FUJI EDSX7-58

FCX – AX SERIES
SMALL FLANGE LEVEL TRANSMITTER
FHY, FKY...3
DATA SHEET
The FCX –AX Series small flange level transmitter accurately measures liquid level and transmits a proportional 4
to 20mA signal. The transmitter utilizes a unique
micromachined capacitance silicon sensor with state-of-theart microprocessor technology to provide exceptional performance and functionality.
FEATURES
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
7. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW (HHC) version
5.3.)
8. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as
wet calibration.
SPECIFICATIONS
Functional specifications
Type:
Model FHY: 4 to 20mA
Model FKY: 4 to 20mA with digital signal
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Static
pressure
F Y
5
F Y
6



1. Directly connectable to 1-1/2 in. and 2 in. flanges
The transmitter is connectable to 1-1/2 in. and 2 in. pipes
without a reducer.
2. Minimum environmental influence
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Replaceable Communication Module
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX–AX
transmitter very unique in design. In case of change in
communication protocl, all that needs to be done is just
to replace the module and the transmitter gets upgraded
to the new version
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART compatible devices can communicate with FCX–AX series transmitters.
5. Application flexibility
Various options that render the FCX–AX suitable for
almost any process applications include:
— Analog indicator at either the electronics side or terminal side
— Full range of hazardous area approvals
— Built-in RFI filter and lightning arrester
— 41/2 digits LCD meter
— Stainless steel electronics housing
— Wide selection of materials
— High temperature, vacuum service.
6. Programmable output Linearization Function
In addition to Linear and Square Root, output signal can
be freely programmable.
(Up to 14 compensated points at approximation.)
Up to
flange
rating
Span limit [kPa] {m bar}
Min.
Max.
FHY
FKY
FHY/FKY
13
{130}
50
{500}
3
{30}
12.5
{125}
130
{1300}
500
{5000}
Range limit
[kPa] {m bar}
+/– 130
{ +/– 1300}
+/– 500
{ +/– 5000}
— Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig . 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60 °C.
— The maximum span of each sensor can be converted to
different units using factors as below.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
Model FHY: 4 to 20mA DC 2-wire, linear signal
Model FKY: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal
EDSX7- 58
Date
Mar, 10. 1999
FHY, FKY...3
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
45V
16.1
10.5V
Power voltage
50
[V]
Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
Model FHY: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
(Output signal just before failure happens
is maintained.)
Model FKY: Selectable from HHC
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Approx. 21.6mA
(Adjustable within the range 20.8mA to
21.6mA from HHC)
“Output Underscale”:
Approx. 3.8mA
(Adjustable within the range 3.2mA to
3.8mA from HHC)
Note: For communication with HHC (Model: FXW), min. of 250Ω required.
3.2
Hazardous locations: (Approval pending)
Authorities
Flameproof
Intrinsic safety
BASEEFA
Factory
Mutual
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Ex ds IIB+H2 T4
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
—
RIIS
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
—
Zero/span adjustment:
Model FHY: Zero is adjustable externally from the
adjustment screw (UP and DOWN).
The adjustment screw can also function
to adjust span when MODE SWITCH (located on the electronics unit) is in the span
mode. INHIBIT mode to disable the adjustment screw is also available.
Model FKY: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Damping:
Adjustable electrical damping.
Model FHY: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Model FKY: The time constant is adjustable between
0 to 38.4 seconds.
Zero elevation/suppression:
– 100% to + 100% of URL
Normal/reverse action:
Model FHY: Selectable by moving a jumper pin located
on the electronics unit.
Model FKY: Selectable from HHC
Indication:
Analog indicator or 41/2 -digit LCD meter,
as specified.
3.8 4
20 20.8
Over scale
Burnout
0
Normal operating range
Under scale
Probable under range
Burnout
Loop-check output:
Model FHY: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKY: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA
by HHC.
Temperature limit:
Ambient: – 15 to + 65°C
(– 15 to + 65°C for LCD indicator)
(– 15 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill transmitter)
(– 10 to + 60°C for silicon oil "H", "S")
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
Fill fluid
13th digit of
"Code symbols"
Fluorinated oil
W, A and D
Silicone oil
H
Y and G
S
Process
temperature
Lower limit
of
static press
– 20 to
80°C Atmospheric
0 to 250°C pressure
–40 to 120°C 2.7kPa abs
0 to 250°C {20.3mmHg abs}
Low pressure side contact liquid temperature on transmitter of
Code H, S, is 120°C or lower.
Storage: – 40 to + 70°C
Humidity limit: 0 to 100% RH
2
21.6
Probable over range
Communication: (Model FKY only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
v
Burnout direction
v
v
Adjustment
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display(*)
v
v
Linearise
(**)
v
v
Rerange
(**)
v
v
(*)
HHC's version must be more than 5.0
1– 2), to use this function.
(or FXW
(**) HHC's version must be more than 5.3, and
Amplifier unit version 24.
Programmable output linearization function:
In smart version, output signal can be
characterized with “14 points linear approximation function” from HHC.
Performance specifications
Accuracy rating: (including linearity, hysteresis, and re(Standard) peatability)
For spans greater than 1/10 of URL: ± 0.25% of span
For spans below 1/10 of URL (Model FKY only):
(
± 0.17 + 0.08
0.1 x URL
Span
) % of span
(Option)
For spans greater than 1/10 of URL:± 0.1% of span
For span below 1/10 of URL (Model FKY only):
(
± 0.05 + 0.05
Linearity:
Stability:
0.1 x URL
Span
) % of span
0.1% of calibrated span
± 0.2% of upper range limit (URL) for 6
months
Temperature effect:
Effects per 28°C change between the limits of – 15°C and + 65°C
Zero shift; ± 0.5%/28°C
(x equal to 1/2 URL or more)
URL
Zero shift; ( ± 0.5
%/28°C
2×x)
(x less than 1/2 URL)
Total shift; ± 0.75%/28°C
(x equal to 1/2 URL or more)
URL
Total shift; ± ( 0.25 +0.5 ×
%/28°C
2 × x)
(x less than 1/2 URL)
High performance type (option) ...
Zero shift; ± 0.5%/28°C
(x equal to 1/6.5 URL or more)
URL
Zero shift; ± (0.5
%/28°C
6.5 × x )
(x less than 1/6.5 URL)
Total shift; ± 0.75%/28°C
(x equal to 1/6.5 URL or more)
URL
Total shift; ± ( 0.25 +0.5
%/28°C
6.5 × x )
(x less than 1/6.5 URL)
Where, x:
Calibrated span
URL:
Maximum span (Upper Range
Limit)
Note: 2.5 times the effects for material code
(7th digit) "H", "M", :T", "B", "L", "U".
Static pressure effect:
Zero shift: ± 0.2% of URL/1MPa (10 bar)
Span shift: – 0.2% of calibrated span for
flange rating pressure
2.5 times the zero shift for material code
"H", "M", "T", "B", "L", "U".
Overrange effect:Zero shift; ± 0.3% of URL for flange nominal pressure
2.5 times the effects for material code
"H", "M", "T", "B", "L", "U".
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
Step response: (without electrical damping)
Time constant
Dead time
0.3 s
approx. 0.3 s
Mounting position effect:
Zero shift, less than 0.3kPa{3m bar} for a
10° tilt in any plane. (No extension)
No effect on span.
This error can be corrected by adjusting
zero.
(Double the effect for fluorinated fill
sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec
Internal resistance for external field indicator:
12Ω or less
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
LP side: 1/4-18 NPT or Rc1/4.
HP side: ANSI, or JIS raised face flange.
See OUTLINE DIAGRAM for detailed dimensions.
Refer to "Code symbols"
3
FHY, FKY...3
Process-wetted parts material:
Optional features
HP side
Wetted
sensor body
Diaphragm &
flange face
316 stainless
steel
Hastelloy-C
lining
Monel lining
316L stainless
steel
Hastelloy-C
Tantalum
lining
Hastelloy-C
lining
Monel lining
Tantalum
lining
Tantalum
Monel
Hastelloy-C
Monel
Tantalum
*(1) Sensor O-rings: Viton or teflon selectable
(2) SCS14 Per JIS G5121
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished with
polyester coating, or 316 stainless
steel, as specified.
