ARTESYN AFE2000

AFE2000 SERIES
Single output
• Approved to EN61000, IEC-1000, UL1950,
CSA 22.2 No. 950-95
• Operating ambient temperature of 0°C to +50°C
• Complies with ETS300 132-1 and EN61000-3-2
• Hot-swap capability
• 11.5 x 6.75 x 4.9 inch size
• N+1 redundancy capability
• Extensive features available
• Compatible with AFS standard shelves for configuring
rack-mounted power systems
The AFE2000 power module is a rack mountable single phase AC to DC power
supply, designed to be a cost-competitive front-end power supply for distributed
power systems. It is particularly suitable for use in data processing, datacom and
telecom applications. The outputs are floating so the end user can ground the plus,
minus or neither depending on the end use application. The AFE2000 power modules
are designed for hot-swap operation and can be mounted into AFS4000/6000 power
shelves for redundant-mode operation.
[ 2 YEAR WARRANTY ]
SPECIFICATION
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
EMC CHARACTERISTICS
OUTPUT SPECIFICATIONS
Output voltage
Main: 48/54.5/56.2VDC
Auxiliary: 12VDC
±1.0%
±1.0%
Conducted emissions
FCC-CFR, part 15, subpart B Class B
CISPR 22
Class B
Output power
Main
Auxiliary
2000W
12W
Radiated emissions
Regulation
Line, load, IT, ageing
±3.0%
Turn-on
Output rise time
100 to 400ms
Turn-on (AC applied)
4s max.
Turn-on (inhibit removed)
1.5s max.
FCC-CFR, part 15, subpart B (Note 7)
CISPR 22
(Note 7)
IEC1000-6
Level 2
IEC1000-3
Level 3
IEC1000-2
Level 3
per EN61000-3-2
Compliant
Ripple and noise
(<50MHz)
Transmission noise
480mV pk-pk
100 to 3kHz
35dBrnC
Overvoltage protection
60VDC max.
Undervoltage protection >44.5VDC
<42VDC for >5s
Short circuit protection
Current sharing
<30s
>30s
Automatic recovery
Latch-off
±10%
Hold-up time
(See Note 1)
Efficiency
Isolation voltage
200/240VAC nom.
Input/output
Input/chassis
Output/chassis
Switching frequency
Approvals and
standards
Input frequency range
50/60Hz nom.
Input surge current
25°C cold start
Safety ground
leakage current
254VAC @ 60Hz
Input current
220VAC, 2000W
47Hz to 63Hz
22A
1.5mA max.
0.5mA typ.
10.5A rms
0.99 min.
MTBF
3000VAC
1500VAC
100VAC
200kHz
EN60950, IEC950, UL1950
CSA C22.2 No. 950
Electrolytic zinc coated CRS,
ASTM A591, light beige paint
Weight
170 to 264VAC
500ms
20ms
86%
1.0V max. distribution line loss
Input voltage range
5.0kg (11Ibs)
MIL-HDBK-217E
Demonstrated
150,000 hours
300,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
Operating ambient
Non-operating
Cooling
0°C to +50°C
-40°C to +100°C
Forced air
Relative humidity
Operating
5% to 95% RH
Altitude
Operating
13,000 feet max.
Vibration
5Hz to 500Hz
Shock
PAGE 1
150 to 170VAC
0 to 150VAC
Case material
INPUT SPECIFICATIONS
Power factor
GENERAL SPECIFICATIONS
Delivers full power
Latch-off
Active current share
(50% to 100% loading)
Remote sense
Immunity - conducted
Immunity - radiated
Immunity - ESD
Line harmonics
0.75G rms peak
15G, 1/2 Sine, 11ms
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
|
2000W AC/DC
2000 Watt
AC/DC PFC front-end for distributed power architectures
OUTPUT
OUTPUT CURRENT
TOTAL
REMOTE
PARALLEL
REGULATION
ENABLE/INHIBIT
INTERFACES
RIPPLE
MODEL NUMBER
VOLTAGE
MIN
MAX
48VDC
0A
41.7A
480mV
±3.0%
Inhibit
All
AFE2000-26S48NA
54.5VDC
0A
36.7A
545mV
±3.0%
Inhibit
All
AFE2000-26S54NA
56.2VDC
0A
35.6A
562mV
±3.0%
Inhibit
All
AFE2000-26S56NA
Parallel interface specifications.
All signals are referenced to ISO_GND unless otherwise indicated.
Isolated signal ground
(ISO_GND)
May be connected to any voltage in the range from +Vout+5VDC to -Vout5VDC.
Overtemperature
(OTW)
Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA
sink capability and maximum voltage stand-off of 60VDC.
Logic 0 : Signal precedes OT shutdown by 5ms.
Logic 1 : Normal operation.
Remote Inhibit
(INHIBIT)
Input bi-level signals. Bi-level input signals shall be no greater than 5VDC.
Logic 0 : Normal operation.
Logic 1 : Output inhibit.
Voltage margin down
(DOWN)
Input bi-level signals. Bi-level input signals shall be no greater than 5VDC.
Logic 0 : Nominal output voltage.
Logic 1 : 44.5 to 45.5VDC output.
Power good signal
(PWR_GOOD)
Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA
sink capability and maximum voltage stand-off of 60VDC.
Logic 0 : Output undervoltage.
Logic 1 : Output voltage normal.
Fault fail signal
(F/F ±)
Differential relay contact, isolated from all outputs and returns within the
power module.
Relay closed : Power supply failure
Relay open : Normal operation.
Power fail warning signal
(PFW)
Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA
sink capability and maximum voltage stand-off of 60VDC.
Logic 0 : Signal precedes loss of output power by 5ms.
Logic 1 : Normal operation.
