KK-1328-32 This filter series is intended to very high common mode and differential insertion loss for DC power systems. This filter can be used for either commercial applications or for applications involving MIL-STD -461F. If the older 461C spec is required, the circuit can be rearranged to accommodate the C version. If severe shock or vibration are required, please contact our engineering department to discuss any necessary modifications. Operating voltage = 18 - 36 VDC Operating current (max) = 32 amperes Temperature range (storage) = -55 to 85 c Temperature range (operating) 32 A = -40 to 55 c 30 A = " 60 c 28 A = " 64 c 24 A = " 73 c 22 A = " 78 c USA JMK Inc 15 Caldwell Dr. Amherst, NH 03031 EUR JMK Inc Glasgow G13 1DN Scotland UK PH: 603 886-4100 FX: 603 886-4115 email: [email protected] PH: 44-(0) 7785310729 Fax: 44-(0) 141 589 1884