ARTESYN DPF600

DPF600 SERIES
Dual output
•
•
•
•
•
•
•
The DPF600 is a 600W universal input AC/DC front end power supply in a fully
enclosed hot pluggable case with built-in fan, front panel with handle, IEC input
connector, on/off switch and DIN output signal connector. Providing dual 49V and 5V
outputs with a full set of status signals, the DPF600 is designed as a slot-in front end
for distributed power systems. The DPF600 provides 600W of output power and is
fully compliant with EN61000-3-2. Standard features include current sharing and full
protection against overvoltage, overload and short circuit. Remote or local system
monitoring is possible via a full set of status signals that include fan fail, DC good,
remote inhibit and current monitoring. The DPF600, with full international safety
approval and the CE mark, meets conducted emissions EN55022 level B. The
DPF600 is designed for use as a front end in medium power communication
applications adopting distributed power architecture. The DPF600 can be used in
conjunction with our complete range of 3 to 200W DC/DC converters to fully configure
a distributed power system.
Patent No. 5446366
[ 2 YEAR WARRANTY ]
SPECIFICATION
600W front end
EN61000-3-2 compliant
Hot pluggable
N+1 redundancy
Full set of status signals
EN55022, EN55011 conducted emissions level B
UL, TÜV, CSA and BABT approvals
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
EMC CHARACTERISTICS
OUTPUT SPECIFICATIONS
Voltage set point
-49VDC ±245mVDC
with 2A load applied
Total regulation
Main output
Full load to no load
±5.0%
Rise time
At turn-on
Transient response
Main output
50% to 100%
step at 1.0A/µs
5.0% max. dev.,
1ms recovery
to 1.0%
Ripple and noise
(0Hz to 30MHz)
Main output
Auxiliary output
750mV pk-pk,
100mV pk-pk
Overvoltage protection
Latching main output
Latching
0.5s, max.
-55V to -60V
5.7V to 6.5V
Output power limit
Short circuit protection
750W
Non-latching
Auto-recovery
Current sharing
±10%, 3V droop from
15% to 100%
Radiated emissions
Conducted emissions
Harmonic current emm.
Electrical fast
transients/bursts
Surge susceptibility
EN55022/11, FCC part 15
EN55022/11, FCC part 15
EN61000-3-2
EN61000-4-4
EN61000-4-5
Level 3
GENERAL SPECIFICATIONS
Hold-up time
120VAC, 60Hz FL
Efficiency
100Vin, load >66% rated
82% min.
Isolation voltage
Input/output
Input/chassis
3000VAC
1500VAC
Switching frequency
Approvals and
standards
EN60950, UL1950, BABT
CSA C22.2 No. 950
Weight
6.9kg (15Ibs)
MTBF
500,000 hours
demonstrated
Input voltage range
85 to 264VAC
ENVIRONMENTAL SPECIFICATIONS
Input frequency range
47Hz to 63Hz
Thermal performance
230VAC, cold start @ 25°C
Input surge
300VAC
Safety ground
leakage current
120VAC, 60Hz
230VAC, 50Hz
0.2mA
0.4mA
Input current
90VAC, 600W
220VAC
7.35A rms max.
2.84A rms max.
Input fuse
Non-replaceable
Power factor
35A max.
20ms
15A
0.99 120Vin, >66% load
Operating ambient
0°C to +50°C
Non-operating
-40°C to +85°C
50°C to 70°C ambient Derate to 50%
Cooling
Built-in fan
Relative humidity
Non-condensing
Altitude
Operating
Non-operating
Vibration
5Hz to 500Hz
International Safety Standard Approvals
TÜV
VDE0805/EN60950/IEC950
UL1950 File No. E136005
CSA C22.2 No. 950 File No. LR41062C
PAGE 1
Certificate No. 606090
20ms @ 600W
50kHz
INPUT SPECIFICATIONS
Input surge current
Level A
Level B
Compliant
Level 3
5% to 85% RH
10,000 feet max.
40,000 feet max.
2.4G rms peak
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
|
600W AC/DC
600 Watt
AC/DC PFC front-end for distributed power architectures
OUTPUT CURRENT
OUTPUT
-49V
TOTAL
RIPPLE
VOLTAGE
MIN
(3)
MAX
(4)
12A
750mV
±5.0%
0.2A
10A
50mV
±5.0%
0A
MODEL NUMBER
REGULATION
DPF600-9617
+5V
Notes
1
2
3
4
STATUS AND CONTROL SIGNALS
Fan fail and power good are open collector signals.
All signals are referenced to earth ground, as is the 5V output.
The main output is floating.
49.5V at minimum current.
Fan fail H
(1,2)
Asserted in event of a failure
Power good L
Asserted when the output voltage
is within specification
Inhibit L
Inhibits the main output when
this pin is open or low
Current monitor
Provides an analog voltage
reflection of the main output current
1.25
(31.75)
11.94
(303.28)
AIR FLOW
6.73
(170.94)
1.619
(REF.)
(41.12)
2.18 ± .02
(55.37 ± 0.51)
2.18 (REF.)
(55.37)
2.105 ± .015
(53.467 ± 0.381)
1.47 ± .02
(37.34 ± 0.51)
1.47 (REF.)
(37.34)
.22 (2PL)
(5.59)
.985 REF
(25.019)
PIN NUMBER
Pin C6
Pin C8
Pin C4
Pin B6
Pins B1, C1
Pins A1-2
.806 ± .01
(20.47 ± 0.25)
3.340
(84.84)
1.015 ± .01
(25.78 ± 0.25)
OUTPUT PIN CONNECTIONS
FUNCTION
PIN NUMBER
Power Good H
Pins A10-12
Inhibit L
Pins B9-12
Current Monitor
Pins C9-12
Fan Fail H
Pins A-C, 13-16
-48V Fan
Pin A9
-48V Fan Return
Pin B8
ALL DIMENSIONS IN INCHES (mm)
Mating connectors
FUNCTION
5V Output
5V Output
5V Output
Ground
+5V Sense
Ground Sense
Signal
48-pin female DIN connector
Main output
ICON connectors (ELCON P/N: 259-28-00100)
Input
IEC
http://www.artesyn.com
PAGE 2
DS_DPF600_19980401.PDF
Data Sheet © Artesyn Technologies® 2000
The information and specifications contained in this data sheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.