MAGNETROL 811-1305-Y02

Kotron® Model 811
RF Point Level Switch
D E S C R I P T I O N
The Kotron® Model 811 Level Switch offers the user great
flexibility. The switch can be used either as a single alarm
relay with narrow differential or for control purposes
with an adjustable differential. Using the proven
RF Capacitance technology, the Model 811 provides
reliable operation for a broad range of applications.
F E A T U R E S
• Useable for both narrow differential (alarm) and wide
differential (control)
• Intrinsically safe probe circuitry yields extra degree of
safety even with bare probes in hazardous media
• Remote mounting up to 150 feet (45 meters) with no
preamplifier on the probe provides protection from
high process temperatures or heavy vibration
• 10-amp DPDT relay provides flexibility for both alarm
and control applications
A P P L I C A T I O N S
• Guard circuitry and probe reject buildup of media
• Clean or dirty liquids
• Useable with all Kotron probes for application flexibility
• Viscous liquids
• LED shows relay status and aids in calibration and
troubleshooting
• Light slurries
• 0 to 120 second time delay feature eliminates relay
chatter due to turbulence
• High temperature/pressure liquids
• Corrosive liquids
• Hydrocarbons and solvents
• Field selectable high level/low level failsafe
• Acids and caustics
• Conformally coated circuit boards reduce circuit
problems due to moisture and fungus
• Foods and beverages
T Y P I C A L
A P P L I C A T I O N
P u m p / V a l v e
C o n t r o l
The Model 811 handles alarm applications as well as
pump/valve control applications with a wide or
adjustable differential.
Pump
control
C o a t i n g
R e j e c t i o n
Conductive coating
The Model 811 provides rejection of conductive buildup
by utilizing a guarded probe. Coating rejection circuit is
standard on all units.
I n t r i n s i c a l l y
S a f e
Non-hazardous Area
The Model 811-1X06-E0X is inherently intrinsically safe
when the main amplifier is mounted in a non-hazardous
area. Barriers are included in the 811 electronics eliminating the need for separate barriers.
811-1X06-E0X
Intrinsically safe circuit
2
Hazardous Area
T E C H N O L O G Y
The amount of capacitance developed in any vessel is
determined by the size (surface area) of the probe, the
As media rises and falls in the tank, the amount of
capacitance developed between the sensing probe and
distance from the probe to its ground, and the dielectric
of the medium being measured. Considering that the
the ground also rises and falls. This change in capacitance is compared to the adjustable set point and
probe’s mounting position is fixed and that the dielectric
value of the medium is constant, then the amount of
changes the state of a relay when they are equal.
capacitance developed in any vessel becomes dependent
upon the amount of the probe which is covered by
the media.
S P E C I F I C A T I O N S
Supply voltage
120 VAC, 50–60 Hz (+10%, -15%)
240 VAC, 50–60 Hz (+10%, -15%)
24 VDC (±10%)
12 VDC (±10%)
Power consumption
120 or 240 VAC Less than 5 volt-amps
12 or 24 VDC 1 watt maximum
Zero range
0 pF minimum to 1000 pF maximum
Adjustable differential
0.5 to 700 pF
Output relays (DPDT) with gold flash contacts
AC 10 amp @ 120/240 VAC resistive
DC 10 amp @ 30 VDC resistive
DC 0.5 amp @ 125 VDC resistive
Response time
100 milliseconds
Repeatability
Better than 1.0%
Ambient temperature
Electronics -40° to +160° F (-40° to +70° C)
Operating process pressure/temperature
Dependent upon probe selection; refer to probe bulletin 50–125
Guarded probe 8XD-AAXA-0XX 3500 psig @ +100° F (240 bar @ +40° C)
Temperature coefficient of set point
-40° to +160° F (-40° to +70° C) ±.01% per degree F of setpoint
(±.018% per degree C of setpoint)
3
D I M E N S I O N A L
I N C H E S
S P E C I F I C A T I O N S
( m m )
Rotation clearance:
2.63 (66)
3/4" PT
Conduit
connection
(plugged)
➀ 9.33 (247)
3/4" NPT
Conduit
connection
Optional
mounting
flange
3/4" NPT
thread
Rotation clearance:
3.00 (76)
Rotation clearance:
2.63 (66)
3/4" NPT
Conduit
connection
➀ 7.75 (197)
2 Holes
.38 (10) dia.
2.00
(51)
3/4" NPT
Conduit
connection
2.37
(60)
3/4" NPT
Conduit
connection
(plugged)
3.00
(76)
3.50
(89)
3/4" NPT
Thread
1/2" NPT (opt.)
3/4" NPT (std.)
Transducer/Amplifier
cable connection
3.75
(95)
➁
.375 (10)
4.11
(104)
6.86
(174)
18" (455)
or
36" (915)
Integral Mount with Guarded Probe
.375 (10)
Remote Mount with Guarded Probe
Rotation clearance:
2.63 (66)
3/4" NPT
Conduit
connection
(plugged)
➀ 8.45 (215)
3/4" NPT
Conduit
connection
Rotation clearance:
2.63 (66)
3/4" NPT
Conduit
connection
➀ 7.75 (197)
Optional
mounting
flange
3/4" NPT
Conduit
connection
¬
2 Holes
.38 (10) dia.
2.00
(51)
.50 (13) Bare probes
.625 (16) Insulated probes
3/4" NPT
Conduit
connection
(plugged)
2.37
(60)
3.00
(76)
3.50
(89)
3.75
(95)
➁
5.98
(152)
➂
1/2" NPT (opt.)
3/4" NPT (std.)
Transducer/Amplifier
cable connection
Integral Mount with Standard Rigid Probe
Remote Mount with Standard Rigid Probe
4
Rotation clearance
3.00 (76)
.50 (13) Bare probes
.625 (16) Insulated
probes
D I M E N S I O N A L
I N C H E S
S P E C I F I C A T I O N S
( m m )
Rotation clearance:
2.63 (66)
3/4" NPT
Conduit
connection
(plugged)
➀ 9.89 (251)
3/4" NPT
Conduit
connection
Optional
mounting
flange
.1875 (5)
.2500 (6)
1.32
(34)
➂
Optional
anchor assembly
4.87
(124)
2.95
(75)
5.00
(127)
.79
(19)
.79
(19)
Optional
weight
Integral Mount with Flexible Probe
Rotation clearance
3.00 (76)
Rotation clearance:
2.63 (66)
3/4" NPT
Conduit
connection
➀ 7.75 (197)
3/4" NPT
Conduit
connection
2.37
2 Holes
(60)
.38
(10) dia.
3.00
2.00
(76)
(51)
3.50
(89)
3/4" NPT
Conduit
connection
(plugged)
3.75
(95)
➁
7.42
(188)
3/4" NPT
Thread
1/2" NPT (opt.)
3/4" NPT (std.)
Transducer/
Amplifier
cable
connection
.1875 (5)
.2500 (6)
1.32
(34)
4.87
(124)
➂
2.95
(75)
5.00
(127)
.79
(19)
Optional
anchor
assembly
.79
(19)
Optional
weight
Remote Mount with Flexible Probe
NOTES:
Allow 6.00 (152) overhead clearance for removal of cover.
Probe/Amplifier Connecting Cable to be triaxial. Magnetrol
part number 037-3180-XXX standard or part number
037-3184-XXX high temperature.
Standard process connection is 3⁄4" NPT. Consult probe
brochure (50-125) for flange and other probe connections.
5
A G E N C Y
AGENCY
FM
A P P R O V A L S
APPROVED MODEL
PROTECTION METHOD
AREA CLASSIFICATION
811-1X05-E0X
Explosion Proof
Explosion proof with intrinsically safe probe circuit
811-1X06-E0X
Class I, Div. 1, Groups C & D
with probe models:
041-5XXX-XXX and
8XX-XXX-XXX
Class II, Div. 1, Groups E, F, & G
811-1X06-E0X
CSA
NEMA 4X
Intrinsically Safe
Remote probe:
(Remote)
Class I, Groups A, B, C, & D
with probe models:
041-5XXX-XXX and
8XX-XXX-XXX
Class II, Div. 1, Groups E, F, & G
811-1X05-E0X
Class III, NEMA 4X
Explosion Proof
Explosion proof with intrinsically safe probe circuit
811-1X06-E0X
Class I, Div. 1, Groups C & D
with probe models:
041-5XXX-XXX and
8XX-XXX-XXX
Class II, Div. 1, Groups E, F, & G
811-1X06-E0X
(Bare probes not approved for Groups E & F)
TYPE 4X
Intrinsically Safe
Remote probe:
(Remote)
Class I, Div. 1, Groups A, B, C, & D
with probe models:
041-5XXX-XXX and
8XX-XXX-XXX
Class II, Div. 1, Groups E, F, & G
(Bare probes are not approved for Groups E & F)
Class III, TYPE 4X
These units have been tested to EN 50081-2
and EN 50082-2 and are in compliance with
the EMC Directive 89/336/EEC.
6
M O D E L
F M
&
C S A
N U M B E R
A P P R O V E D
Models available for quick shipment, usually within one week after factory
receipt of a complete purchase order, through the Expedite Ship Plan (ESP).
Applies only if Model 811 and selected probe both qualify for ESP.
BASIC MODEL
811 Kotron RF Capacitance Level Switch
INPUT POWER
0
120 VAC
1
240 VAC
2
24 VDC
3
12 VDC
MOUNTING
5
Integral
6
Remote
HOUSING
NEMA 4X/7/9 Groups C & D, aluminum,
E
3
⁄4" NPT dual conduit
Y
NEMA 4X/7/9 Groups C & D, stainless steel,
3
⁄4" NPT single conduit
PROBE
0
Probe ordered separately
1
18" (455 mm) guarded probe
2
36" (915 mm) guarded probe
8
1
1
1
0
0
P R O B E S
R E M O T E
C A B L E
A full range of rigid and flexible probes for conductive and non-conductive materials is available in
various lengths and materials of construction. For
further information on probe assemblies, refer to
bulletin 50-125.
Specify connecting cable by exact length between
10 and 150 feet.
Standard cable (+175° F / +80° C) Magnetrol part
number 037-3180-XXX (length in feet).
High temperature cable (+390° F / +200° C)
Magnetrol part number 037-3184-XXX (length in feet).
7
Q U A L I T Y
The quality assurance system in place at
Magnetrol guarantees the highest level of
Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment
quality throughout the company. Magnetrol
is committed to providing full customer
to known international quality standards
providing the strongest assurance of product
satisfaction both in quality products and
and service quality available.
quality service.
E S P
Expedite
Ship
Plan
Several Kotron Model 811 RF Point Switches
are available for quick shipment, usually
within one week after factory receipt of a
purchase order, through the Expedite Ship
Plan (ESP).
To take advantage of ESP, simply match the
color coded model number codes (standard
dimensions apply).
ESP service may not apply to orders of ten
units or more. Contact your local representative for lead times on larger volume orders, as
well as other products and options.
W A R R A N T Y
All Magnetrol electronic level and flow
controls are warranted free of defects in
materials or workmanship for one full year
from the date of original factory shipment.
If returned within the warranty period; and,
upon factory inspection of the control, the
cause of the claim is determined to be covered under the warranty; then, Magnetrol
will repair or replace the control at no cost
to the purchaser (or owner) other than
transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or consequential
damage or expense arising from the installation or use of equipment. There are no
other warranties expressed or implied, except
special written warranties covering some
Magnetrol products.
For additional information, see Instruction Manual 50-608.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2010 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
Magnetrol & Magnetrol logotype and Kotron are registered trademarks of Magnetrol International.
BULLETIN: 50-103.7
EFFECTIVE: May 2010
SUPERSEDES: April 2005