Module Missing Pin
(MM)
Provision for detection of unseated or removed module. MM pins are
common internal to the power supply. Internal pull-up resistor to +5VDC logic
bias, referenced to RS-.
Auxiliary Output
(AUX ±)
12VDC auxiliary output. Isolated from both the main output and the isolated
signal ground. May be utilized for external housekeeping supply and
connected to either main output or isolated signal ground.
Reset
(RESET)
Input bi-level signal. Bi-level input signal shall be no greater than 5VDC.
Logic 0 : Resets fault indicators without unit shut-down.
Logic 1 : Normal operation.
AC Good
(AC OK)
Output bi-level signal. Bi-level output signal is open-collector (drain) with a
5mA sink capability and maximum voltage stand-off of 60VDC.
Logic 0 : AC input below normal operating range.
Logic 1 : AC input within steady-state operating range (170 to 264VAC).
Voltage monitoring
(VMARG)
Input analog signal referenced to RS-. Adjusts output up to 4VDC higher than
the nominal set point.
Features
Live insertion and removal
OR-ing diodes provided on output.
Voltage monitoring jacks
Located on front panel.
LED’s (located on front panel)
Power Good
Power Fail
AC Good
-
Green
Red
Green
Protection
Thermal protection - automatic shut-off for fan failure or internal
overtemperature.
Output Overload and Short Circuit - automatic shut-down after 30 seconds.
Current regulated output down to less than 1VDC.
Output Overvoltage - automatic shut-down for both main (60VDC max.) and
auxiliary (15.6VDC max.) outputs.
Output Undervoltage - automatic shut-down below 42VDC.
Current Share
Active current sharing for up to 9 AFE2000 power modules.
Short Pin
Short pin located in the output connector initiates shut-down of the power
supply output when the power supply is removed from the host power shelf.
Current Monitor
(IMON)
Current source which mirrors magnitude of the output current. Signal return
is referenced to RS-.
Current Limit
(CL)
Output bi-level signal. Bi-level output signal is open-collector (drain) with a
5mA sink capability and maximum voltage stand-off of 60VDC.
Logic 0 : Output is in current mode control and is current limiting.
Logic 1 : Normal operation.
Remote Enable
(ENABLE)
Input bi-level signal. Bi-level input signal shall be no greater than 5VDC.
Logic 0 : Output inhibited.
Logic 1 : Normal operation.
International Safety Standard Approvals
EN60950/IEC950 File No. E9972397
UL1950 File No. E135734
Please consult our website for the following items: ✔ Application Note
http://www.artesyn.com
PAGE 2
2000W AC/DC
|
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
2000 Watt
AC/DC PFC front-end for distributed power architectures
PIN CONNECTIONS
PIN NO.
FUNCTION
PIN NO.
FUNCTION
PIN NO.
FUNCTION
PIN NO.
FUNCTION
A1
Short Pin
B1
DOWN
C1
RS+
D1
+Vout
A2
AUX+
B2
VMARG
C2
RS-
D2
+Vout
A3
AUX-
B3
MM
C3
MM
D3
PWR RTN
A4
RS-
B4
I SHR
C4
F/F-
D4
PWR RTN
A5
Not Used
B5
RESET
C5
F/F+
D5
CGND
A6
Not Used
B6
IMON
C6
INHIBIT/ENABLE
A7
AC OK
B7
Power Good
C7
CL
B8
(3)
C8
OTW
A8
PFW
ISO GND
(2)
Notes
1
2
3
4
5
6
PFW signal warning issued 5 msec prior to shutdown.
Chassis or safety ground.
Isolated signal ground.
Output ground - referenced to RS-.
Refer to Application Note 106 for installation of the AFE2000 power
modules into the AFS4000 power shelf.
Refer to Application Note 110 for description of outputs and signals
available with AFE2000 power modules installed in Artesyn standard frontend power shelf.
7
8
Class A for power module, Class B when installed in AFS4000 shelf
(subject to cable/system configuration).
NOTICE: Some models do not support all options. Please contact your
local Artesyn representative or use the on-line model number search tool at
http://www.artesyn.com/powergroup/products.htm to find a suitable
alternative.
SHORT SIGNAL PIN
A1
B1
C1
A8
B8
C8
D5
D4
D3
D2
D1
6.44
(163.58)
AIR FLOW
NORMAL
0.074
(1.879)
11.46
(291.08)
AC INPUT
POWER DYNAMICS 42R08-1122
MATE - POWER DYNAMICS 43R06-2114
0.25
(6.35)
1.30
(33.02)
6.75
(171.45)
5.725
(145.415)
0.800
(20.32)
4.23
(107.44)
4.83
(122.68)
0.050
(1.270) TAPERED GUIDE
PIN HOLE
0.0875
(2.2225)
2.063
(52.400)
AC GOOD
PWR FAIL
PWR GOOD
V OUT
0.625
(15.875)
REF
0.475
(12.065)
TAPERED GUIDE
PIN HOLE
0.462
(11.735)
0.375
(9.525)
INSERTION/EJECTOR
HANDLE WITH 6-32
CAPTIVE SCREW
MAIN DC OUTPUT/SIGNALS
ELCON 279-0468-00100
MATE - ELCON 278-0468-00200
(J2) DC connector
(J2) DC mating connector
Elcon 279-0468-00100 or equivalent.
Elcon 278-0468-00200 or equivalent.
(J1) AC connector
(J1) AC mating connector
Power Dynamics 42R08-1122 or equivalent.
Power Dynamics 43R06-2114 or equivalent.
PAGE 3
ds_afe2000_20050824.PDF
Datasheet © Artesyn Technologies® 2005
The information and specifications contained in this datasheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising