PST-240 Series 240W Three Phase Industrial DIN Rail Power Supply F ea tures : T hree-P ha s e A C 3 40 ~ 5 50V w ide r a nge i nput High e fficiency 8 9% a nd low dis s ipa tion P rotections :S hort circuit/O ver loa d/O ver v olta ge/O ver tempera ture C ooling by f ree a ir c onvection B uilt-in c ons ta nt current limiting c ircuit C a n be i ns ta lled on D IN r a il T S -35/7.5 o r 1 5 U L 5 08(indus tria l c ontrol e quipment)a pproved E N61000-6-2(E N50082-2) i ndus tria l immunity l evel 100% f ull loa d burn-in tes t 3 y ea rs w a rra nty R SPECIFICATION MODEL OUTPUT INPUT PST-24024 PST-24048 DC VOLTAGE 24V 48V RATED CURRENT 10A 5A CURRENT RANGE 0 ~ 10A 0 ~ 5A RATED POWER 240W 240W RIPPLE & NOISE (max.) Note.2 80mVp-p 80mVp-p VOLTAGE ADJ . R ANGE 48 ~ 55V 1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE R EGULATION 0.5% LOAD REGULATION 0.5% 1200ms, 40ms, 20ms/400VAC VOLTAGE R ANGE Three-Phase 340 ~ 550VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 89% AC CURRENT INRUSH CURRENT (max.) 0.95A/400VAC 0 .75A/500VAC COLD START 50A OVER L OAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC OTHERS 8 00ms, 40ms, 40ms/500VAC at full load 4 80 ~ 780VDC <3.5mA / 530VAC 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 30 ~ 36V 59 ~ 66V Protection type : Shut down o/p voltage, re-power on to recover 100 5 (TSW) Detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes UL508, EN60950-1 Approved, UL60950-1 I/P-O/P:3KVAC I /P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), E N55022 (CISPR22), E N61204-3 Class B EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,1 1, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A MTBF 114.6Khrs min. MIL-HDBK-217F (25 ) 125.5*125.2*100mm (W*H*D) 1.3Kg; 12pcs/16.6Kg/1.34CUFT DIMENSION PACKING NOTE 0.5% SETUP, R ISE, HOLD TIME LEAKAGE C URRENT (Note 4) 0.5% 1. A ll parameters N OT s pecially mentioned a re measured a t 400VAC i nput, r ated load a nd 25 of ambient temperature. 2. R ipple & n oise a re measured a t 20MHz o f bandwidth by using a 1 2" twisted pair-wire terminated with a 0 .1uf & 4 7uf parallel capacitor. 3. T olerance : i ncludes s et up tolerance, line regulation a nd load regulation. 4. T he power s upply is c onsidered a c omponent which will be installed into a f inal equipment. T he final equipment must be re-confirmed that it still meets E MC d irectives. 5. D ual phase operation: d erating of 20% i s r equired. 35 Royal Road, Flemington, NJ 08822-6000 • (tel.) 908-806-9400 • (fax) 908-806-9490 • www.altechcorp.com PST-240 Series 240W Three Phase Industrial DIN Rail Power Supply Mechanical Specification 125.5 125.5 100 TB1 4 3 2 1 LE D TB2 4 3 2 1 +V ADJ. 35 Admissible Din Rail: TS35/7.5 or TS35/15 TB1 Terminal Pin. No Assignment Pin No. 1 2 3 4 TB2 Terminal Pin. No Assignment Assignment FG AC/L3 AC/L2 AC/L1 Pin No. 1,2 3,4 Assignment DC OUTPUT +V DC OUTPUT -V Static Characteristics Derating Curve 100 100 Three phase operation 90 80 80 LOAD (%) LOAD (%) Dual phase operation 70 60 40 20 60 50 40 -20 0 10 20 30 40 AMBIENT TEMPERATURE ( 50 ) 60 70 (VERTICAL) 340 355 370 385 400 415 430 460 475 490 505 520 550 INPUT VOLTAGE (VAC) 60Hz 35 Royal Road, Flemington, NJ 08822-6000 • (tel.) 908-806-9400 • (fax) 908-806-9490 • www.altechcorp.com