FUJI EDSX6-106

FCX – AX SERIES
DIFFERENTIAL PRESSURE TRANSMITTER
Hydroseal® Diaphragm Version
FHC, FKC...3
DATA SHEET
FEATURES
1. Unique hydroseal diaphragm
Permeation of hydrogen into the detecting unit through
seal diaphragm can be suppressed thanks to the unique
seal diaphragm (double coating) which employs coating
of gold and ceramic.
Micro Capacitance
Silicone sensor
Base material
(SUS316L)
Process
cover
Sensor
unit
Ceramics
coating
Gold
coating
Sealing diaphragm
coated with gold
and ceramics
2. High accuracy
± 0.15% accuracy for all calibrated spans is the standard
feature for differential pressure (flow) transmitter
covering 3.2 to 130kPa (or 320mm to 13 mH2O). Fuji's
Micro-capacitance silicon sensor assures this feature.
3. Minimum environment influence
Fuji's patented "Advanced Floating Cell" design which
protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications.
4. Replaceable Communication Module
Fuji micro-electronics manufacturing technology offers
replaceable communication module the makes FCX-AX
transmitter very unique in design. In case of change in
communication protocol, all that needs to be done is
just to replace the module and the transmitter gets upgraded to the new version.
5. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART
compatible devices can communicate with FCX-AX
series trans-mitters.
6. Application flexibility
Various options that render the FCX-AX series suitable
for almost any process applications include.
— Analog indicator at either the electronics side or terminal side
— Full range of hazardous location approvals
— 4 12 -digit LCD meter
— Stainless steel electronics housing
— Built-in RFI filter and lightning arrester
7. Programmable output Linearization Function
In addition to Linear and Square Root, output signal
can be freely programmable.
(Up to 14 compensated points at approximation.)
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
8. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW hand
Held Communicator (HHC) to comply with NAMUR
NE43.
(Available for amplifier unit from version 24 and FXW(HHC) version
5.3.)
9. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Type:
Model FHC: 4 to 20mA, Traditional type
Model FKC: 4 to 20mA with digital signal, Smart type
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Span limit [kPa]
{mbar}
Static pressure
[MPa] {bar}
Type
Min.
FHC
F
F
C
C
33
35
–0.1
(–1
–0.1
(–1
to
to +
to
to +
16
160)
16
160)
FKC
3.2)
0.32
( 32 ) ( 3.2 )
13
1.3 )
( 130 ) ( 13 )
Max.
FHC/FKC
(
(
Range limit
[kPa] {m bar}
32) +/–
320) (+/–
130) +/–
1300) (+/–
32 1
320)
130))
1300)
EDSX6-106
EDS5-62b
Date
Mar. 15, 1999
FHC, FKC...3
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs)
at temperature below 80°C
– The maximum span of each sensor can be converted
to different units using below factors.
1MPa= 103KPa=10bar=10.19716kgf/cm2=
145.0377psi
1kpa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
Model FHC: 4 to 20mA DC 2-wire, linear signal
Model FKC: 4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
3.2
600Ω
24V
250
10
16.1
10.5V
Power voltage
45V
50
[V]
Hazardous locations: (Approval pending)
CSA
RIIS
SAA
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP 66/67
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
—
Ex ia II C T5, T6
IP 66/67
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
Ex n II C T5, T6
IP 66/67
Zero/span adjustment:
Model FHC: Zero is adjustable from the external adjustment screw.
The adjustment screw can also function
to adjust span when MODE SWITCH (located on the electronics unit) is in the
span mode. INHIBIT mode to disable the
adjustment screw is also available.
Model FKC: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Damping:
Adjustable electrical damping.
Model FHC: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Model FKC: The time constant is adjustable between
0 to 38.4 seconds. (4 steps)
Zero elevation/suppression:
–100% to +100% of URL
2
20 20.8
Over scale
Burnout
Note: For communication with HHC (Model: FXW), min. of 250 Ω required.
BASEEFA
Factory
Mutual
3.8 4
Operating
area
500
Authorities
Normal/reverse action:
Model FHC: Selectable by moving a jumper pin located
on the electronics unit.
Model FKC: Selectable from HHC
Indication:
Analog indicator or 4 12 -digit LCD meter, as
specified.
Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
Model FHC: Unless otherwise specified in the order,
the transmitter will be shipped in “Output
Hold” mode.
(Output signal just before failure happens
is maintained.)
Model FKC: Selectable from HHC
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Approx. 21.6mA
(Adjustable within the range 20.8mA to
21.6mA from HHC)
“Output Underscale”:
Approx. 3.8mA
(Adjustable within the range 3.2mA to
3.8mA from HHC)
0
Normal operating range
Under scale
Probable under range
Burnout
21.6
Probable over range
Loop-check output:
Model FHC: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKC: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit: Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified in
each standard.
Process: – 40 to +120°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Communication: (Model FKC only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Items
Display
v
v
v
v
v
v
v
v
v
v
—
v
v
—
v
v
v
v
Tag No.
Model No.
Serial No.
Engineering unit
Range limit
Measuring range
Damping
Output mode
Burnout direction
Adjustment
Output adjust
Data
Self diagnoses
Printer
External switch lock
Transmitter display(*)
Linearise
(**)
Rerange
(**)
Set
v
v
—
v
—
v
v
v
v
v
v
—
—
—
v
v
v
v
Notes: (*) HHC's version must be more than 5.0
(or FXW
1 – 2 ), to use this
function.
(**) HHC's version must be more than 5.3,
and Amplifier unit version 24.
Programmable output linearization function:
In smart version, output signal can be
characterized with “14 points linear approximation function” from HHC.
Performance specifications for linear output
Accuracy rating: (including linearity, hysteresis, and repeatability)
For spans greater than 1/10 of URL: ± 0.15% of span
For spans below 1/10 of URL (Model FKC only):
0.1×URL
± 0.1+0.05
% of span
Span
Linearity:
0.075% of calibrated span
Stability:
± 0.15% of upper range limit (URL) for 24
months
Temperature effect:
Effects per 55°C change between the limits of – 40°C and +85°C
(
)
Range code
(6th digit in Code Zero shift
symbols)
“3”/32kPa
{320mbar} max.
span
Range code
Time constant
Dead time
“3”
0.45 s
approx. 0.3 s
“5”
0.2 s
(6th digit in Code symbols)
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar} for
a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
(Double the effect for fluorinated fill sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Performance specifications for square root output
(Model FKC only)
Accuracy rating:
Span
Output
over 0.1 × URL
50 to 100%
± 0.15%
20 to 50%
± 0.375%
10 to 20%
± 0.75%
)
(
)
Temperature effect:
effect per 55°C change between the limits of – 40°C and +85°C
Range code
Static pressure effect:
Zero shift
(% of URL)
below 0.1 × URL
± (0.1+0.05 ×
0.1 ×URL/Span)%
± 2.5 × (0.1+0.05 ×
0.1 × URL/Span)%
± 5 × (0.1+0.05 ×
0.1 × URL/Span)%
Total effect
URL
± 0.1+0.075 URL %/28°C ± 0.125+0.075
%/28°C
Span
Span
(
Supply voltage effect:
Less than 0.05% of calibrated span per
10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
Span shift
(% of calibrated span)
±0.15%/10MPa{100bar} –0.2%/10MPa{100bar}
“3” through “5”
Shift at 20% output point
(
± 0.25+0.19
URL
%/28°C
Span
)
Low flow cut-off: Customer configurable for any point between 7 to 20% of output
Overrange effect:
Zero shift (% of URL)
± 0.3% /16MPa
{160bar } (*1)
(*1) in case of 6th code “5”
3
FHC, FKC...3
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 ×1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
Process-wetted parts material:
C
316 stainless
steel(*1)
Wetted
sensor body
316L stainless 316 stainless
steel(*2)
steel
Vent/drain
316 stainless
steel
Notes: * (1) SCS14 per JIS G 5121
(2) The diaphram face is coated with gold and ceramic.
Remark: Sensor O-rings: Viton and teflon selectable.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with epoxy/polyurethane double coating, or 304 stainless steel, as specified.
Bolts and nuts: Cr-Mo alloy (standard),
304 stainless steel (for static pressure
code “1”, “2”, and “3” only), or 630
stainless steel (for static pressure code
“3” and “4” only). Static pressure rating for code “3” with 304 stainless
steel bolts is degraded to 10MPa.
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as
specified
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm(JIS 50A) pipe using mounting
bracket, direct wall mounting, or direct
process mounting.
Mass{weight}:
Transmitter approximately 4.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
Silicon oil (Code : Y. G. N)
Silicon oil (Code : R)
[kPa abs]
{mmHg abs}
101
{1010}
Operating
area
Operating pressure
Material
code
(7th digit Process cover Diaphragm
in Code
symbols)
Chlorine service: The fill fluid is flourinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (16
MPa) is degraded to 10MPa.
Vacuum service: Special silicone oil and filling procedure
are applied.
See below figure.
20
{200}
4
{40}
2.7
{27}
Non-operating
area
–40 –15
Fig. 1 Relation between process temperature and
operating pressure
Customer tag:
Coating of cell:
Oval flanges:
Indicator:
4
A stainless steel tag with customer tag
data is wired to the transmitter.
Cell's surface is finished with epoxy/polyurethane double coating. Specify if
environmnet is extremely corrosive.
ACCESSORIES
Optional features
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 4 12 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity : 4KV (1.2 x
50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
60 85 120 [°C]
Process temeprature [°C]
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Equalizing valves:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in CS or in 316 stainless steel
and in pressure rating 16MPa or 42MPa.
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Communication module: (standard for model FKC)
When using this module for model FHC,
remote setting function becomes available.
Remark: When the communication module is connected, the operation mode of external
zero/span adjustable screw is changed to
zero adjustment.
CODE SYMBOLS
1 2 3 4 5 6 7 8
9 10 11 12 13
14 15
Description
3
Type
4 to 20mA, Output type
4 to 20mA with digital signal, Output type
FHC
FKC
Connections
Process
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
S
T
V
W
X
Oval flange
screw
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
Conduit
connection
G 1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Span and materials
Static
Span limit (*1)
pressure FHC/FKC
[MPa]
[kPa]
{bar}
(m bar)
33C
35C
Process
cover
Diaphragm
Wated
cell body
–0.1 to 16 3.2/0.32...32/32
316 stainles 316Lstainless 316 stainless
steel
(–1 to
(32/3.2...320/320)
steel
steel (*1)
+160)
13/1.3...130/130
(130/13...1300/1300)
Notes: * (1) The diaphragm face is coated with gold and ceramic.
5
FHC, FKC...3
1 2 3 4 5 6 7 8
FHC
3
F KC
3
9 10 11 12 13
14 15
Description
Indicator and arrester
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale
None
Analog, custom scale
None
Analog, double scale
None (*4)
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes
Analog, custom scale
Yes
Analog, double scale
Yes(*4)
Digital, 0 to 100%
None
Digital, custom scale
None (Model FKC only) (*5)
Digital, 0 to 100% square root
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes (Model FKC only) (*5)
Digital, 0 to 100% square root
Yes
Approvals for hazardous locations (Approval pending)
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
JIS, Flameproof (Cable gland seal)
FM, Flameproof (or explosionproof)
CSA, Flameproof (or explosionproof)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
JIS, Intrinsic safety
FM, Intrinsic safety and Nonincendive
CSA, Intrinsic safety and Nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA Flameproof (Conduit seal)(Available for 4th digit code "S,T,W")
SAA Intrinsic safety (Available for 4th digit code "S,T,W")
SAA Type–N (non-sparking)(Available for 4th digit code "S,T,W")
Side vent/drain and mounting brackert
Side vent/drain
Mounting bracket
None
None
None
Yes, carbon steel
None
Yes, stainless steel
Yes
None
Yes
Yes, carbon steel
Yes
Yes, stainless steel
Stainless steel parts
Stainless steel tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
None (standard)
Silicone oil
None (standard)
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil
NACE specification
Silicon oil
A
B
C
D
J
E
F
G
H
K
L
P
Q
M
S
N
A
B
C
D
E
M
N
G
H
J
K
P
R
T
Q
A
B
C
D
E
F
Y
B
C
E
M
N
P
Q
Y
W
G
A
N
Sensor O-ring
Viton
Teflon
A
B
A
B
C
D
E
Bolt/nut
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTMA 193 B7M/A 194 2HM)
(*3)
NACE bolt/nut (ASTMA 193 B7M/A 194 2HM)
304 stainless steel/304 stainless steel (*6)
}
Notes: * (3) Static pressure should be –0.1 to +10MPa{–1 to 100bar}
(4) The scale is selectable "JIS and SI unit" or "Linear and sq. root" or "Linear and sq. root by 10"
(5) In case of FKC, specified thhe output mode linear or sq. root. Unless specified the output mode
is linear. In case of 9th digit code "P", "S"with FKC, specified the output indication. Unless
specified, the indication is output mode.
(6) In case of tropical use, select a stainless bolts and nuts.
6
OUTLINE DIAGRAM (Unit:mm)
Vent/drain plug
(When the vent/drain plug attatched on
the upper side of the detector)
Zero/span ADJ. screw
Fastener
(In case of 10th
digit code “B,C,M,N“)
In case of 4th
digit code
“S,V,W,X“
“A“
Press. conn.
Mtg. Pipe
JIS 50A (2")
U - Bolt M8
70
110
50
126.5
104
ø80
43.5
Up
88
Down
37
120
71
51
58
242
With field ind.
(option)
Earth terminal
(both side )
see table1
4 Holes
9 dia.
38
Vent/drain plug
“B“
Conduit conn.
Cable gland (option)
see note
“C“
Conduit conn.
(27)
Detail “A“
(press conn.)
ø15
ø13
E
17
8
F
2.5
ø80
ø18.5
H
Detail “C“
DETAIL “B“
(Conduit conn.)
ø7
41.3
270
Side vent
(option)
D
Oval flange
screw
see table1 1
4-M8 × 12
L.P.
G 1/2
See table 1
see table 1
H.P.
54
70
104
4th of Code
symbols
Conduit conn.
D
F
E
Press. conn.
G
Oval flange
screw
Earth
terminal
+
S
G1/2
17 8
Rc1/4
7/16-20UNF
screw depth 13
M4
T
1/2-14NPT
16 5
1/4-18NPT
7/16-20UNF
screw depth 13
No. 8-32UNC
V
Pg13.5
1/4-18NPT
M10 or M12
screw depth 13
M4
W
M20x1.5
1/4-18NPT
M10 or M12
screw depth 13
M4
X
Pg13.5
1/4-18NPT
7/16-20UNF
screw depth 13
M4
8 4.5
16 5
8 4.5
Table 1
CONNECTION
DIAGRAM
–
CK+ CK–
+ –
S
T
H
C
F
V
K
W
X
C 3
Note *: Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
7
FHC, FKC...3
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510412. The applicable standards used to demonstrate
compliance are :EMI (Emission)
EN50081-1 : 1992
Test item
Frequency range
Basic standard
Applicable Electromagnetic Radiation
Disturbance
30-1000MHz
EN55022
Class B
EMS (Immunity)
EN50082-1 : 1992
No.
Test item
Test
specification
Basic
standard
Performance
criteria
1
Electrostatic
discharge
8kV (Air)
IEC 801-2:1984
B
2
Radio-frequency 27-500MHz
electromagnetic 3V/m
IEC 801-3:1984
field.
(Unmodulated)
A
3
Fast transients
common mode
0.5kV, 5/50
(Tr/Th) ns
5kHz Rep.
IEC 801-4:1988
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
Fax: 81-42-585-6187, 6189
Information in this catalog is subject to change without notice.
Printed in Japan