Front-end shelves for AFE2000 series power supplies
Distributed power architecture
UL and TUV approval
Hot-swap power system
N+1 redundancy
to find a suitable alternative.
The AFS4000 and AFS6000 power shelves are designed to house Artesyn standard
AFE2000 series front-end power supplies. The shelves mount into standard 19 inch
racks. The power shelves accept high range (200 to 240VAC) AC power and deliver a
regulated DC bus voltage generated from the AFE2000 power supplies. The power
shelf provides input filtering and protection and individual 20 Amp circuit breakers for
each AFE2000 power supply are provided on the front end of the shelf. An output bus
bar on the rear of the unit is provided for distribution of the main output to system
payload. Control, diagnostic and protection signals and the auxiliary output from
AFE2000 power supplies are routed through the power shelf to a parallel interface
connector on the rear of the unit. Clearance is provided on the rear of the unit to
maintain adequate airflow and cooling of the AFE2000 power supplies mounted within
the shelf.
[ 2 YEAR WARRANTY ]
POWER SHELF
MAIN OUTPUT
POWER
N+1 REDUNDANT
POWER
HEIGHT
AFE2000 POWER
SUPPLIES
SIGNAL
INTERFACE
AFS4000-3U2P
4000W
2000W
3U (5.25 inch)
2
Parallel via 25 pin D
type connector
AFS6000-4U3P
6000W
4000W
4U (7.0 inch)
3
Parallel via 37 pin D
type connector
AFS Power Shelf Characteristics
POWER MODULE
POWER SHELF
AFE2000-26S48NA
AFE2000-26S54NA
AFE2000-26S56NA
AFS4000-3U2P
48V @ 83A
12V @ 2A
54.5V @ 73A
12V @ 2A
56.2V @ 71A
12V @ 2A
AFS6000-4U3P
48V @ 124A
12V @ 3A
54.5V @ 109A
12V @ 3A
56.2V @ 106A
12V @ 3A
AFE2000 Output Configurations with AFS Power Shelves
Nominal Input Voltage
Line Current (Typical)
200VAC
11.6A rms
200VAC
11.2A rms
220VAC
10.6A rms
240VAC
9.7A rms
AC Input Line Cord Current
(for each AFE2000 module within power shelf)
PAGE 1
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
|
2000W AC/DC
AFS4000 and AFS6000 Rack-mountable
power shelves for AFE2000 series modules
Mechanical Notes for AFS4000-2U2P Interface Drawing
1
All dimensions in inches (mm).
NORMAL
AIR FLOW
VENT AREA
(KEEP FREE OF OBSTRUCTIONS)
ALLOW 6" CLEARENCE
FRONT / BACK TO
INSURE ADEQUATE
COOLING
17.32
(439.93)
CUSTOMER SIGNAL
ACCESS (CONNECTOR)
MATE - USE 25 PIN
D-TYPE CONNECTOR
VENTING FOR POWER SYSTEM
OPTION SLOT PWB - FARSIDE
A
AC SECTION
BREAKERS/LINE FILTERS
0.12
(3.05)
13.5 (342.90)
CUSTOMER DC OUTPUT
POWER BUS ACCESS
(TWO 10-32 STUDS
EACH OUTPUT
VIEW A-A
REAR VIEW
AFE2000 SERIES
HOT PLUGGABBLE
POWER SUPPLIES
CHASSIS GND
(#8-32 STUDS)
CUSTOMER 200-240 VAC INPUTS
HUBBELL H320BL
MATE - USE 20 AMP POWER CORD
WITH HUBBELL H320C CONNECTOR
POWER SYSTEM
OPTION SLOT
0.406
(10.312)
1.50
(31.0)
REF
TYP
0.265
(6.731)
TYP
2.250
5.22
(132.59) (57.150)
AC GOOD
PWR GOOD
FAIL
V OUT
AC GOOD
CLEARANCE TO ACCOMMODATE
CABINET RAIL MTG/SUPPORT
PWR GOOD
MOUNTING BRACKETS
OPTIONAL LOCATION
FAIL
A
V OUT
1.49 (37.85)
0.093 (2.362) REF
18.31 (465.07)
19.00 (482.60)
International Safety Standard Approvals
EN60950/IEC950 File No. E9972397
UL1950 File No. E135734
Please consult our website for the following items: ✔ Application Note
http://www.artesyn.com
PAGE 2
2000W AC/DC
|
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
AFS4000 and AFS6000 Rack-mountable
power shelves for AFE2000 series modules
Mechanical Notes for AFS6000-4U3P Interface Drawing
1
All dimensions in inches (mm).
NORMAL
AIR FLOW
CHASSIS GND
(#9-32 STUDS)
ALLOW 6" CLEARANCE
FRONT/BACK TO INSURE
ADEQUATE COOLING
VENT AREA
(KEEP FREE OF OBSTRUCTIONS)
17.32
(439.93)
CUSTOMER SIGNAL
ACCESS (CONNECTOR)
MATE - USE 37 PIN
D-TYPE CONNECTOR
13.70
(347.98)
VIEW A-A
REAR VIEW
CUSTOMER 200-240 VAC INPUTS
HUBBELL H320BL
MATE - USE 20 AMP POWER CORD WITH
HUBBELL H320C CONNECTOR
AFE2000 SERIES
HOT PLUGGABLE
POWER SUPPLIES
AC SECTION
BREAKERS/LINE FILTERS
0.12
(3.05)
1.50
(38.10)
REF
A
CUSTOMER DC OUTPUT
POWER BUS ACCESS
(THREE 10-32 STUDS
EACH OUTPUT)
0.406
(10.312)
0.265
(6.731)
AC GOOD
AC GOOD
AC GOOD
FAIL
FAIL
FAIL
PWR GOOD
PWR GOOD
PWR GOOD
1.750
(44.45)
1.750
(44.45)
6.97
(177.04)
1.750
(44.45)
0.86
(21.84)
A
MOUNTING BRACKETS
OPTIONAL LOCATION
0.093 (2.36) REF
CLEARANCE TO ACCOMMODATE
CABINET RAIL MTG/SUPPORT
V OUT
V OUT
V OUT
18.08 (459.23)
18.98 (482.09)
DIMENSIONS IN INCHES (MM)
PAGE 3
ds_afs4000_6000_obs_obs_20010404.PDF
Data Sheet © Artesyn Technologies® 2001
The information and specifications contained in this data sheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.