MEANWELL PB300N-12

PB-360
360W Single Output Battery Charger
series
Features :
3 stage charging
AC 115/230VAC selected by switch
Built-in passive PFC function compliance to EN61000-3-2 Class A (option)
Protection: Overload / Short circuit / Reverse polarity / Over voltage
/ Over temperature
Charger for lead-acid batteries
2 color LED loading indicator
Low cost, High reliability
FAN on/off control(Depends on charging current)
2 years warranty
(except for 48V)
PB
300/360 P
(P type only)
12
1.300W without FAN
2.360W with FAN
12:14.4V
24:28.8V
48:57.6V
P:With Passive PFC
N:Without Passive PFC
SPECIFICATION
MODEL
PB-360
-12
PB-360
-48
28.8V
FLOAT CHARGE VOLTAGE
13.6V
27.2V
54.4V
26 ~ 28.8V
52 ~ 58.6V
40 ~ 125Ah
20 ~ 65Ah
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)(Note 5)
INPUT
PB-360
14.4V
VOLTAGE ADJUSTABLE RANGE 13 ~ 14.7V
OUTPUT
-24
BOOST CHARGE VOLTAGE
80 ~ 200Ah
57.6V
BATTERY TYPE
Open & Sealed Lead Acid
OUTPUT CURRENT
24.3A
VOLTAGE RANGE
90 ~ 132VAC / 180 ~ 264VAC selected by switch
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
85%
POWER FACTOR (Typ.)
>0.65 (with P type) at 230VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
7A/115VAC
3.5A/230VAC
COLD START 60A
LEAKAGE CURRENT
<3.5mA / 240VAC
OVERLOAD
90 ~ 110% rated output current
Protection type : Constant current limiting, recovers automatically after fault condition is removed
SHORT CIRCUIT
PROTECTION REVERSE POLARITY
OVER VOLTAGE
OVER TEMPERATURE
FUNCTION REMOTE CONTROL (CN5)
WORKING TEMP.
12.5A
6.25A
248 ~ 370VDC
86%
87%
O/P Built in fuse (FS100) to protect short circuit condition, shut down o/p voltage and can not re-power on
By internal fuse
16 ~ 18V
31 ~ 35V
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Automatically derate charge current until zero
Open: Normal work
59 ~ 64V
Short: Stop Charging
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.05%/ (0 ~ 45
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
IEC60335-2-29 CB approved by TUV(except for 48V), UL60950-1 approved
SAFETY STANDARDS
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
MTBF
DIMENSION
PACKING
NOTE
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
OTHERS
I/P-O/P:3KVAC
ISOLATION RESISTANCE
/ 70% RH
Compliance to EN61000-3-2,-3 (only P type)
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
115.8Khrs min.
MIL-HDBK-217F (25
)
253*135*48.5mm(L*W*H)
1.5Kg; 6pcs/10Kg/0.95CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
File Name:PB-360-SPEC 2008-11-11
PB-360
360W Single Output Battery Charger
Mechanical Specification
Case No.801A
series
Unit:mm
253
235
12
54
127
48.5
11
12
135
230
LED
+V
SVR1 CN5
-V
ON/OFF
SWITCH
INLET
9.25
9 .75
5.5
Air flow
direction
Remote Control(CN5) : JST B2B-XH or equivalent
Assignment
PIN1,2 Open: Normal work
PIN1,2 Short: Stop Charging
Mating Housing
Terminal
JST XHP
or equivalent
JST SXH-001T-P0.6
or equivalent
Block Diagram
fosc : 70KHz
FAN ON/OFF
CONTROL
RECTIFIERS
&
PASSIVE P.F.C.
EMI
FILTER
I/P
POWER
SWITCHING
POLARITY
REVERSE
PROTECTION
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
FG
O.L.P.
DETECTION
CIRCUIT
PWM
CONTROL
O.V.P.
Output Load VS Temperature
Charging Curve
Start
100
V boost
90
V FLT
Charge Voltage
80
100%
Charge Current
Constant Current Constant Voltage
stage 1
LED COLOR
stage 2
Red
stage 3
Green
LOAD (%)
70
60
40
30
-20
10
20
30
40
50
60
70
AMBIENT TEMPERATURE ( )
State
V boost
V FLT
PB-360-12
14.4V
13.6V
PB-360-24
28.8V
27.2V
PB-360-48
57.6V
54.4V
File Name:PB-360-SPEC 2008-11-11