1/2-14NPT, 3/4-14NPT, Rc 1/2, Rc 3/4 Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. Fuji/HART® bilingual communications protocol FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX -AIII. Application flexibility Various options that render the FCX -AIII suitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5 -digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum seals Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 8. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type Static pressure Span limit [kPa] (m bar} Min. F KX 3 F KX 5 F KX 6 Up to flange rating 3 { 30} 13 {130} 50 {500} Max. 32 { 320 } 130 { 1300 } 500 {5000 } Range limit [kPa] {m bar} +/− 32 {+/− 320} +/− 130 {+/− 1300} +/− 500 {+/− 5000} Maximum static pressure limit for screw connction type: 4.2MPa − Lower limit of static pressure (vacuum limit), Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: Atmospheric pressure − The maximum span of each sensor can be converted to different units using factors as below. 1MPa =103kPa=10bar=10.19716kgf/cm2 =145.0377psi 1kPa=10mbar=101.976mmH2O=4.01463H2O − EDSX6-137h Date Aug. 10, 2011 FKX...5 Overrange limit: To maximum static pressure limit Output signal: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal. Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below [Ω] Load resistance 2000 1500 Temperature limit: Ambient: −15 to + 65°C (−15 to + 60°C for arrester option) (−10 to + 60°C for fluorinated oil fill transmitter) (−10 to + 60°C for silicone oil “H”, “S”) (−15 to + 45°C for capillary length more than 7m) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: 1474Ω R= E-10.5 (Imax+0.9)x10-3 13th digit of “Code symbols” Process temperature Fluorinated oil W, A and D −20 to 120°C Silicone oil H 577Ω −40 to 180°C 0 24V 10 45V 16.35 10.5V Power voltage (DC) 50 E[ V ] Note: For communication with HHC(1) (Model: FXW), min. of 250 is required. Hazardous locations: SEE TABLE2 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: −100% to +100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC(1) 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout 0 to 250°C S Operating area 250 3.2 0 to 250°C Y and G 1000 500 Probable over range Output limits conforming to NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC(1). Lower limit of static press. Atmospheric pressure 2.7kPa abs {20mmHg abs} Storage: −40 to +70°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1− 4), for FCX–AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Linear v v v v Square root v v v v Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — Output mode Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326-1: 2006 (Note) 2 Fill fluid (1) HHC: Hand Held Communicator Static pressure effect: Zero shift; 0.2% of URL/1MPa (10 bar) Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode and capillary length 3m. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: 0.25% of span For spans below 1/10 of URL: 0.1 x URL ± 0.17+0.08 % of span Span ( ) (Option) (Code; 21th digit H,K) For spans greater than 1/10 of URL: 0.1% of span For spans below 1/10 of URL: 0.1 x URL ± 0.05+0.05 % of span Span ( ) Stability: ±0.2% of upper range limit (URL) for 10 years. Temperature effect: Effects per 28°C change between the limits of −15°C and +65°C Zero shift: ±0.5%/28°C (x equal to 1/2 URL or more) URL Zero shift; ± (0.5 2 x )%/28°C Span shift: −0.2% of calibrated span /1MPa Overrange effect: Zero shift; 0.1% of URL for flange rating pressure Supply voltage effect: Less than 0.005% of calibrated span per 1V Update rate: 60 msec Step response: (without electrical damping) Time constant (at 23°C) 1.7 s Dead time 0.12 s Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M