FUJI EDSX6-104

FCX – C SERIES
DIFFERENTIAL PRESSURE TRANSMITTER
DATA SHEET
FHK, FKK
The FCX –C differential pressure transmitter accurately
measures differential pressure, liquid level or gauge pressure
and transmits proportional 4 to 20mA signal. The transmitter
utilizes the unique micromachined capacitive silicon sensor
with state-of-the-art microprocessor technology to provide
exceptional performance and functionality.
FEATURES
1. High accuracy
0.1% accuracy for all calibrated spans is the standard
feature covering 0.6kPa {60mbar} draft range to 2000kPa
{20bar} high differential. Fuji's micro-capacitance silicon
sensor assures this feature for all elevated or suppressed
calibration ranges without additional adjustment.
2. Minimum inventory
Electronics unit, communication module, local indicators
and electronics housing are interchangeable among all
FCX –C models. Process cover including bolts and nuts
are common for all DP and flow transmitters, rating 3.2
and 14MPa (32 and 140 bar).
3. Replaceable Communication Module
Fuji micro-electronics manufacturing technology offers
replaceable communication module that makes FCX-A/
C transmitter very unique design. In case of change in
communication protocol all that needs to be done is just
replace the module and the transmitter gets upgraded
to the new version.
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART compatible
devices can communicate with FCX-A/C series transmitters.
5. Application flexibility
Example features that render the FCX –C suitable for
almost any process applications includes.
– Analog indicator at either the electronics side or
terminal side
– Full range of hazardous location approvals
– Built-in RFI filter and lightning arrester
– 4 12 -digits LCD meter
SPECIFICATIONS
Functional specifications
Type:
Model FHK: 4 to 20mA
Model FKK: 4 to 20mA with digital signal
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Static pressure
[MPa] {bar}
Type
F K
12
F K
33
F K
35
F K
36
F K
37
–0.1 to + 3.2
{–1 to + 32 }
–0.1 to + 14
{–1 to + 140 }
–0.1 to + 14
{–1 to + 140 }
–0.1 to + 14
{–1 to + 140 }
–0.1 to + 14
{–1 to + 140 }
Span limit [kPa] {mbar}
Max.
Min.
FHK
FKK
FHK/FKK
0.6
0.375
6
{ 6 } { 3.75 } {
60 }
3.2
2
32
{ 32 } { 20 }
{ 320 }
13
8.125
130
{ 130 } { 81.25 } { 1300 }
50
31.25
500
{ 500 } { 312.5}
{ 5000 }
200
125
2000
{2000} {1250
} { 20000 }
Range limit
[kPa] {mbar}
+/–
6
{ +/–
60 }
+/–
32
{ +/–
320 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/– 2000
{ +/– 20000 }
EDSX6-104
Date
Feb. 2, 1999
FHK, FKK
– Lower limit of static pressure (vacuume limit) is:
Silicone fill sennsor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mm Hg abs)
at temperature below 80°C
– The maximum span of each sensor can be converted
to in different units using below factors.
1MPa=103kPa=10bar=
10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrage limit: To maximum static pressure limit
Output signal:
Model FHK: 4 to 20mA DC 2-wire, linear signal
Model FKK: 4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
}
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
16.1
10.5V
Power voltage
45V
50
[V]
Note: For communication with FXW, min. of 250Ω required.
Hazardous locations:
Authorities
BASEEFA
Factory
Mutual
CSA
SAA
2
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex d II C T5, T6
IP 66/67
Zero/span adjustment:
Model FHK: Zero is adjustable from an external adjustable screw.
The adjustable screw can also function to
adjust span when MODE SWITCH (located on the electronics unit) is in the span
mode. INHIBIT mode to disable the adjustable screw is also available.
Model FKK: Zero and span are adjustable either from
the HHC. Zero is also adjustable externally from the adjustable screw.
Damping:
Adjustable electrical damping.
Model FHK: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Model FKK: The time constant is adjustable between 0
to 38.4 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Model FHK: Selectable by moving a jumper pin located
on the electronics unit.
Model FKK: Selectable from HHC
Indication:
Analog indicator or 4 12 -digit LCD meter, as
specified.
Burnout direction:Output hold
Output 21.6mA selectable
Output 3.8mA
Model FHK: Unless otherwise specified, the burnout is
in hold position.
Model FKK: Selectable from HHC
Loop-check output:
Model FHK: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKK: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit: Ambient: –40 to +85°C
(–20 to +80°C for LCD indicator)
(–40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified in
each standard.
Process: –40 to +100°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: –40 to +90°C
Humidity limit:
0 to 100% RH
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
Ex ia II C T5, T6
IP 66/67
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
Ex n II C T5, T6
IP 66/67
Communication: (Model FKK only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Items
Display
Set
v
v
v
v
v
v
v
v
v
v
—
v
v
—
v
v
v
v
—
v
—
v
v
v
v
v
v
—
—
—
v
v
Tag No.
Model No.
Serial No.
Engineering unit
Range limit
Measuring range
Damping
Output mode
Burnout direction
Adjustment
Output adjust
Data
Self diagnoses
Printer
External switch lock
Transmitter display(*)
Note: (*) HHC's version must be higher than 5.0
(or FXW
1– 2), to use this function.
Performance specifications
Accuracy rating: (including linearity, hysteresis, and repeatability)
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL (Model FKK only):
± (0.05 + 0.05 0.1 x URL ) % of span
span
Stability:
0.2% of upper range limit (URL) for 24
months
(In case of 6th digit code "3", "5", "6", "7")
Temperature effect:
Effects per 28°C change between the limits of –40°C and +85°C
Range code
Zero shift,
(6th digit in Code symbols)
“2”/6kPa
max. span
{60mbar}
Zero
± (0.25
Total effect
URL )% / 28°C,
span
Total
± (0.25+0.25
“3”/32kPa
{320mbar}
max. span
“5”/130kPa {1300mbar}
max. span
“6”/500kPa {5000mbar}
max. span
“7”/ 2000kPa {20000mbar}
max. span
URL
span )% / 28°C
URL
Zero ± (0.1 span )% / 28°C
URL
Total ± (0.075+0.1 span )% / 28°C
Span shift
(% of calibrated span)
+ 0.2
±0.2%/10MPa{100bar} –0.2% – 0.3 /10MPa{100bar}
“1”
“3”
“2”
0.85 s
“3”
0.45 s
“4” through “7”
0.2 s
Dead time
approx. 0.3 s
Mounting position effect:
Zero shift, less than 0.12kPa {1.2mbar} for
a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
(Double the effect for fluorinated fill sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Performance specifications for square root output:
(Model FKK only)
Accuracy rating:
Span
Output
at (1 to 1/2.5) x URL
50 to 100%
20 to 50%
10 to 20%
± 0.1 %
± 0.25%
± 0.5 %
For span below 1/2.5 of URL
x URL )
± (0.05 + 0.05 0.1span
0.1 x URL
± 2.5 x (0.05 + 0.05
)
span
± 5 x (0.05 + 0.05 0.1 x URL )
span
OUTPUT 50 to 100%
OUTPUT 20 to 50%
OUTPUT 10 to 20%
Shift at 20% output point
“2”
URL
± (0.625 span )% / 28°C
“3” through “7”
URL
± (0.25 span )% / 28°C
Low flow cut-off: Customer configurable for any point between 7 to 20% of output
Overrange effect:
Static pressure code
(5th digit in Code symbols)
Time constant
Range code
Zero shift
(% of URL)
“1” /6kPa {60mbar} sensor ±0.4% / 3.2MPa{32bar} ±0.4% /3.2MPa{32bar}
“3”
Range code
Temperature effect:
Effect per 28°C change between the limits of –40°C and +85°C
Static pressure effect:
Static pressure code
(5th digit in Code symbols)
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
Zero shift (% of URL)
± 0.4% / 3.2MPa {32bar }
± 0.4% /14MPa
{140bar }
3
FHK, FKK
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
Process-wetted parts material:
Material
code
(7th digit Process cover
in Code
symbols)
V
Diaphragm
Wetted
sensor body
Vent/drain
316 stainless 316L stainless 316 stainless 316 stainless
steel(*1)
steel
steel
steel
Notes: * (1) SCS14 per JIS G 5121
Remark:
Sensor O-rings: Viton or teflon selectable.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with epoxy/polyurethane double coating, as specified.
