ALTECH PST240_1

PST-240 Series
240W Three Phase Industrial DIN Rail Power Supply
F ea tures :
T hree-P ha s e A C 3 40 ~ 5 50V w ide r a nge i nput
High e fficiency 8 9% a nd low dis s ipa tion
P rotections :S hort circuit/O ver loa d/O ver v olta ge/O ver tempera ture
C ooling by f ree a ir c onvection
B uilt-in c ons ta nt current limiting c ircuit
C a n be i ns ta lled on D IN r a il T S -35/7.5 o r 1 5
U L 5 08(indus tria l c ontrol e quipment)a pproved
E N61000-6-2(E N50082-2) i ndus tria l immunity l evel
100% f ull loa d burn-in tes t
3 y ea rs w a rra nty
R
SPECIFICATION
MODEL
OUTPUT
INPUT
PST-24024
PST-24048
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
VOLTAGE ADJ . R ANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE R EGULATION
0.5%
LOAD REGULATION
0.5%
1200ms, 40ms, 20ms/400VAC
VOLTAGE R ANGE
Three-Phase 340 ~ 550VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
89%
AC CURRENT
INRUSH CURRENT (max.)
0.95A/400VAC
0 .75A/500VAC
COLD START 50A
OVER L OAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
OTHERS
8 00ms, 40ms, 40ms/500VAC at full load
4 80 ~ 780VDC
<3.5mA / 530VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V
59 ~ 66V
Protection type : Shut down o/p voltage, re-power on to recover
100
5
(TSW) Detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
0.03%/
(0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL508, EN60950-1 Approved, UL60950-1
I/P-O/P:3KVAC
I /P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), E N55022 (CISPR22), E N61204-3 Class B
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,1
1, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria
A
MTBF
114.6Khrs min. MIL-HDBK-217F (25 )
125.5*125.2*100mm (W*H*D)
1.3Kg; 12pcs/16.6Kg/1.34CUFT
DIMENSION
PACKING
NOTE
0.5%
SETUP, R ISE, HOLD TIME
LEAKAGE C URRENT
(Note 4)
0.5%
1. A ll parameters N OT s pecially mentioned a re measured a t 400VAC i nput, r ated load a nd 25 of ambient temperature.
2. R ipple & n oise a re measured a t 20MHz o f bandwidth by using a 1 2" twisted pair-wire terminated with a 0 .1uf & 4 7uf parallel capacitor.
3. T olerance : i ncludes s et up tolerance, line regulation a nd load regulation.
4. T he power s upply is c onsidered a c omponent which will be installed into a f inal equipment. T he final equipment must be re-confirmed that it still meets
E MC d irectives.
5. D ual phase operation: d erating of 20% i s r equired.
35 Royal Road, Flemington, NJ 08822-6000 • (tel.) 908-806-9400 • (fax) 908-806-9490 • www.altechcorp.com
PST-240 Series
240W Three Phase Industrial DIN Rail Power Supply
Mechanical Specification
125.5
125.5
100
TB1
4 3 2 1
LE D
TB2
4 3 2 1
+V ADJ.
35
Admissible Din Rail: TS35/7.5 or TS35/15
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
TB2 Terminal Pin. No Assignment
Assignment
FG
AC/L3
AC/L2
AC/L1
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Static Characteristics
Derating Curve
100
100
Three phase operation
90
80
80
LOAD (%)
LOAD (%)
Dual phase operation
70
60
40
20
60
50
40
-20
0
10
20
30
40
AMBIENT TEMPERATURE (
50
)
60
70 (VERTICAL)
340
355
370
385
400
415 430
460 475
490
505 520 550
INPUT VOLTAGE (VAC) 60Hz