Bolts and nuts: Cr-Mo alloy (standard) or
304 stainless steel
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting flange: Carbon steel or 304
stainless steel, as specified
Environmental protection:
IEC IP67 and NEMA 4X
Flange mounting:See drawings
Mass{weight}:
Transmitter approximately 13kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.0kg per 50mm extension of
diaphragm
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 41/2 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics from lightning surges.
Lightning surge immunity is 4kV (1.2 x 50µs).
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for
use on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See below figure.
Filled liquid:
Silicone (Code Y,G)
[kPa abs]
{m bar abs}
Silicone (Code S)
101
{1010}
Operating pressure
LP side
Material
code
Process
(7th digit
Diaphragm
cover
in "Code
symbols")
316 stainless 316L stainless
V
steel (*2)
steel
H
316 stainless Hastelloy-C
steel (*2)
316 stainless
M
Monel
steel (*2)
316 stainless
T
Tantalum
steel (*2)
B
Hastelloy-C
Hastelloy-C
lining
Monel lining
L
Monel
U
Tantalum
Tantalum
lining
53.3
{533}
Operating area
13.3
{133}
Non-operating
area
2.7
{27}
–40 0
Fig. 1
Coating of cell:
EMI (Emission) EN 50081-1 : 1992
Test item
Basic standard
30-1000MHz
EN55022
Class B
EMS (Immunity) EN 50082-1 : 1992
No. Test item
Performance
criteria
Test specification
Basic standard
8kV (Air)
IEC 801-2 : 1984
B
1
Electrostatic
discharge
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
field
(Unmodulated)
IEC 801-3 : 1984
A
3
Fast transients 0.5kV 5/50(Tr/Th)ns
IEC 801-4 : 1984
common mode 5kHz Rep.
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
4
A stainless steel tag with customer tag
data is wired to the transmitter.
Cell's surface is finished with epoxy/polyurethane double coating.
Specify if environment is extremely corrosive.
ACCESSORIES
Oval flanges:
Frequency range
Applicable Electromagnetic
Radiation Disturbance
200 230 250
[°C ]
Relation between process temperature and
operating pressure
Customer tag:
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :-
60 85 120
Process temperature
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Communication module: (Standard for model FKY)
By adding communiction module, remote
setting function becomes available for
model FHY.
Remark: When the communication module is connected, the operation mode of external
zero/span adjustament screw is limited to
zero adjustment only.
CODE SYMBOLS
1 2 3 4 5 6 7 8
F
Y
9 10 11 12 13
14 15
Description
3
Type
4 to 20mA, Output type
4 to 20mA with digital signal, Output type
FHY
FKY
Connections
Process
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
S
T
V
W
X
Oval flange
screw
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
Conduit
connection
G 1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Mounting flange
Material
Size and rating
304 stainless
JIS 10K 40A
steel
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
Carbon steel
JIS 10K 40A
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
0
1
2
3
4
5
A
B
C
D
G
H
J
K
L
M
Q
R
S
T
Span limit [kPa] {m bar}
FHY
13...130 {130...1300}
50...500 {500...5000}
5
6
FKY
3...130 { 30...1300}
12.5...500 {125...5000}
Material
LP side
V
H
M
T
B
L
U
Process cover
Diaphragm
Wetted sensor
body
HP side
Diaphragm and
flange face
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
Hastelloy-C lining
Monel lining
Tantalum lining
316L
stainless steel
Hastelloy-C
316 stainless
steel
Hastelloy-C lining
316L stainless
steel
Hastelloy-C
Monel
Monel lining
Monel
Tantalum
Tantalum lining
Tantalum
Hastelloy-C
Monel
Tantalum
Hastelloy-C lining
Monel lining
Tantalum lining
Hastelloy-C
Monel
Tantalum
Notes: * (1) 100; 1 turn down is possible for model FKE, but should be used at a span greater than 1/40 of the
maximum span for better performance.
(2) In case of 6th digit code "6", LP side diaphrgm is Hastelloy-C.
(3) Material Code R; 6th digit code "6" is not available.
5
FHY, FKY...3
1 2 3 4 5 6 7 8
F
Y
9 10 11 12 13
14 15
Description
3
Indicator and arrester
Indicator
None
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
None
Analog, 0 to 100% linear scale
Analog, custom scale
Analog, double scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100%
Digital, custom scale
A
B
D
J
E
F
H
K
L
P
Q
S
Approvals for hazardous locations (Approval pending)
None (for ordinary locations)
JIS, Flameproof (Conduit seal) (Available for 4th code "S")
JIS, Flameproof (Cable gland seal) (Available for 4th code "S")
FM, Flameproof (or explosionproof) (Available for 4th code "T")
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
A
B
C
D
M
N
H
K
P
Diaphragm extension [mm]
Extension [mm]
Applicable material code
0
Any
50
100
(7th digit code "V" only, 11/2 in. flange is not applicable)
150
200
Y
A
B
C
D
}
Stainless steel parts
Stainless steel tag plate
None
Yes
None
Yes
None
Yes
None
Yes
Y
B
C
E
M
N
P
Q
Stainless steel elec. housing
None
None
Yes
Yes
None
None
Yes
Yes
Special applications and fill fluid
Treatment
None (standard)
None (standard)
Degreasing
Oxygen service
Chlorine service
High temp. 250°C
High temp. and vacuum (250°C)
Y
W
G
A
D
H
S
Coating of cell
None
None
None
None
Yes
Yes
Yes
Yes
Fill fluid
Silicone oil
Fluorinated oil
Silicone oil
Fluorinated oil (7th digit code "V" only)
Fluorinated oil (7th digit code "H", "T", "B" and "U")
Silicone oil (7th digit code "V" only)
Silicone oil (7th digit code "V" only)
O-ring and Teflon membrane
O-ring
Teflon membrane
Viton
None
Teflon
None
Viton
Yes
(11th digit code "Y" only)
Teflon
Yes
A
B
C
D
}
A
B
E
6
Arrester
None
None
None
None
Yes
Yes
Yes
Yes
None
None (Model FKY only)
Yes
Yes (Model FKY only)
Bolt/nut
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
304 stainless steel/304 stainless steel
OUTLINE DIAGRAM (Unit:mm)
Zero/span adj.
screw
Fastener
(In case of 10th
digit code “B,C,M,N”)
In case of 4th
digit code “S,V,W,X”
110
Up
50
φ 80
43.5
N holes
h dia.
88
Down
2
“B”
Conduit conn.
1
“C”
Conduit conn.
Cable gland
(option)
See note
t
L
20
Detail “C”
Detail “B”
(conduit conn.)
Inner of gasket
φ 80
41.3
G1/2
J
See talbe 1
27
71
17
M N
8
φ7
See talbe 1
φ 84
φE
φD
φ 13
φ 15
51
2.5
N
φ 48
φ 18.5
φ 49
46.4
Detail “A”
(L.P. conn.)
(27)
With field ind.
(option)
H.P. conn.
Oval flange screw
See table 1
Earth terminal
(both side)
See talbe 1
P
3
CONNECTION DIAGRAM
View from P
Vent/drain plug
+
–
CK+ CK–
+ –
Note 2)
11th digit of
L
Code symbols [mm] Mass approx. [kg]
Y
0
A
50
B
100
10.5 to 17.5
C
150
11
10
200
R1 R2
R3
355 150 325
to 17
4th digit of
Code symbols
349 144 319
to 18
11.5 to 18.5
S
φD
φE
t
N-φ h
0, G
140
105
36
4-19
JIS-10K-40A
1, H
155
120
36
4-19
JIS-10K-50A
2, J
140
105
38
4-19
JIS-20K-40A
3, K
155
120
38
8-19
JIS-20K-50A
4, L
160
120
42
4-23
JIS-30K-40A
5, M
165
130
42
8-19
JIS-30K-50A
A, Q
127 98.4 37.5 4-16
ANSI/JPI-150LB-1 1/2"
B, R
152 120.6 39.5 4-20
ANSI/JPI-150-2"
C, S
156 114.3 41
D, T
165
4-23
42.5 8-20
8 4.5
Pg13.5
Flange
W
127
17 8
1/2-14NPT 16 5
V
5th digit
of Code
symbols
Press. conn. Oval flange
Conduit conn.
screw
J
K M N
G1/2
T
“A” L.P. conn.
X
16 5
M20x1.5
Pg13.5
7/16-20UNF
screw depth 13
M4
7/16-20UNF
1/4-18NPT
screw depth 13
No. 8-32UNC
M10
1/4-18NPT
screw depth 13
M4
M10
1/4-18NPT
screw depth 13
M4
M4
<Optional stainless steel tag>
ANSI/JPI-300LB-1 1/2"
ANSI/JPI-300LB-2"
Rc1/4
Earth
terminal
7/16-20UNF
8 4.5 1/4-18NPT
screw depth 13
Table 1
75
D
9.5 to 12
Vent/drain
(When the vent/drain plug
attached on the upper side
of the detector)
20
S
T
H
F K YV
W
X
V
H3
M
T
Note * : Cable gland is supplied only for flameproof packing type.
φ11 cable is suitable.
7
FHY, FKY...3
Detail “B“
(L.P conn.)
4th digit code
“T, V ,W, X“
Detail “A“
(L.P conn.)
4th digit code “S“
φ16
2 -0.1
Up
110
50
107
0
1/4-18NPT
10
1
φ16
+0.2
φ12 +0.1
In case of 4th
digit code “S,V,W,X“
Down
Detail “C“
(conduit conn)
88
φ4
Detail “D“
2
φ13
φ15
K
Cable gland (option)
see note
“D“
Conduit conn.
t
G1/2
20
See table 1
(27)
Zero/span ADJ.
screw
Inner of gasket
46.4
Fastener
(In case of 10th
digit code “B,C,M,N“)
With field ind.
(option)
φ80
40.5
51
φ80
43.5
71
φ49
N Holes
h dia
Earth terminal
(both side )
see table1
“C“
Conduit conn.
φ84
φE
φD
M
17
N
1
H.P conn.
Oval flange
screw see table 1
41.3
3
Vent/drain
plug
“A“ or “B“
L.P. conn.
CONNECTION DIAGRAM
+
–
CK+ CK–
11th digit of
Code symbols
+ –
Y
5th digit
of Code
symbols
φD
φE
t
N-φ h
0, G
140
105
36
4-19
Flange
JIS-10K-40A
1, H
155
120
36
4-19
JIS-10K-50A
2, J
140
105
38
4-19
JIS-20K-40A
3, K
155
120
38
8-19
JIS-20K-50A
4, L
160
120
42
4-23
JIS-30K-40A
5, M
165
130
42
8-19
JIS-30K-50A
A, Q
127 98.4 37.5 4-16
ANSI/JPI-150LB-1 1/2"
B, R
152 120.6 39.5 4-20
ANSI/JPI-150-2"
C, S
156 114.3 41
D, T
165
127
4-23
42.5 8-20
Conduit conn.
J
K M
4th digit of
Code symbols
Note * : Cable gland is supplied only for flameproof packing type.
φ11 cable is suitable.
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www. fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
R1
R2
R3
11.5 to 15
355
150
325
Oval flange
screw
Earth
terminal
S
G1/2
17 8
Not attached
T
1/2-14NPT
16 5
7/16-20UNF
screw depth 13
No. 8-32UNC
V
Pg13.5
M10
screw depth 13
M4
W
M20x1.5
M10
screw depth 13
M4
7/16-20UNF
8 4.5
screw depth 13
M4
X
8 4.5
16 5
Pg13.5
M4
Table 1
ANSI/JPI-300LB-1 1/2"
ANSI/JPI-300LB-2"