at 500V DC. Internal resistance for external field indicator: 12 or less (x less than 1/2 URL) Total shift; ±0.75%/28°C (x less than 1/2 URL or more) Total shift; ±(0.25 + 0.5 URL )%/28°C 2x (x less than 1/2 URL) (option) (Code; 21th digit J,K) Zero shift: ±0.5%/28°C (x equal to 1/6.5 URL or more) URL Zero shift; ± (0.5 )%/28°C 6.5 x (x less than 1/6.5 URL) Total shift; ±0.75%/28°C (x equal to 1/6.5 URL or more) URL Total shift; ±(0.25 + 0.5 )%/28°C 6.5 x (x less than 1/6.5 URL) Where, x: Calibrated span URL: Maximum span (Upper Range Limit) Note : Above specifications are based on the conditions that flanges and sensor unit are at the same temperature and in the same level. If temperature is different at flanges, capillary or sensor unit, output variation may increase. 3 FKX...5 Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: JIS 10K, 20K, 30K - 40, 50A 10K, 20K, 30K - 15, 20A (with Adapter) ANSI/JPI 150LB, 300LB -11/2", 2" 150LB, 300LB - 1/2", 3/4" (with Adapter) Screw connection (with Adapter); Rc1/2, Rc3/4, 1/2 - 14NPT, 3/4 - 14NPT Diaphragm extension: 0, 50, 100, 150, or 200mm as specified. (See model code. Extended diaphragm is available only with 316L stainless steel diaphragm) Process-wetted parts material: Diaphragm:316L stainless steel, Hastelloy-C, Monel or Tantalum Flange face: 316 stainless steel, HastelloyC lining Monel lining, or Tantalum lining Extension: 316 stainless steel Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyester coating (standard), or 316 stainless steel (ASTM CF8M), as specified. Capillary: In case of 11th code “D. E. L.”, PE armored stainless steel. In case of 11th code “Q. R. S”, stainless steel armored stainless steel. Mounting flange: 304 stainless steel or carbon steel. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 12.7 to 30.7kg without options. Add; 0.5kg for mounting bracket 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm Optional features Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs). Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1. Optional tag plate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. Filled liquid: Silicone (Code Y,G) [kPa abs] {m bar abs} Silicone (Code S) 101 {1010} Operating pressure Physical specifications 53.3 {533} Operating area 13.3 {133} Non-operating area 2.7 {27} –40 0 60 85 120 180 Process temperature 230 250 [°C ] Fig. 1 Relation between process temperature and operating pressure ACCESSORIES Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) 4 CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 5 6 7 Description <Connections> <Conduit connection> <Case type> G1/2 T type 1/2-14NPT T type Pg 13.5 T type M20 × 1.5 T type G1/2 L type 1/2-14NPT L type Pg 13.5 L type M20 × 1.5 L type <Flange> Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2B ANSI/JPI 600LB 2B Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2B ANSI/JPI 600LB 2B None 40A, 1 1/2B (Wafer type) 50A, 2B Direct mounting adapter connection (* 1) <Span limit [kPa] {m bar}> 3........32(30...320) 13......130(130...1300) 50......500(500...5000) <Material/diapharagm extension> Diaphragm Flange face Diaphragm extension(mm) 316L stainless steel 316 stainless steel 0 316L stainless steel 316 stainless steel 50 316L stainless steel 316 stainless steel 100 (*2) 316L stainless steel 316 stainless steel 150 316L stainless steel 316 stainless steel 200 316L stainless steel 316 stainless steel 0 +Au coating Hastelloy-C 316 stainless steel 0 Hastelloy-C Hastelloy-C 0 0 Monel Monel Tantalum Tantalum Note 1: (*1) Note 2: (*2) Note F KX 5 9 10 11 12 13 14 15 16 17 18 19 20 21 Digit No. of code 5 6 7 8 S T V W Note 1 0 1 2 3 4 5 6 7 A B C D E F G H J K L M N P Q R S T U V W X Y 3 5 6 Note 2 V A B C D J W H M T Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code "V". Diaphragm extension is available only for 2" (50A) flanges. 