Bolts and nuts: Cr-Mo alloy (standard),
304 stainless steel, or 630 stainless
steel. Static pressure rating for code
“3” with 304 stainless steel bolts is degraded to 10MPa(100bar).
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A or 2B) pipe using
mounting bracket, direct wall mounting,
or direct process mounting.
Mass{weight}:
Transmitter approximately 3.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
Optional features
Indicator:
A plug-in turnable analog indicator (1.5%
accuracy) can be housed in the electronics
compartment or in the terminal box of the
housing.
An optional 4 12 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity : 4KV (1.2 ×
50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
for oxygen or chlorine measurement.
4
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
Includes ASTM B7M or L7M bolts and
2HM nuts. (Class II)
Static pressure rating for code “3” (14
MPa(140bar)) is degraded to 10MPa
(100bar).
Silicone oil (Code:Y,G,N)
[kPa abs]
(mmHg abs)
101
(760)
Operating pressure
Physical specifications
Operating
area
20
(150)
4
(30)
2.7
(20)
None-operating
area
–40
60
100
Process temperature[°C ]
Fig. 1 Relation between process temperature and
operating pressure
Customer tag:
A stainless steel tag with customer tag
data is wired to the transmitter.
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless ateel.
Three-valve manifold:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in carbon steel or in 316 stainless steel and in pressure rating 14MPa
(140bar).
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Communication module: (standard for model FKK)
When using this module for model FHK,
remote setting function becomes available.
Remark: When the communication module is connected, the operation mode of external
zero/span adjustable screw is changed to
zero adjustment only.
CODE SYMBOLS
1 2 3 4 5 6 7 8
F
K
9 10 11 12 13
14 15
Description
1
Type
Without communication module
With communication module
H
K
Connections
S
T
V
W
X
Process conn.
Screw size for oval flange
Conduit conn.
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
7/16-UNF
7/16-UNF
M10 or M12
M10 or M12
7/16-UNF
G 1/2
1/2-14NPT
Pg 13.5
M20 x 1.5
Pg13.5
Span and materials
Static
pressure
Span limit
[MPa]
{bar}
[kPa]
{mbar}
–0.1 to +3.2 0.6/0.375
{–1 to +32}
{6/3.75
12V
33V
37V
Wetted
cell body
316 stainless
steel
…32
…320}
316 stainless 316L stainless
steel(*1)
steel
316 stainless
steel
…130
…1300}
316 stainless 316L stainless
steel(*1)
steel
316 stainless
steel
…500
…5000}
316 stainless 316L stainless
steel(*1)
steel
316 stainless
steel
316 stainless 316L stainless
200/125
…2000
{2000/1250 …20000} steel(*1)
steel
316 stainless
steel
Indicator and arrester
Indicator
None
Analog, 0 to 100% linear scale
Analog, 0 to 100% sq. root scale
Analog, custom scale
Analog, double scale
None
Analog, 0 to 100% linear scale
Analog, 0 to 100% sq. root scale
Analog, custom scale
Analog, double scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100% sq. root scale
Digital, 0 to 100%
Digital, custom scale
Digital, 0 to 100% sq. root scale
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
Diaphragm
316 stainless 316L stainless
steel(*1)
steel
13/8.125
{130/81.25
–0.1 to +14
{–1 to +140} 50/31.25
{500/312.5
36V
Element
Process
cover
…6
…60}
3.2/2
{32/20
35V
Material
Arrester
None
None
None
None
None (*2)
Yes
Yes
Yes
Yes
Yes (*2)
None
None
None
Yes
Yes
Yes
(Model FKK only) (*3)
(Model FKK only) (*3)
Approvals for hazardous locations
None (for ordinary locations)
FM, Flameproof (or explosionproof) (Available for 4th digit code "T")
CSA, Flameproof (or explosionproof) (Available for 4th digit code "T")
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and Nonincendive
CSA, Intrinsic safety and Nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal) ( Available for 4th digit code "S, T, W")
SAA Intrinsic safety ( Available for 4th digit code "S, T, W")
SAA Type – N (non-speaking) ( Available for 4th digit code "S, T, W")
A
D
E
M
N
H
J
K
P
R
T
Q
Process connection
A
C
D
F
Side vent Yes / No
None
None
Yes
Yes
Mounting bracket Yes / No
None
Yes (Stainless steel)
None
Yes (Stainless steel)
Note: *(1) SCS14 per JIS G 5121
*(2) The scale is selectable "JIS and SI unit" or "Linear and sq. root" or "Linear and sq. root by 10".
*(3) In case of FKC, specified, the output mode is linear.
In case of 9th digit code "P", "S" with FKC, specified, the indication is output is output mode.
5
FHK, FKK
1 2 3 4 5 6 7 8
F
K
9 10 11 12 13
14 15
Description
1
Optional specification
Stainless tag
None
Yes
Y
B
Special applications and fill fluid
Y
G
A
N
Treatment
Filled liquid
None (standard)
Degreasing
Oxgen service
NACE specification
Silicone oil
Silicone oil
Fluorinated oil
Silicone oil
O-ring materials
Viton
Teflon
A
B
A
B
C
D
E
F
Vent / drain plug type
Standard
Standard
Standard
Standard
Standard
Standard
Bolt / nut materials
Standard (Cr-Mo hex. socket head cap screw)
Cr-Mo hexagon bolt / nut
NACE bolt / nut (ASTM A193 B7M/A194 2HN)
(*2)
NACE bolt / nut (ASTM A320 L7M/A194 2HM)
304 / 304 stainless steel (*5)
(*3)
630 / 304 stainless steel (*5)
(*4)
}
Note : (2) Static pressure should be – 0.1 to +10MPa{–1 to +100bar}.
(3) Available for the 5th digit code "1" or "3". In case of the 5th digit code "3", static
pressure should be – 0.1 to +10MPa{–1 to +100bar}.
(4) Available for the 5th digit code "3". In case of stainless steel (630 stainless steel)
bolt, static pressure should be – 0.1 to +14MPa{–1 to +140bar}.
(5) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
Fastener
(flameproof ex. only)
Zero span adj. screw
4th of Code symbol "S, V, W, X"
U-bolt M8
type is attached
"A"
Press. conn.
MTG pipe
JIS 50A (2B)
50
70
110
126.5
φ80
104
45.5
UP
DOWN
88
4 holes
9 dia.
38
"B"
Conduit conn.
120
71
51
193
"C"
Conduit conn.
(27)
Details of "A"
Details of "B"
φ13
2.5
E
Higher
pressure
17
8
F
Oval frange
screw
See table 1
41.3
Details of "C"
φ15
φ7
221
58
Vent/drain plug
*Cable gland
With field ind.
(option)
φ80
Earth terminal
(both side)
See table 1
30
G
φ18.5
Lower
pressure
See table 1
54
G1/2
D
See table 1
70
120
4th of Code
symbols
S
Press. conn.
G
Conduit conn.
D
E
F
G1/2
T
1/2-14NPT
V
Pg13.5
W
M20×1.5
X
Pg13.5
17 8
16 5
8 4.5
16 5
8 4.5
Oval flange
screw
CONNECTION DIAGRAMS
Earth
terminal
Rc1/4
7/16-20UNF
screw depth 13
M4
1/4-18NPT
7/16-20UNF
screw depth 13
No. 8-32UNC
1/4-18NPT
M10 or M12
screw depth 13
M4
1/4-18NPT
M10 or M12
screw depth 13
M4
1/4-18NPT
7/16-20UNF
screw depth 13
M4
+
–
CK+
+
CK–
–
Table 1
<Optional stainless steel tag>
S
T
F
K V
K
W
X
75
H
V1
20
Note *: Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
7
FHK, FKK
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :EMI (Emission)
EN50081-1 : 1992
Test item
Frequency range
Basic standard
Applicable Electromagnetic Radiation
Disturbance
30-1000MHz
EN55022
Class B
EMS (Immunity)
EN50082-1 : 1992
No.
Test item
Test
specification
Basic
standard
Performance
criteria
1
Electrostatic
discharge
8kV (Air)
IEC 801-2:1984
B
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
IEC 801-3:1984
field.
(Unmodulated)
A
3
Fast transients
common mode
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan