Time and hours meters electronic 2 presets, PNP, NPN or AC logic Display LCD, 6-digits, programmable BE134 Features –– Hour counter with 2 presets –– Display 6-digits –– Totalizer for hour –– Counting range 9999.99 s / 999.95.9 min / 9999.59 min / 9999.59 h –– With reset –– Connection: Count impulse, NPN, PNP, AC logic –– Batch counter with preset Technical data - mechanical design Voltage supply Operating temperature 0...+50 °C Storing temperature -20...+70 °C Relative humidity 80 % non-condensing E-connection Plug-in screw terminals Core cross-section 1.5 mm² 22...50 VAC (50/60 Hz) 85...265 VAC (50/60 Hz) 12...30 VDC Power consumption 5 VA, 5 W Sensor supply AC: 24 VDC ±20 % / 100 mA DC: 9...28 VDC / 100 mA Display LCD, 7-segment display, 2-lines, backlit Protection DIN EN 60529 IP 65 face with seal Operation / keypad Membrane with softkeys Number of digits 6-digits 8-digits - totalizer in 2 steps Housing type Built-in housing 7 mm (count) 4 mm (preset) Dimensions W x H x L 48 x 48 x 100 mm Installation depth 100 mm Mounting Clip frame Cutout dimensions 45 x 45 mm (+0.6) Materials Housing: Makrolon 6485 (PC) Keypad: Polyester Weight approx. 150 g Digit height Function Hour counter Main counter with 2 presets Count mode Adding or subtracting Counting frequency Batch counter: approx. 20 Hz Operating mode Time meter and hour counter Data memory >10 years in EEPROM Reset Button, electric or automatic Keylock Yes, electric (keylock) Outputs electronic Optocoupler Outputs relay Normally open or closed, programmable Output holding time 0.01...99.99 s Interface RS485 Standard DIN EN 61010‑1 Protection class II Overvoltage category II Pollution degree 2 Emitted interference DIN EN 61000-6-4 Interference immunity DIN EN 61000-6-2 Programmable parameters Measuring units, sensor logic Control inputs Approvals UL/cUL, CE conform 1 www.baumerivo.com 30/10/2008 Technical data - electrical ratings Subject to modification in technic and design. Errors and omissions excepted. BE134 with two presets Time and hours meters electronic 2 presets, PNP, NPN or AC logic Display LCD, 6-digits, programmable BE134 Part number Block circuit diagram AX01 Voltage supply Voltage supply 1 22...50 VAC 2 85...265 VAC 3 12...30 VDC Adaptor plate for clip mount, face 53.2 x 53.2 mm Z 118.035 Adaptor plate for clip mount, face 60 x 75 mm Connection diagram Main counter with presets 3 Output 3 2 Signal input 1 P2 P1 Outputs max. 265 V terminal - terminal/ RS485 Sensor supply 6 5 3 Signal input 2 1 P2 P1 Outputs max. 265 V terminal - terminal / - terminal 7 A 1 Control input 4 8 B 9 2 3 0V +24V T,R- 15 14 13 12 11 10 T,R+ 7 4 9 2 10 3 11 - P1 5 6 P2 Batch counter with or without preset Interface RS485 Input circuit Inputs PNP- / NPN- / AC-logic Input level Programmable Input level Low 0...2 VDC Input level High 3...40 VDC Input resistance 3 kΩ Relay outputs Output circuit Switching voltage max. 250 VAC / 110 VDC Switching current max. 1A Switching capacity max. 150 VA / 30 W Relay responding time 5 ms Electronical outputs Output circuit Optocoupler short-circuit proof Switching voltage max. 40 V Switching current max. 25 mA Supply voltage 4 8 Supply voltage RS485 Sensor- Control supply input 1 3 9 2 15 14 13 12 11 10 A Electronic outputs B Relay outputs 0V 8 13 Subject to modification in technic and design. Errors and omissions excepted. Adaptor plate for screw mount, face 60 x 75 mm +24V 7 B (Stop) Totalizer Sensor supply + Trigger level Z 118.034 T,R- A (Start) 12 Comparator inputs Adaptor plates (page %S) T,R+ 2 T,R+ 15 Accessories 5 + T,R- 14 Interface 0 Without interface 1 RS485 6 1 Control input 1 Outputs 1 Relay outputs 2 Optocoupler outputs Z 118.033 - - terminal Dimensions 100 60.8 48 7 1-6 44.7 48 10 2 www.baumerivo.com 30/10/2008 BE134.