5 FKX...5 1 2 3 4 5 6 7 8 Digit 9 10 11 12 13 14 Description <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, 0 to 100% sq. root scale (*7) None Analog, custom scale None Analog, double scale(Linear and sq.root) None None Yes Analog, 0 to 100% linear scale Yes Analog, 0 to 100% sq. root scale (*7) Yes Analog, custom scale Yes Analog, double scale(Linear and sq.root) Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% square root None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% square root Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD display) None Digital, custom scale (Local configurator unit with LCD display) None Digital, 0 to 100% square root scale (Local configurator unit with LCD display) None Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Yes Digital, custom scale (Local configurator unit with LCD display) Yes Digital, 0 to 100% square root scale (Local configurator unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*9) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*12) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*12) ATEX Flameproof (*11) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*11) IECEx Scheme, Flameproof (*11) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*12) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) (*10) NEPSI, Intrinsic safety (Entity) NEPSI, Combined of flameproof and intrinsic safety (*10) <Capillary and mounting bracket> mounting bracket Capillary armor of capillary Stainless steel 1.5m PE Stainless steel 3m PE Stainless steel 5m PE Stainless steel 6m PE (*4) Stainless steel 7m PE Stainless steel 8m PE Stainless steel 10m PE Stainless steel 1.5m Stainless steel Stainless steel 3m Stainless steel Stainless steel 5m Stainless steel Stainless steel 6m Stainless steel Stainless steel 7m Stainless steel Stainless steel 8m Stainless steel Stainless steel 10m Stainless steel <Options> Stainless steel elec. housing Coating of cell Extra ss tag plate None None None Yes None None None (*3) None Yes Yes None Yes None Yes Yes (*8) Yes Yes Yes <Treatment/Fill fluid> Treatment Fill fluid Standard Silicone oil (for general use) Fluorinated oil Standard Degreasing Silicone oil Fluorinated oil (7th digit code "V", "W", "A", "B", "C" and "D") Oxygen service Chlorine service Fluorinated oil (7th digit code "H" and "T") High temp. 250°C Silicone oil (7th digit code "V", "W", "A", "B", "C", "D" and "H") High temp. and vacuum (250°C) Silicone oil (7th digit code "V", "W", "A", "B", "C" and "D") <Teflon membrane> None Yes (Available for 7th digit code "V", "J", "W". Not available for 5th digit code "Y" and 13th digit code "H", "S".) Note 3: (*3) Note 4: (*4) Note 7: (*7) 6 Note F KX 9 10 11 12 13 14 15 16 17 18 19 20 5 0 21 Digit No. of code A B C D J E F G H K L P M Q S N 1 Note7 Note7 2 3 4 5 6 A C G D H V X K P M R T E J F S U Note 9 Note 12 Note 12 Note 11 Note 11 Note 11 Note 12 Note 10 Note 10 D E L F M N P Q R S T V W X Note4 Y B M N P Q Note3 Note8 Note8 Y W G A D H S Note 13 Note 13 Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". Available for 13th digit code "Y", "W", "G", "A" and "D". In case of squre root output mode, squre root scale is not available. Y C Note 8: Note 9: Note 10: Note 11: Note 12: Note 13: (*8) (*9) (*10) (*11) (*12) (*13) Not available for 10th digit code "C". Available for 4th digit code "S". Not available for 4th digit code "8", "W". Available for 4th digit code "6", "8", "T", "W". Available for 4th digit code "6", "T". Treatment: Standard. Specifications of Connecting pipe less adapter {for 15, 20A (1/2, 3/4") connection} and others Note 1. When odering the instrument with connecting pipe less adapter, specify “Y” in the 5th digit of Code Symbol, and specify 16th digit to 20th digit. When odering the instrument without connecting pipe less adapter, nothing should be filled in the 16th to 20th digit. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 1 2 3 4 5 6 7 8 Digit Description Note 16, 17 <Process connection (connecting pipe less adapter)> JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 18 <Material (connecting pipe less adapter)> (*5) Note 5 Adapter Bolts/nuts (* 5) 316 Stainless Steel Cr-Mo steel/carbon steel 19 <Vent/drain (for connecting pipe less adapter)> Standard Long type 20 <Gasket (for connecting pipe less adapter)> Standard (Teflon) (Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). 21 Note 6 <Other options> (*6) High accuracy type Instruction manual attached Low temperature effect type Instruction manual attached H+J Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached Low temperature effect type Instruction manual unattached T+U Instruction manual unattached F KX 5 9 10 11 12 13 14 15 16 17 18 19 20 21 0 Digit No. of code 1 1 1 2 2 1 2 2 3 1 3 2 1H 1 T 2H 2 T SR S 2 SN ST W A N 1 2 H J K L T U V Note 5: (*5) For connection of transmitter receiving pressure unit and connecting pipe less adapter Note 6: (*6) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. 7 FKX...5 ORDERING INFORMATION When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale / Underscale Unless otherwise specified, output hold function is supplied. 4. Output mode (linear or square root output) Unless otherwise specified, output mode is linear. 5. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S, 2, 5 on 9th digit). 6. Tag No. (up to 14 alphanumerical characters), if required. 8 OUTLINE DIAGRAM (Unit:mm) <AMP. case: L type> IN CASE OF 4TH DIGIT CODE S, V, W MTG. PIPE JIS 50A (2B) ZERO ADJ. SCREW φ81 103 103 φ81 8 10 IN CASE OF 4TH DIGIT CODE T 38 U-BOLT M8 57 B CONDUIT CONN. 37 195 (21) (11) 4 HOLES 9 DIA. WITH ANALOG IND. WITH DIGITAL IND. N HOLES h DIA φ E P φ48±1 φF φ49 φE φD INNER OF GASKET FLANGE 126 t 41 φ15 43 M L DETAIL B (CONDUIT. CONN.) 242 20 EARTH TERMINAL K 2-M6 SCREW DEPTH 9 INNER OF GASKET 221 Q 20 2-M8×12 S <WAFER TYPE> Q 60 71 5th digit of the code symbols φD 0, G 1, H 2, J 3, K 4, L 5, M 6, N 7, P A, Q B, R C, S D, T E, U F, V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 φE 105 120 105 120 120 130 130 145 95.4 120.6 114.3 127 114.3 127 62 70 120 φF CorrosionStandard resistant materials specification materials specification Note 1 Note 2 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 t 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 P N-φh 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 60 71 60 71 60 71 60 71 60 71 60 71 60 71 FLANGE JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W. Note2) In case of the 7th digit of type code is H, M, T. CONNECTION DIAGRAM <SS TAG PLATE> 7th digit of the code symbols L V, W, J, H, M, T A B C D 0 50 100 150 200 75 12.7 13.7 14.2 14.7 15.2 ∼ ∼ ∼ ∼ ∼ D, Q E, R L, S 1.5 3 5 F, T 6 M, V conduit conn. 4th digit of the code symbols 18.2 29.2 29.7 30.2 30.7 S T J K M G1/2 18 2 1/2-14NPT 16 V W 11th digit of the code symbols S (m) 4 Pg13.5 10.5 4.5 M20×1.5 16 4 TABLE 1 7 N, W 8 P, X 10 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) G1/2 DETAIL C φ13 −/CK− CK+ 19 106 20 MASS. APPROX. (kg) 17 40A, 1 1/2B 50A, 2B + S H.P. L.P. φ33.5 φF φ49 J SEE TABLE1 "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. 9 FKX...5 <AMP. case: T type> IN CASE OF 4TH DIGIT CODE 5, 7, 8 (21) (11) 38 U-BOLT M8 ZERO ADJ. SCREW φ81 8 100 IN CASE OF 4TH DIGIT CODE 6 10 EARTH TERMINAL 100 MTG. PIPE JIS 50A (2B) 57 37 B CONDUIT CONN. WITH ANALOG IND. 208 WITH DIGITAL IND. 4 HOLES 9 DIA. N HOLES h DIA φ E P φ48±1 φF φ49 φE φD INNER OF GASKET FLANGE 20 242 t L DETAIL B (CONDUIT. CONN.) 127 φ15 K M 20 2-M6 SCREW DEPTH 9 J SEE TABLE1 Q φ49 φF 248 INNER OF GASKET 20 2-M8×12 S <WAFER TYPE> Q 60 71 40A, 1 1/2B 50A, 2B 5th digit of the code symbols φD 0, G 1, H 2, J 3, K 4, L 5, M 6, N 7, P A, Q B, R C, S D, T E, U F, V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 φE 105 120 105 120 120 130 130 145 95.4 120.6 114.3 127 114.3 127 62 70 120 φF CorrosionStandard resistant materials specification materials specification Note 1 Note 2 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 73 84 100 84 t 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 P N-φh 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 60 71 60 71 60 71 60 71 60 71 60 71 60 71 FLANGE JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B Note1) In case of the 7th digit of type code is V, A, B, C, D, J or W. Note2) In case of the 7th digit of type code is H, M, T. CONNECTION DIAGRAM <SS TAG PLATE> −/CK− CK+ 75 + 20 10 S H.P. L.P. 7th digit of the code symbols L V, W, J, H, M, T A B C D 0 50 100 150 200 11th digit of the code symbols S (m) D, Q E, R L, S 1.5 3 5 F, T 6 M, V 7 N, W 8 P, X 10 MASS. APPROX. (kg) 12.7 13.7 14.2 14.7 15.2 ∼ ∼ ∼ ∼ ∼ 18.2 29.2 29.7 30.2 30.7 4th digit of the code symbols 5 6 conduit conn. J K G1/2 18 2 1/2-14NPT 16 4 M 7 Pg13.5 10.5 4.5 8 M20×1.5 16 4 TABLE 1 <AMP. case: L type> with direct mount adaptor (screw connection type) IN CASE OF 4TH DIGIT CODE S, V, W ZERO ADJ. SCREW MTG. PIPE JIS 50A (2B) 38 U-BOLT M8 57 B CONDUIT CONN. 37 WITH ANALOG IND. (21) (11) 195 φ81 103 φ81 103 8 10 IN CASE OF 4TH DIGIT CODE T WITH DIGITAL IND. 4 HOLES 9 DIA. S φ84 S 25 LOW PRESS. CONN. ” D” HIGH PRESS. CONN. ” D” VENT/DRAIN PLUG 20 23 242 126 41 43 DETAIL B (CONDUIT. CONN.) φ15 K M EARTH TERMINAL J 4th digit of the code symbols S T 221 SEE TABLE1 2-M8×12 conduit conn. J K G1/2 18 2 1/2-14NPT 16 4 M V Pg13.5 10.5 4.5 W M20×1.5 16 4 62 70 120 11th digit of the code symbols S (m) TABLE 1 16th digit of the 17th digit of the code symbols code symbols Press. conn. D D, Q E, R L, S 1.5 3 5 6 S R Rc 1/2 F, T S N 1/2-14NPT M, V 7 S 2 Rc 3/4 N, W 8 S T 3/4-14NPT P, X 10 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) CONNECTION DIAGRAM <SS TAG PLATE> 10th digit code C (Cable gland type) NOTE1) G1/2 φ33.5 φ13 −/CK− CK+ 75 19 106 20 17 + DETAIL C "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. 11 FKX...5 <AMP. case: T type> with direct mount adaptor (screw connection type) IN CASE OF 4TH DIGIT CODE 5, 7, 8 IN CASE OF 4TH DIGIT CODE 6 ZERO ADJ. SCREW φ81 100 100 EARTH TERMINAL 8 10 MTG. PIPE JIS 50A (2B) (21) (11) 38 U-BOLT M8 57 B CONDUIT CONN. 37 208 WITH ANALOG IND. 4 HOLES 9 DIA. WITH DIGITAL IND. S φ84 S 25 LOW PRESS. CONN. ” D” HIGH PRESS. CONN. ” D” VENT/DRAIN PLUG 20 23 242 127 DETAIL B (CONDUIT. CONN.) 20 248 K M φ15 J SEE TABLE1 4th digit of the code symbols 5 6 conduit conn. J K M G1/2 18 2 1/2-14NPT 16 7 8 2-M8×12 4 Pg13.5 10.5 4.5 M20×1.5 16 4 11th digit of the S (m) code symbols TABLE 1 16th digit of the 17th digit of the code symbols code symbols D, Q E, R L, S Press. conn. D S R Rc 1/2 F, T 6 S N 1/2-14NPT M, V 7 S 2 Rc 3/4 N, W 8 S T 3/4-14NPT P, X 10 CONNECTION DIAGRAM <SS TAG PLATE> −/CK− CK+ 75 + 20 12 1.5 3 5 62 70 120 <AMP. case: L type> with direct mount adaptor IN CASE OF 4TH DIGIT CODE S, V, W ZERO ADJ. SCREW IN CASE OF 4TH DIGIT CODE T 57 φ81 B CONDUIT CONN. 38 U-BOLT M8 103 φ81 103 8 10 MTG. PIPE JIS 50A (2B) 37 (21) (11) 195 4 HOLES 9 DIA. WITH ANALOG IND. WITH DIGITAL IND. φ84 t N HOLES h DIA. S S 25 φF φE φD 80 20 VENT/DRAIN PLUG 242 126 41 43 DETAIL B (CONDUIT. CONN.) φ15 K M EARTH TERMINAL J conduit conn. 4th digit of the code symbols S T J K M G1/2 18 2 11th digit of the S (m) code symbols D, Q E, R 2-M8×12 1.5 3 4 L, S V Pg13.5 10.5 4.5 F, T 6 M, V 7 W M20×1.5 16 4 1/2-14NPT 16 221 SEE TABLE1 5 N, W 8 P, X 10 62 70 120 TABLE 1 16th digit of the 17th digit of the code symbols code symbols φD φE φF t N-φh FLANGE 1 1 95 70 51 12 4-15 JIS-10K-15A 1 2 100 75 56 14 4-15 JIS-10K-20A 2 1 95 70 51 14 4-15 JIS-20K-15A 2 2 100 75 56 16 4-15 JIS-20K-20A 3 1 115 80 55 18 4-19 3 2 120 85 60 18 4-19 JIS-30K-20A 1 H 89 60.3 34.9 11.5 4-16 ANSI/JPI-150LB-1 1/2B 1 T 98 69.9 42.9 13 4-16 ANSI/JPI-150LB-2 3/4B 2 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-300LB-1 1/2B 2 T 117 82.5 42.9 16 4-20 ANSI/JPI-300LB-2 3/4B JIS-30K-15A OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) CONNECTION DIAGRAM <SS TAG PLATE> 10th digit code C (Cable gland type) NOTE1) G1/2 φ33.5 φ13 −/CK− CK+ 75 19 106 20 17 + DETAIL C "C" CONDUIT CONN. G1/2 CABLE GLAND NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. 13 FKX...5 <AMP. case: T type> with direct mount adaptor IN CASE OF 4TH DIGIT CODE 5, 7, 8 8 100 38 U-BOLT M8 57 ZERO ADJ. SCREW φ81 10 EARTH TERMINAL 100 IN CASE OF 4TH DIGIT CODE 6 MTG. PIPE JIS 50A (2B) (21) (11) 37 WITH ANALOG IND. 208 4 HOLES 9 DIA. B CONDUIT CONN. φ84 t WITH DIGITAL IND. N HOLES h DIA. S 25 φF φE φD 80 20 VENT/DRAIN PLUG 242 127 DETAIL B (CONDUIT. CONN.) 21 248 K M φ15 J SEE TABLE1 conduit conn. 4th digit of the code symbols 5 6 K M G1/2 18 2 1/2-14NPT 16 7 8 J Pg13.5 M20×1.5 10.5 16 2-M8×12 11th digit of the code symbols S (m) D, Q E, R L, S 4 1.5 3 5 F, T 4.5 4 62 6 M, V 7 70 N, W 8 P, X 10 120 TABLE 1 16th digit of the 17th digit of the code symbols code symbols φD φE φF t N-φh FLANGE 1 1 95 70 51 12 4-15 JIS-10K-15A 1 2 100 75 56 14 4-15 JIS-10K-20A 2 1 95 70 51 14 4-15 JIS-20K-15A 2 2 100 75 56 16 4-15 JIS-20K-20A 3 1 115 80 55 18 4-19 3 2 120 85 60 18 4-19 JIS-30K-20A 1 H 89 60.3 34.9 11.5 4-16 ANSI/JPI-150LB-1 1/2B 98 69.9 JIS-30K-15A 1 T 42.9 13 4-16 ANSI/JPI-150LB-2 3/4B 2 H 95 66.7 34.9 14.5 4-16 ANSI/JPI-300LB-1 1/2B 2 T 117 82.5 42.9 16 4-20 ANSI/JPI-300LB-2 3/4B CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 14 S TABLE 2 Authorities ATEX Intrinsic safety Authorities Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual Tamb A,B,C,D,J Y,G,H,S −40°C to +85°C L,P,M,1,2,3 Y,G,H,S −20°C to +80°C Q,S,N,4,5,6 Y,G,H,S −20°C to +60°C E,F,G,H,K Y,G,H,S −40°C to +60°C W,A,D −10°C to +60°C - Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester),Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameter: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI ATEX Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 13th digit 9th digit Note) “Seal Not Required” enclosure is allowed. TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp.=+120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C Tamb Type n Nonincendive Authorities ATEX Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 13th digit 9th digit Flameproof Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X A,B,C,D,J Y,G,H,S −40°C to +85°C L,P,M,1,2,3 Y,G,H,S −20°C to +80°C Q,S,N,4,5,6 Y,G,H,S −20°C to +60°C Model code 9th digit 13th digit E,F,G,H,K Y,G,H,S −40°C to +60°C A,B,C,D,J Y,G,H,S −40°C to +85°C − W,A,D −10°C to +60°C L,P,M,1,2,3 Y,G,H,S −20°C to +80°C Q,S,N,4,5,6 Y,G,H,S −20°C to +60°C E,F,G,H,K Y,G,H,S −40°C to +60°C − W,A,D −10°C to +60°C Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH CSA Tamb Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH 15 FKX...5 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan