FUJI EDSX5-72

FCX– –A
FCX
AXSERIES
SERIES REMOTE SEAL TYPE
PRESSURE TRANSMITTER
FHB, FKB...3
DATA SHEET
The FCX – AX pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA signal.
The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of -the-art microprocessor
technology to provide exceptional performance and functionality.
Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive
process conditions.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard feature for all GP models covering 6.4kPa{0.064bar} range
to 50000kPa{500bar} high pressure range. 0.1% accuracy is available as option. Fuji's micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Replaceable Communication Module
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX – AX
transmitter very unique in design. In case of change in
communication protocol, all that needs to be done is just
to replace the module and the transmitter gets upgraded
to the new version.
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both Fuji
proprietary protocol and HART. Any HART compatible
devices can communicate with FCX – AX series transmitters.
5. Application flexibility
Various options that render the FCX – AX suitable for
almost any process applications include:
— Analog indicator at either the electronics side or terminal side
— Full range of hazardous area approvals
— Built-in RFI filter and lightning arrester
— 4 12 -digits LCD meter
— Stainless steel electronics housing
— Wide selection of materials
— High temperature, high vacuum seals
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Type:
Model FHB: 4 to 20mA
Model FKB: 4 to 20mA with digital signal
Service:
Liquid, gas, or vapour
Span, range, and overrange limit:
Span limit [kPa]{bar}
Type
Min.
FHB
F
B
1
F
B
2
F
B
3
F
B
4
F
B
5
6.4
{0.064}
50
{0.5}
300
{3}
1000
{10}
5000
{50}
Max.
FKB
0.64
{0.0064}
5
{0.05}
30
{0.3}
100
{1}
500
{5}
Overrange
limit
[MPa] {bar}
Range limit
[kPa]{bar}
FHB/FKB
64
{0.64}
500
{5}
3000
{30}
10000
{100}
50000
{500}
–64 to +64
{–0.64 to +0.64}
–100 to +500
{–1 to +5}
–100 to +3000
{–1 to +30}
–100 to +10000
{–1 to +100}
–100 to +50000
{–1 to +500}
1
{10}
1.5
{15}
9
{90}
15
{150}
75
{750}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
— Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: Atmospheric pressure
— Conversion factors to different units;
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Output signal:
Model FHB: 4 to 20mA DC 2-wire
Model FKB: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX5-72
EDS5-62b
Date
Mar. 15, 1999
FHB, FKB...3
Load limitations: see figure below
Note: For communication with HHC (Model: FXW), min. of 250Ω is required.
Model FHB: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
(Output signal just before failure happens
is maintained.)
Model FKB: Selectable from HHC
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Approx. 21.6mA
(Adjustable within the range 20.8mA to
21.6mA from HHC)
“Output Underscale”:
Approx. 3.8mA
(Adjustable within the range 3.2mA to
3.8mA from HHC)
Hazardous locations: (Approval pending)
3.2
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
Authorities
BASEEFA
Factory
Mutual
CSA
RIIS
SAA
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP 66/67
45V
16.1
10.5V
Power voltage
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
—
Ex ia II C T5, T6
IP 66/67
50
[V]
20 20.8
Over scale
Burnout
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
Ex n II C T5, T6
IP 66/67
Zero/span adjustment:
Model FHB: Zero is adjustable from the external adjustment screw.
The adjustment screw can also function to
adjust span when MODE SWITCH (located on the electronics unit) is in the span
mode. INHIBIT mode to disable the adjustment screw is also available.
Model FKB: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Damping:
Adjustable electrical damping.
Model FHB: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Model FKB: The time constant is adjustable between 0
to 38.4 seconds.
Zero elevation/suppression:
Zero can be elevated or suppressed within
the specified range limit of each sensor
model.
Normal/reverse action:
Selectable by moving a jumper pin located
on the electronics unit.
Indication:
Analog indicator or 4 12 -digit LCD meter, as
specified.
Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
2
3.8 4
0
Normal operating range
Under scale
Probable under range
Burnout
21.6
Probable over range
Loop-check output:
Model FHB: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKB: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit:
Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil fill transmitter)
(–10 to +85°C for silicone oil "H", "S", "K")
(+20 to +85°C for silicone oil "J", "T")
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified by each standard.
Process:
Fill fluid
Code in the
13th digit of
"Code symbols"
Process
temperature
Fluorinated oil
W, A and D
–20 to 120°C
Silicone oil
H
–15 to 250°C
J
Atmospheric
pressure
85 to 300°C
Y and G
– 40 to 120°C
S
–15 to 250°C
T
85 to 300°C
K
–15 to 200°C
Storage: – 40 to +90°C
Lower limit
of
static press.
2.7kPa abs
{20mmHg
abs}
0.13kPa abs
{1mmHg abs}
or more
Humidity limit:
0 to 100% RH
Communication: (Model FKB only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Items
Display
Set
Tag No.
v
Model No.
v
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
v
Burnout direction
v
v
Adjustment
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display(*)
v
v
Note: (*) HHC's version must be more than 5.0 (or
1 – 2), to use this function.
FXW
Performance specifications
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ± 0.2% of span
For spans below 1/10 of URL (Model FKB only):
0.1 × URL
± 0.1+0.1
% of span
Span
(Option) Not available for Max span 50000kPa model.
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL (Model FKB only):
0.1 × URL
± 0.05+0.05
% of span
Span
Linearity:
0.1% of calibrated span
Stability:
± 0.2% of upper range limit (URL) for 24
months
Temperature effect:
Effect per 28°C change between the limits of – 40°C and +85°C
(Standard)
Zero shift: ± 0.35% of URL
Total effect: ± 0.5% of URL
(Option)
Zero shift: ± 0.25% of URL
Total effect: ± 0.275% of URL
Overrange effect: Zero shift; 0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
(
(
)
)
Step response:
Time constant: 0.3s (with 1.5m capillary)
Dead time: approximately 0.3s
(without electrical damping)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ/500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
JIS, ANSI, or DIN raised face flanges or
screw connection JIS/ISO G1 external
thread.
Refer to "Code symbols."
Process-wetted parts material:
Diaphragm: 316L stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Flange face:316 stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Extension: 316 stainless steel, Hastelloy-C
(Refer to "Code symbols")
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with polyester coating, or 316 stainless
steel (SCS14 per JIS G5121), as specified.
Capillary: In case of 13th code "Y, W, G, A,
D", PVC armored stainless steel.
In case of 13th code "H, J, S, T, K",
stainless steel armored stainless steel.
Mounting flange: 304 stainless steel or
carbon steel
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as
specified
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting
Mass {weight}:
Transmitter approximately 10kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
3
FHB, FKB...3
ACCESSORIES
Optional features
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS8-47)
Communication module: (Standard for FKB)
By adding communication module, remote setting function becomes available
for FHB.
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 4 12 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4KV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Not available with material code “W”.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum and high temperature service:
Special silicone oil and filling procedure
are applied.
See below figure.
Remark: When the communication module is connected, the operation mode of external
zero/span adjustment screw is limited to
zero adjustment only.
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
[kPa abs]
{mbar abs}
Silicone (Code S)
Silicone (Code T)
Sealing liquid:Silicone (Code K)
101
{1010}
53.3
{533}
Operating pressure
Operating pressure
101
{1010}
Operating arear
13.3
{133}
Non-operating
area
0.27
{2.7}
0.13
{1.3}
2.7
{27}
–40 –15
60 85 120
Process temperature[°C ]
200 230 250
300
–15
Customer tag:
Coating of cell:
100
Process temperature[°C ]
200
Fig. 2 Relation between process temperature and
operating pressure
Fig. 1 Relation between process temperature and
operating pressure
A stainless steel tag for customer tag data
is wired to the transmitter.
Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :EMI (Emission)
Test item
Applicable Electromagnetic Radiation
Disturbance
4
Operating arear
EN50081-1 : 1992
Frequency range
Basic standard
30-1000MHz
EN55022
Class B
EMS (Immunity)
EN50082-1 : 1992
No.
Test item
Test
specification
Basic
standard
Performance
criteria
1
Electrostatic
discharge
8kV (Air)
IEC 801-2:1984
B
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
IEC 801-3:1984
field.
(Unmodulated)
A
3
Fast transients
common mode
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
CODE SYMBOLS
1 2 3 4 5 6 7 8
9 10 11 12 13
Description
3
Type
4 to 20mA, Output type
4 to 20mA with digital signal, Output type
FHB
FKB
Conduit connection
G 1/2
1/2-14NPT
Pg 13.5
M20 × 1.5
S
T
V
W
Flanges
Mounting flange
0
1
2
3
4
5
6
7
8
304 stainless
steel
A
B
C
D
E
F
G
H
J
K
P
Q
R
Carbon steel
None
(wafer type)
Flange size and rating
JIS 10K 80A
JIS 10K 100A
JIS 30K 50A
ANSI/JPI 150LB "3"
ANSI/JPI 150LB "4"
ANSI/JPI 600LB "2"
DIN PN16/40 DN80
DIN PN16 DN100
DIN PN40 DN50
JIS 10K 80A
JIS 10K 100A
JIS 30K 50A
ANSI/JPI 150LB "3"
ANSI/JPI 150LB "4"
ANSI/JPI 600LB "2"
DIN PN16/40 DN80
DIN PN16 DN100
DIN PN40 DN50
Screw type, JIS/ISO G1
3 inch wafer
4 inch wafer
2 inch wafer
Span limit (*2) [kPa]{bar}
FHB/FKB
6.4/0.64…64/64
{0.064/0.0064…0.64/0.64}
50/5…500/500
{0.5/0.05…5/5}
300/30…3000/3000
{3/0.3…30/30}
1000/100…10000/10000
{10/1…100/100}
5000/500…50000/50000
{50/5…500/500}
1
2
3
4
5
}
Ranges
1 2 3 4 5
* *
* *
* *
* *
* *
* *
* *
* *
* *
* *
* *
* *
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
* *
* *
*
*
*
*
Available only with
material code "W"
Material/diaphragm extension
W
A
B
C
D
H
F
G
K
L
M
T
P
R
(*1)
Diaphragm
Flange face
316L stainless
steel
316 stainless
steel
Hastelloy-C
Hastelloy-C
Monel
Tantalum
Titanium
Zirconium
Monel
Tantalum
Titanium
Zirconium
Diaph. extension [mm]
0
50
100
150
200
0
50
100
150
200
0
0
0
0
}
(*3)
} (*4)
Notes: * (1) If range 4 or 5 is selected, specify material "W" in any cases.
(2) 100: 1 turn down is possible for model FKB, but should be used at a span greater than
1/40 of the maximum span for better performance.
(3) In case of 7th digit code "A", "B", "C", "D" and 13th digit code "S", "T", "K", 5th digit code
“1“,“4“,“7“,“B“,“E“,“H“,“Q“ is available.
(4) In case of 6th digit code "2",“3“ and 5th digit “0“,“3“,“6“,“A“,“D“,“G“,“P“ is available.
5
FHB, FKB...3
1 2 3 4 5 6 7 8
FHB
3
F KB
3
9 10 11 12 13
14 15
Description
Indicator and arrester
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, custom scale
None
Analog, double scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Analog, double scale
Yes
Digital, 0 to 100%
None
Digital, custom scale
None (Model FKB only)
Digital, 0 to 100%
Yes
Digital, custom scale
Yes (Model FKB only)
Approvals for hazardous locations (Approval pending)
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
(Available for 4th digit code “S“)
JIS, Flameproof (Cable gland seal) (Available for 4th digit code “S“)
FM, Flameproof (or explosionproof) (Available for 4th digit code “T“)
CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit cord (S,T,W)
SAA Intrinsic safety (Available for 4th digit cord (S,T,W)
SAA Type–N (non-sparking)(Available for 4th digit cord (S,T,W)
Capillary and mounting bracket
Capillary
Mounting bracket
A
B
D
J
E
F
H
K
L
P
Q
S
A
B
C
D
E
M
N
H
J
K
P
R
T
Q
A
B
G
C
H
J
K
D
E
L
F
M
N
P
1.5 m
3
5
6
7
(*1)
8
(*1)
10 (*1)
1.5
3
5
6
7
(*1)
8
(*1)
10 (*1)
Stainless steel parts (*2)
Stainless steel tag plate
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
H
J
S
T
K
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Carbon steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel elec. housing



Y
C
Y
A
B
E
F
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
None (standard)
Silicone oil
None (standard)
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "W", "A", "B", "C" and "D")
Chlorine service
Fluorinated oil (7th digit code "H", "F", "G", "K", "L" and "T")
High temp. 250°C
Silicone oil • Available for 6th digit code "1", "2" or "3".
(*3)
High temp. 300°C
Silicone oil In case of 13th code "S", "T", "K", available for
High temp. and vacuum (250°C) Silicone oil 6th digit code "2" only.
High temp. and vacuum (300°C) Silicone oil • Available for 7th digit code "W", "A", "B", "C" or
High temp. and high vacuum
Silicone oil "D".
Teflon membrane
None
Yes (Available for the 5th digit code "0", "2", "3", "5", "6", "8", "A", "C", "D", "F", "G", "J", "P", "R".
and 7th digit code "W", "H", "M", "T", "P", "R".)
Bolt/nut
None
(6th digit code "1", "2", "3")
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
} (6th digit code "4", "5")
Cr-Mo alloy hexagon bolt/nut
304 stainless steel/304 stainless steel
(6th digit code "4")
} (*4)
630 stainless steel/304 stainless steel
(6th digit code "5")



Notes: * (1) Available for 5th digit code "0, 1, 3, 4, 6, 7, A, B, D, E, G, H, P, Q and 13th digit code "Y,
W, G, A, D". Inquire about in case of 13th other code.
(2) Not applicable to carbon steel flange material.
(3) Treatment; None
(4) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
In case of 4th
digit code
“S,V,W,X“
Zero/span ADJ. screw
70
110
50
ø80
104
Mtg.pipe
U - Bolt M8 JIS 50A (2")
Up
43.5
Fastener
(In case of 10th
digit code
“B,C,M,N“)
88
Down
30 38
“A“
Conduit conn.
224
4 Holes
9 dia
58
N holes h DIA.
“B“
Conduit conn.
Inner of gasket
øH
øG
øF
øE
øD
P
Cable gland (option)
see note
No flange is attached
in case of 5th digit code
“P,Q,R”.
Earth terminal
(both side)
see table 1
51
71
(27)
20
t
191
L
Detail “A“
Detail “B“
ø80
(Conduit conn.)
ø13
ø15
J
17
252
K M
With field ind .
(option)
G1/2
S
See table 1
2-M8 × 12
7th digit code
W
H
M
T
P
50
70
120
øD
øF øG øH
t
P
185 150
126 100 73
38
118
8–19 JIS–10K–-80A
210 175
151 103 96
38
143
8–19 JIS–10K–100A
8–19 JIS–30K–50A
84
52
48
42
50
191 152.5 126 100 73
44
118
N-øh
Flange
4–20 ANSI/JPI
–150LB–3"
229 190.5 151 103 96
44
165 127
45.5 50
8–20
143
52
48
ANSI/JPI
–600LB–2"
4th digit
code
Conduit conn.
K
S
G1/2
17 8
M4
T
1/2
–14NPT
16 5
No. 8
–32UNC
8
M
126 100 73
44
118
8–18 DIN PN40 DN80
220 180
151 103 96
40
143
8–18 DIN PN16 DN100
V
Pg13.5
40
50
4–18 DIN PN40 DN50
W
M20 × 1.5 16 5
84
52
48
Earth
terminal
J
200 160
165 125
Mass approx.(kg)
11th digit code
9.5
A
D
1.5
B
E
3
G
L
5
C
F
6
H
M
7
J
N
8
K
P
10
A
F
50
10.5
B
G
100
11.5
C
K
150
12
D
L
200
12.5
S (m)
8–20 ANSI/JPI
–150LB–4"
84
0
R
øE
165 130
L
4.5
CONNECTION
DIAGRAM
+
–
CK+ CK–
M4
M4
+ –
S
T
H
B V
F
K
W
X
1
2
3
3
Table 1
Note) : Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
7
FHB, FKB...3
Fastener
(In case of 10th
digit code
“B,C,M,N“)
Zero/span ADJ. screw
In case of 4th
digit code
“S,V,W,X“
Mtg.pipe
JIS 50A (2")
U - Bolt M8
70
110
50
ø80
S
88
Down
38
30
With field ind .
(option)
51
71
“B“
Conduit conn.
(27)
4 Holes
9 dia
191
G1
45
Earth terminal
(both side )
see table 1
Cable gland (option)
see note
58
20
224
2
ø80
Packing
100
“A“
Conduit conn.
53 18
104
43.5
Up
-0.1
-0.2
-0.1
-0.2
ø23.6
252
ø30
Detail “B“
Detail “A“
(Conduit conn.)
ø13
ø15
17
K M
2–M8 12
G1/2
J
50
See table 1
70
120
Conduit conn.
4th digit
code
C
–
E
Earth
terminal
S
G1/2
17
8
M4
16
5
No.8-32UNC
T
1/2-14NPT
V
Pg13.5
W
M20 × 1.5
CONNECTION
DIAGRAM
+
D
8
16
4.5
M4
5
M4
11th digit code
S (m)
A
D
1.5
B
E
3
G
L
5
C
F
6
H
M
7
J
N
8
K
P
10
Table 1
CK+ CK–
+ –
S
V
T
H
B V K H W3
F
K
M
W
T
X
Note) : Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
Fax: 81-42-585-6187, 6189
Information in this catalog is subject to change without notice.
Printed in Japan