IVO PCD41.013PX01

Process displays electronic
Analgoue measured value input, 2 limits
Large 14 mm display LED, 6-digits, programmable
PCD41
Features
–– Process display
–– Display 6-digits
–– Connection: One-channel analogue sensor
–– Two limits as relay output
–– With peak value memory
–– Interface RS232 or RS422/RS485
Description
Voltage supply
115/230 VAC ±10 % (50/60 Hz)
24/48 VAC ±10 % (50/60 Hz)
12...30 VDC
Power consumption
6 VA, 4 W
Sensor supply
12...26 VDC / max. 80 mA
PCD41 is a display for measured values which signals are
available as voltage or DC current. The operator is aligning the display by means of the front keypad. Two optional
limits “P1” and “P2” that can be assigned at will allow production process control. Furthermore there is an electronic
peak value memory (slave pointer).
Display
LED, 7-segment display
Number of digits
6-digits
Technical data - mechanical design
Digit height
14 mm
Operating temperature
0...+50 °C
Function
Digital display of 1 analogue
measured value
Storing temperature
-20...+70 °C
Relative humidity
80 % non-condensing
Core cross-section
1.5 mm²
Protection DIN EN 60529
IP 65 face with seal
Operation / keypad
Membrane with softkeys
Housing type
Housing for control panel
installation
Dimensions W x H x L
96 x 48 x 124 mm
Cutout dimensions
94 x 45 mm (+0.6)
Installation depth
123.75 mm
Mounting
Front panel installation by clip
frame
Weight approx.
350 g (AC), 250 g (DC)
Material
Housing: Makrolon 6485 (PC)
Measuring principle
Analogue resolution 12 bit
Input logic
PNP
Control inputs
2 Inputs
Control functions
Hold, Reset, Keylock, etc.
Data memory
>10 years in EEPROM
Analogue input
0(2)...10 V, 0(4)...20 mA
Resolution 12 bit
Temp. coeffic. typ. ±20 ppm/°C
Outputs relay
Normally open or closed,
programmable
Interfaces
RS232, RS422, RS485
Standard
DIN EN 61010‑1
Protection class II
Overvoltage category II
Pollution degree 2
Emitted interference
DIN EN 61000-6-3
Interference immunity
DIN EN 61000-6-2
Programmable
parameters
2 limits, analogue input
Control inputs
Calculating functions
Offset (maximum and minimum
analogue limit)
Approvals
UL/cUL, CE conform
1
www.baumerivo.com
30/10/2008
Technical data - electrical ratings
Subject to modification in technic and design. Errors and omissions excepted.
PCD41 - Process display
Process displays electronic
Analgoue measured value input, 2 limits
Large 14 mm display LED, 6-digits, programmable
PCD41
Part number
Block circuit diagram
PCD41.
PX01
Voltage
supply
+
Analog input
Voltage supply
1 24 / 48 VAC
2 115 / 230 VAC
3 12...30 VDC
0
1
2
3
1
7
8
2
9
Control input
1
2
Measuring value
11
Output
12
3
Measuring
value
RS485
T,R+
RS422
TxD+ 22
T,R-
TxD- 23
Limit 1
4
Limit 2
5
6
P1
P2
Interface
RS485/RS422
RxD+ 24
Interface
0 Without interface
1 RS422 / RS485
2 RS232
+
Peak-value memory
10
Inputs / outputs
0...10 V / without limits
0...20 mA / without limits
0...10 V / with limits
0...20 mA / with limits
Sensor
supply
-
RxD- 25
TxD 22
Interface
RS232
RxD 24
GND 25
Connection diagram
1
+
8
7
- +24V 0V
6
5
4
3
2
1
P2
P1
Limit value
Sensor
supply
Analog
input
max. 250 V
terminal - terminal /
- terminal
T,RT,R+
RS232
Control
input
TxD
RxD
GND
RS422
RS485
Comparator inputs
Input circuit
Control inputs
PNP-logic
Input level
Programmable
Input level Low
0...2 VDC
Input level High
3...40 VDC
Input resistance
3 kΩ
Relay outputs
Output circuit
Switching voltage max.
250 VAC / 110 VDC
Switching current max.
1A
Switching capacity max.
150 VA / 30 W
Relay responding time
5 ms
Dimensions
96
7
48
123.75
109
19.75
1-10
2
www.baumerivo.com
30/10/2008
2
9
Supply voltage
TxD+
TxD-
RxD+
RxD-
12 11 10
Subject to modification in technic and design. Errors and omissions excepted.
Trigger level
25 24 23 22