FUJI EDSX7-62K

SMALL FLANGE LEVEL TRANSMITTER
FKY...4
DATA SHEET
The FCX–A2 small flange level transmitter accurately measures liquid level and transmits a proportional 4 to 20mA
signal. The transmitter utilizes a unique micromachined
capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FEATURES
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Static
pressure
Type
FKY
3
FKY
5
FKY
6



1. Directly connectable to 1-1/2 in. and 2 in. flanges
The transmitter is connectable to 1-1/2 in. and 2 in. pipes
without a reducer.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–A2.
Further, by upgrading electronics FOUNDATION™
fieldbus and Profibus™ are also available.
4. Application flexibility
Various options that render the FCX–A2 suitable for
almost any process applications include:
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum service.
5. Programmable output Linearization Function
Output signal can be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as
wet calibration.
Up to
flange
rating
Span limit [kPa] {m bar}
Min.
3
{30}
13
{130}
50
{500}
Max.
32
{320}
130
{1300}
500
{5000}
Range limit
[kPa] {m bar}
+/–
{ +/–
+/–
{ +/–
+/–
{ +/–
32
320}
130
1300}
500
5000}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig.1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60 °C.
– The maximum span of each sensor can be converted to
different units using factors as below.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX7-62k
Date
Apr. 1, 2007
FKY...4
Load limitations: see figure below
Authorities
Intrinsic safety
[Ω]
Load resistance
2000
ATEX
1533Ω
1500
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
1000
600Ω
Operating
area
500
24V
250
0
10
16.1
10.5V
Power voltage
Factory
Mutual
45V
50
Hazardous locations:
ATEX
A,B,D
Y,G,H,S
-40°C to +85°C
Y,G,H,S
-20°C to +80°C
Q,S,4,5
Y,G,H,S
-20°C to +60°C
E,F,H
Y,G,H,S
-40°C to +60°C
W,A,D
-10°C to +60°C
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
Flameproof
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = -40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = -40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
-
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp.=+120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = -40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = -40°C to +65°C
Tamb
L,P,1,2
-
(Note) (1) HHC: Hand Held Communicator
2
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
13th digit
9th digit
[V]
Note: For communication with HHC(1) (Model: FXW), min. of 250Ω required.
Authorities
Ex II 1 GD
EEx ia IIC T5 Tamb = -40°C to +40°C
EEx ia IIC T4 Tamb = -40°C to +80°C
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameter:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = -40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = -40°C to +50°C
Entity Parameter:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
ATEX
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = -40°C to +40°C
EEx nL IIC T4 Tamb = -40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
3.2
Normal operating range
Under scale
Probable under range
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
13th digit
9th digit
CSA
Tamb
A,B,D
Y,G,H,S
-40°C to +85°C
L,P,1,2
Y,G,H,S
-20°C to +80°C
Q,S,4,5
Y,G,H,S
-20°C to +60°C
E,F,H
Y,G,H,S
-40°C to +60°C
W,A,D
-10°C to +60°C
-
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
-
IECEx
Scheme
/SAA
-
20 20.8
21.6 [mA]
Over scale
Burnout
EEx nAL IIC T5 Tamb = -40°C to +40°C
EEx nAL IIC T4 Tamb = -40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
3.8 4
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(Span adjustment is not available with 9th
digit code “L, P, Q, S”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
– 100% to + 100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA
by HHC(1).
Temperature limit:
Ambient: – 15 to + 65°C
(– 15 to + 65°C for LCD indicator)
(– 15 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill transmitter)
(– 10 to + 60°C for silicon oil “H”, “S”)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
Fill fluid
13th digit of
“Code symbols”
Fluorinated oil
W, A and D
Silicone oil
H
Lower limit
of
static press
Process
temperature
– 20 to
80°C Atmospheric
0 to 250°C pressure
–40 to 120°C 2.7kPa abs
0 to 250°C {20.3mmHg abs}
S
Low pressure side contact liquid temperature on transmitter of
Code H, S, is 120°C or lower.
Y and G
Storage: – 40 to + 70°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326
3
FKY...4
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4-20 mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ± 0.25% of span
For spans below 1/10 of URL:
± 0.17 + 0.08 0.1 x URL
Span
(
) % of span
(Option) (Code: 21th digit H, K)
For spans greater than 1/10 of URL: ± 0.1% of span
For span below 1/10 of URL:
(
± 0.05 + 0.05
0.1 x URL
Span
)
% of span
± 0.2% of upper range limit (URL) for 3
years.
Temperature effect:
Effects per 28°C change between the limits of – 15°C and + 65°C
Zero shift; ± 0.5%/28°C
(x equal to 1/2 URL or more)
URL
Zero shift; ± 0.5
%/28°C
2x
(x less than 1/2 URL)
Total shift; ± 0.75%/28°C
(x equal to 1/2 URL or more)
URL
Total shift; ± 0.25 +0.5 ×
%/28°C
2x
(x less than 1/2 URL)
Stability:
(
)
(
)
(Option) (Code: 21th digit J, K)
Zero shift; ± 0.5%/28°C
(x equal to 1/6.5 URL or more)
URL
Zero shift; ± (0.5
%/28°C
6.5 x )
(x less than 1/6.5 URL)
Total shift; ± 0.75%/28°C
(x equal to 1/6.5 URL or more)
URL
Total shift; ± ( 0.25 +0.5
%/28°C
6.5 x )
(x less than 1/6.5 URL)
Where, x:
Calibrated span
URL:
Maximum span (Upper Range
Limit)
Static pressure effect:
Zero shift: ± 0.2% of URL/1MPa
Overrange effect:Zero shift; ± 0.1% of URL for flange rating pressure
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Update period: 120 msec *)
Step response: (without electrical damping)
*)
4
Time constant *)
Dead time *)
0.3 s
0.2 s
Faster response is available as option (maximum update rate : 25 times per second)
Mounting position effect:
Zero shift, less than 0.3kPa{3m bar} for a
10° tilt in any plane. (No extension)
No effect on span.
This error can be corrected by adjusting zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec
Internal resistance for external field indicator:
12Ω or less
Physical specifications
Electrical connections:
G 1/2 , 1/2 -14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
And 1-conduit or 2-conduit, as specified.
Process connections:
LP side: 1/4-18 NPT or Rc1/4.
HP side: ANSI, or JIS raised face flange.
See OUTLINE DIAGRAM for detailed dimensions.
Refer to “Code symbols”
Process-wetted parts material:
LP side
HP side
Material
code
Wetted
Diaphragm &
Process
(7th digit
Diaphragm
sensor body
flange face
cover
in “Code
symbols”)
V
316 stainless 316L stainless 316 stainless 316L stainless
(*1)
J
316 stainless 316L stainless 316 stainless 316L stainless
(*1)
steel
+ AU coating
316 stainless 316L stainless 316 stainless Hastelloy-C
C
(*1)
D
316 stainless 316L stainless 316 stainless Monel
(*1)
316 stainless 316L stainless 316 stainless Tantalum
E
(*1)
Hastelloy-C
316 stainless Hastelloy-C
Hastelloy-C
H
lining
(*1)
Monel lining Monel
M
316 stainless Monel
(*1)
Tantalum
316 stainless Tantalum
Tantalum
T
lining
(*1)
Hastelloy-C
Hastelloy-C Hastelloy-C
Hastelloy-C
B
lining
Monel lining Monel
L
Monel lining Monel
Tantalum
U
Hastelloy-C
Tantalum
Tantalum
lining
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remark: Sensor O-rings: Viton O-ring or teflon gasket selectable
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating(standard),
or 316 stainless steel (SCS14A per JIS
G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard) or
304 stainless steel
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting flange: 304 stainless steel or
carbon steel, as specified.
Environmental protection:
IEC IP67 and NEMA 6 / 6P
Flange mounting:See drawings
Mass{weight}:
Transmitter approximately 13kg without
options.
Add; 0.8kg for indicator option
4.5kg for stainless steel housing
option
1.0kg per 50mm extension of
diaphragm
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics from lightning surges.
Lightning surge immunity : 4kV (1.2 x 50µs).
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for
use on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig.1
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating.
Specify if environment is extremely corrosive.
Filled liquid:
Silicone (Code Y,G)
[kPa abs]
{m bar abs}
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2 -14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
53.3
{533}
Operating area
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Silicone (Code S)
101
{1010}
Operating pressure
ACCESSORIES
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
13.3
{133}
Non-operating
area
2.7
{27}
–40 0
Fig. 1
60 85 120
200 230 250
[°C ]
Process temperature
Relation between process temperature and
operating pressure
5
FKY...4
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
<Connections>
Process
Conduit
Oval flange
connection
connection
screw
7/16-20UNF
Rc1/4
(×1)
G 1/2
1/4-18NPT
7/16-20UNF
1/2-14NPT (×1)
1/4-18NPT
M10 (or M12)
Pg13.5
(×1)
1/4-18NPT
M10 (or M12)
M20×1.5 (×1)
1/4-18NPT
7/16-20UNF
Pg13.5
(×1)
7/16-20UNF
G 1/2
Rc1/4
(×2)
1/4-18NPT
7/16-20UNF
1/2-14NPT (×2)
1/4-18NPT
M10 (or M12)
Pg13.5
(×2)
1/4-18NPT
M10 (or M12)
M20×1.5 (×2)
1/4-18NPT
7/16-20UNF
Pg13.5
(×2)
<Mounting flange>
Material
Size and rating
304 stainless
JIS 10K 40A
steel
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
Carbon steel
JIS 10K 40A
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
<Span limit [kPa] {m bar}>
3
32
{ 30
320}
13
130
{130
1300}
50
500
{500
5000}
<Material>
LP side
Process cover
Diaphragm
Wetted sensor
body
316 stainless steel 316 stainless steel 316 stainless steel
316 stainless steel 316 stainless steel 316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
Hastelloy-C lining
Monel lining
Tantalum lining
Note 1: (*1)
6
F KY
Description
316 stainless steel
316 stainless steel
316 stainless steel
Hastelloy-C
Monel
Tantalum
Hastelloy-C
Monel
Tantalum
316 stainless steel
316 stainless steel
316 stainless steel
Hastelloy-C lining
Monel lining
Tantalum lining
Hastelloy-C lining
Monel lining
Tantalum lining
Combination with
12th digit code
"C, E, P, Q" are
not available.
9 10 11 12 13
4
A
B
C
D
E
S
T
V
W
X
0
1
2
3
4
5
A
B
C
D
G
H
J
K
L
M
Q
R
S
T
3
5
6
HP side
Diaphragm &
flange face
316 stainless steel
Diaphragm:
316L stainless steel
+Au coating
Flange face:
316 stainless steel
Hastelloy-C
Monel
Tantalum
Hastelloy-C
Monel
Tantalum
Hastelloy-C
Monel
Tantalum
V
J
C
D
E
H
M
T
B
L
U
100% turn down is possible for model FKY, but should be used within indicated span for better performance.
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
9
10
11
12
Description
Note
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Z/S board
Analog, custom scale
None
attached.
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Conduit seal) (Available for 4th code "A","S")
TIIS, Flameproof (Cable gland seal) (Available for 4th code "A","S")
FM, Flameproof (or explosionproof) (Available for 4th code "B","T")
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Diaphragm extension [mm]>
Extension [mm]
Applicable material code
0
Any
50
100
(7th digit code "V" only, 11/2 in. flange is not applicable)
150
200
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Yes
(*2)
Yes
None
Note 2
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Note 2: (*2)
F KY
9 10 11 12 13
14 15
4
21
Digit No.
of code
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
A
B
C
D
X
R
G
H
K
P
T
V
Y
A
B
C
D
Y
B
C
E
M
N
P
Q
Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes".
7
FKY...4
1 2 3 4 5 6 7 8
Digit
13
14
15
21
Description
Note
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E")
High temp. 250°C
Silicone oil (7th digit code "V", "H")
High temp. and vacuum (250°C) Silicone oil (7th digit code "V" only)
<O-ring / Gasket and Teflon membrane>
O-ring / Gasket
Teflon membrane
Viton (O-ring)
None
Teflon (gasket)
None
Viton (O-ring)
Yes
(11th digit code "Y" only)
Teflon (gasket)
Yes
(13th digit code "H", "S" are not available.)
<Bolt/nut> (*3)
Note 3
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
304 stainless steel bolt / 304 stainless steel nut
<Other options> (*4)
Note 4
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Note 3: (*3) In case of tropical use, select stainless bolts and nuts.
Note 4: (*4) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
8
F KY
9 10 11 12 13
14 15
21
4
Y
W
G
A
D
H
S
A
B
C
D
A
B
E
H
J
K
L
T
U
V
Digit No.
of code
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA).
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit).
5. TAG No. (up to 26 alphanumerical characters), if required.
9
FKY...4
OUTLINE DIAGRAM (Unit:mm)
< 7th digit code : "V", "J", "C" , "D", "E", "H", "M"or "T" >
Vent / drain plug
(When the vent / drain plug attatched on the upper side of the detector)
In case of 4th digit code "T"
In case of 4th digit code "S.V.W.X"
In case of 4th digit
code "A.B.C.D.E"
In case of frange with
4 bolt holes
Fastener
(Flameproof only)
105
ø80
52.5
105
UP
ø80
43.5
94.5
8
10
"A" L. P. conn.
DOWN
88
N holes
h dia.
2
"C" Conduit conn.
Zero ADJ. screw
(27)
1
Note)
Vent / drain plug
"B" Conduit conn.
Cable gland (option)
With field ind.
Long vent/drain p lug (Option)
t
L.P. conn.
41.3
Oval flange screw
See table 1
Detail "A"
Detail "B"
Sensor unit
+
– CK+
+ CK–
–
10
t
N-øh
Flange
4th digit of the
code symbols
Y
0
A
50
B
100
10.5 to 17.5
C
150
11
D
200
11.5 to 18.5
Conduit conn.
J
K
9.5 to 12
10
H
G1/2
17
8
Rc1/4
4-19 JIS-10K-50A
B, T
1/2-14NPT
18
5
1/4-18NPT
4-19 JIS-20K-40A
C, V
Pg13.5
8
4.5
1/4-18NPT
D, W
M20
16
5
1/4-18NPT
E, X
Pg13.5
8
4.5
1/4-18NPT
4-19 JIS-10K-40A
1, H
155 120 36
2, J
140 105 39
3, K
155 120 38
8-19 JIS-20K-50A
4, L
160 120 42
4-23 JIS-30K-40A
5, M
165 130 42
8-19 JIS-30K-50A
A, Q
127
B, R
152 120.6 39.5 4-20 ANSI/JPI-150-2B
98.4 37.5 4-16 ANSI/JPI-150LB-1 1/2B
C, S
156 114.3 41
D, T
165 127 42.5 8-20 ANSI/JPI-300LB-2B
4-23 ANSI/JPI-300LB-1 1/2B
Cable gland is supplied in case offlamproof packing type.
ø11 cable is suitable.
15
Table 1
1
2
3
333 160 296
to 17
327 154 290
to 18
Press. conn.
M
A, S
140 105 36
Note)
G1/2
11th digit of
L
Mass approx, [kg]
Code symbols [mm]
+ –
0, G
J
Electronics unit
CONNECTION
DIAGRAM
øE
K
8
H
ø18.5
3
Inner of gasket
øD
ø13
M
Earth terminal
2.5
43
143
27
øD
øE
ø84
ø49
ø48
H.P. conn
5th digit
of Code
symbols
ø15
48
ø7
Detail "C"
17
L
20
Oval flange screw
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
SCREW DEPTH15
M10
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
< 7th digit code : "B", "L" or "U" >
Oval flange screw
See Table 1
In case of 4th digit code "T"
Fastener
(Flameproof only)
N holes
h dia.
10
8
"A" or "B"
L. P. conn.
41.3
In case of 4th digit code "S.V.W.X"
94.5
In case of flange with
4 bolt holes
In case of 4th digit code "A.B.C.D.E"
ø80
105
107
ø80
52.5
105
Up
88
Down
150
Note)
Vent / drain plug
Cable gland
(option)
(27)
323
Zero ADJ. screw
"C" Conduit conn. 1
"D" Conduit conn.
With field ind.
t
20
Details of "A"
4th of code symbols
"A, S" type
ø16
Details of "B"
4th of code symbols
"B, C, D, E, T, V, W, X" type
ø16
1/4-18NPT
0.1
2–0.1
–0.2
0.2
0
ø12+0.1
10
1
øD
øE
ø84
ø49
40.5
43
91
186
H.P. conn
286
Inner of gasket
ø4
Earth terminal
Electronics unit
Details of "C"
Details of "D"
ø13
ø15
– CK+ CK–
K
+
M
CONNECTION DIAGRAM
17
Sensor unit
+ –
J
G1/2
See table 1
5th digit
of Code øD
symbols
øE
t
140
105
36
4-19 JIS-10K-40A
1, H
155
120
36
2, J
140
105
39
3, K
155
120
38
8-19 JIS-20K-50A
0, G
N-øh
Flange
K
M
A, S
G1/2
17
8
4-19 JIS-10K-50A
B, T
1/2-14NPT
16
5
4-19 JIS-20K-40A
C, V
Pg13.5
8
4.5
D, W
M20
16
5
E, X
Pg13.5
8
4.5
4, L
160
120
42
4-23 JIS-30K-40A
165
130
42
8-19 JIS-30K-50A
A, Q
127
B, R
152 120.6 39.5
4-20 ANSI/JPI-150-2B
C, S
158 114.3 41
4-23 ANSI/JPI-300LB-1 1/2B
D, T
165
8-20 ANSI/JPI-300LB-2B
Note)
127
42.5
Conduit conn.
J
5, M
98.4 37.5
4th digit of the
code symbols
4-16 ANSI/JPI-150LB-1 1/2B
15
Oval flange screw
7/16-20UNF
SCREW DEPTH10
7/16-20UNF
SCREW DEPTH10
M10
SCREW DEPTH10
M10
SCREW DEPTH10
7/16-20UNF
SCREW DEPTH10
Table 1
Cable gland is supplied in case of flamproof packing type.
ø11 cable is suitable.
11
FKY...4
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng