FUJI EDSX5-86D

PRESSURE TRANSMITTER
FHG...4
DATA SHEET
The FCX – A2e pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA
signal.
The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ±0.1%
0.1% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated
or suppressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX–A2e series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–A2e.
4. Application flexibility
Various options that render the FCX – A2e suitable for almost any process applications include:
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Span limit [kPa] {bar}
Type
Min.
F HG 02
F HG 03
F HG 04
16.66
{0.16}
100
{1}
333.3
{3.33}
Range limit
[kPa] {bar}
Max.
Lower limit
Upper limit
500
{5}
3000
{30}
10000
{100}
–100
{–1}
–100
{–1}
–100
{–1}
500
{5}
3000
{30}
10000
{100}
Overrange
limit
[MPa] {bar}
1.5
{15}
9
{90}
15
{150}
– Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 60°C
– Conversion factors to different units;
1 MPa=103 kPa=10bar=10.19716kgf/cm2= 145.0377psi
1kPa=10mbar=101.9716mmH2O =4.01463inH2O
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
EDSX5-86d
Date
Apr. 25, 2003
FHG...4
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
45V
16.1
10.5V
Power voltage
50
[V]
Note: For communication with HHC (1) (Model: FXW), min. of 250 Ω
required.
Hazardous locations:
Authorities
Factory
Mutual
Flameproof
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex do IIB+H2 T4
CSA
TIIS
Intrinsic safety
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
Ex ia II C T4 (*)
Type n
Nonincendive
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
(*) Approval pending
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(span adjustment is not available with 9th
digit code "L, P, Q, S").
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
Zero can be elevated or suppressed within
the specified range limit of each sensor
model.
Normal/reverse action:
Selectable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC
3.2
3.8 4
20 20.8
21.6 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
(Note)
2
(1) HHC: Hand Held Communicator
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit:
Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil fill
transmitter)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified by
each standard.
Process: – 40 to +100°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: –40 to +90°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC's version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
Performance specifications
Physical specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.05+0.05
% of span
Span
Stability:
± 0.2% of upper range limit (URL) for 6
month.
Temperature effect:
Effects per 28°C change between the limits of –40°C and +85°C
URL
Zero shift: ± (0.1+0.025 span )%
URL
Total effect: ± (0.125+0.025 span )%
Overrange effect: Zero shift; 0.3% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: Time constant: 0.2s
Dead time: approximately 0.2s
(without electrical damping)
Mounting position effect:
Zero shift, less than 0.1kPa {1m bar} for a
10° tilt in any plane.
No effect on span. This error can be corrected by adjusting Zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
(
)
Electrical connections:
G1 /2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
1-port (standard), as spcified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meet DIN 19213
Process-wetted parts material:
Material
code
(7th digit Process cover
in Code
symbols)
V
Diaphragm
Wetted
sensor body
316 stainless 316L stainless 316 stainless
steel(*1)
steel
steel
Vent/drain
316 stainless
steel
Note: *(1) SCS14 per JIS G 5121
Remark: Sensor O-rings: Viton O-ring and teflon gasket selectable
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating.
Bolts and nuts: Cr-Mo alloy (standard), or
304 stainless steel (630 stainless steel
for 50MPa unit).
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct
process mounting.
Mass {weight}:
Transmitter approximately 3.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
3
FHG...4
Optional features
Indicator:
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Silicone oil (Code:Y,G,N)
Operating pressure
[kPa abs]
{mbar abs}
101
{1010}
Operating
area
20
{200}
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Basic
standard
Performance
criteria
IEC61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
IEC61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
IEC61000-4-8
A
Burst
2kV
5kHz
IEC61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
IEC61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
IEC61000-4-6
A
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
4
{40}
2.7
{27}
None-operating
area
–40
60
120
ORDERING INFORMATION
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
ACCESSORIES
Oval flanges:
4
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1 /2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occured in the transmitter.
Hold/Overscale (21.6mA)/Overscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of
the actual scale (code D,H,P,S on 9th digit).
5. Tag No.(up to 26 alphanumerical characters), if required.
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
6, 7
9
10
11
12
13
14
15
Description
<Connections>
Process
Oval flange
connection
screw
7/16-20UNF
Rc1/4
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10
1/4-18NPT
M10
1/4-18NPT
7/16-20UNF
<Span and materials>
Process cover
Span limit
[kPa]{bar}
316 stainless steel
16.66…500
{0.16…5}
316 stainless steel
100…3000
{1…30}
316 stainless steel
333.3…10000
{3.33…100}
Conduit
connection
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
Note
(×1)
(×1)
(×1)
(×1)
(×1)
F HG
0
9 10 11 12 13
14 15
4
Digit No.
of code
A
B
C
D
E
Diaphragm
Wetted cell body
316L stainless steel
316 stainless steel
2V
316L stainless steel
316 stainless steel
3V
316L stainless steel
316 stainless steel
4V
<Indicator and arrester>
Indicator
Arrester
None
None Z/S board
Analog, 0 to 100% linear scale
None attached.
Analog, custom scale
None Approval
pending for
None
Yes
10th digit
Analog, 0 to 100% linear scale
Yes
code "G, H, J"
Analog, custom scale
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None Approval
Digital, custom scale
pending for
(Local adjustment unit with LCD display)
None 10th digit
Digital, 0 to 100%
code "D, E,
(Local adjustment unit with LCD display)
Yes
G, H, J"
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code “A“)
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A“)
FM, Flameproof (or explosion proof) (Available for 4th digit code “B“)
CSA Frameproof (or explosion proof) (Available for 4th digit code “B“)
TIIS, Intrinsic safety (Approval pending)
FM, Intrinsic safety and Nonincendive
CSA Intrinsic safety and Nonincendive
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Standard
None
Standard
Yes, stainless steel
Side
None
Side
Yes, stainless steel
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Note 1
(*1)
Yes
None
None
None
None
Yes
Yes
None
Yes
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code “V“ only)
NACE specification
Silicone oil (Not available for 15th digit code “A“, “B“)
<Sensor O-ring / Gasket>
Viton (O-ring)
Teflon (gasket)
<Bolt/nut>
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel bolt/304 stainless steel nut
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
A
B
C
D
E
G
H
J
A
C
D
F
Y
B
M
N
Y
G
A
N
A
B
A
B
C
D
E
Note 1: (*1) Costomer tag number can be engraved on standartd stainless steel name plate.
If extra tag plate is required, select “Yes“.
5
FHG...4
OUTLINE DIAGRAM (Unit:mm)
Note2)
Vent/drain plug
(When the vent/drain plug
attached on the upper side
of the detector)
Fastener
(Flameproof only)
Zero ADJ. screw
MTG. Pipe JIS 50A
(2B)
"A" Press. conn.
41
52.5
58
Down
88
38
U - bolt M8
ø80
70
130
104
ø80
Up
Cable gland
(option)
210
189 (6th digital code “5”)
4 holes
9 dia.
Note1)
Vent/drain plug
37
(27)
"C" Conduit conn.
"B" Conduit conn.
With field ind. (option)
Approx.147
Detail "A"
(Press. conn.)
ø18.5
Detail "B"
(Conduit conn.)
43
Earth terminal
Detail "C"
ø13
H
G 1/2
D
231
ø7
Electronics
unit
Oval flange
screw
See table 1
41.3
E
17
8
F
2.5
ø15
Side
vent
(option)
See table 1
See table 1
Sensor
unit
4-M8 12
Conduit conn.
D
E
F
4th digit of the
code symbols
Press.conn.
H
A
G1/2
17
8
Rc1/4
B
1/2-14NPT
16
5
1/4-18NPT
C
Pg13.5
8
4.5
1/4-18NPT
D
M20 1.5
16
5
1/4-18NPT
E
Pg13.5
8
4.5
1/4-18NPT
Oval flange screw
7/16-20UNF
Screw depth15
7/16-20UNF
Screw depth15
M10
Screw depth15
M10
Screw depth15
7/16-20UNF
Screw depth15
27
54
70
104
Table 1
Note1)
Cable gland is supplied in case of 10th digit code "C".
ø11 cable is suitable.
Note2)
The pressure connector is located on the down side surface of
the detector, when the vent / drainplug is attatched on the upper
side of the detector
CONNECTION
DIAGRAM
CK CK
(M4 screws)
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng