ARTESYN DFP1000

DPF1000 SERIES
Dual output
•
•
•
•
•
•
•
•
[ 2 YEAR WARRANTY ]
SPECIFICATION
1000W front end
EN61000-3-2 compliant
11 x 6.0 x 5.0 inch size
Hot pluggable
N+1 redundancy
Full set of status signals
EN55022, EN55011 conducted emissions level A
UL, VDE and CSA safety approvals
The DPF1000 is a 1000W universal input AC/DC front end power supply in a fully
enclosed hot pluggable case with built-in fan, handle, IEC input connector, on/off
switch and DIN output signal connector. Providing dual 48V and 5V outputs with a full
set of status signals. The DPF1000 is designed for use as a front end in medium
power communication applications adopting distributed power architecture. The
DPF1000 is fully compliant with EN61000-3-2. Standard features include current
sharing and full protection against overvoltage, overload and short circuit. Remote or
local system monitoring is possible via a full set of status signals that include fan fail,
DC good, power fail, remote inhibit and current monitoring. The DPF1000, with full
international safety approval and the CE mark, meets conducted emissions EN55022
level A. The DPF1000 can be used in conjunction with our complete range of 3 to
200W DC/DC converters to fully configure a distributed power system.
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
EMC CHARACTERISTICS
OUTPUT SPECIFICATIONS
Voltage set point
-48V ±0.1V @ 10A
Total regulation
(Full load to no load)
Main output
±5.0%
Auxiliary output, 5V, 0.5A max. ±5.0%
Rise time
At turn-on
Transient response
Main output
75% to 100%
step at 0.1A/µs
Ripple and noise
(20MHz)
Main output
Overvoltage protection
latching
1.0s, max.
5.0% max. dev.,
1ms recovery
1.0V pk-pk,
-57V to -60V min.
Output power limit
Yes
±10% sharing
0.1V/A droop
1/3L to FL
INPUT SPECIFICATIONS
Input voltage range
1000W
1200W
Input frequency range
47Hz to 63Hz
Input surge current
25°C cold start
36A typ.
Input surge
300VAC
Safety ground
leakage current
254.4VAC, 50Hz
Input current
90VAC, 1000W
Input fuse
Replaceable
20A
Power factor
110VAC
220VAC
0.99
0.98
PAGE 1
110VAC, 60Hz
Efficiency
110VAC @ 1kW
77% min.
Isolation voltage
Input/output
Input/chassis
3000VAC
1500VAC
Switching frequency
MTBF
20ms @ 1000W
200kHz
Approvals and
standards
VDE0805, EN60950, IEC950
UL1950, BABT
CSA C22.2 No. 950
4.3kg (9.5Ibs)
MIL-HDBK-217F
@ 25°C full load
80,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
2.5mA
Operating ambient, FL
0°C to +50°C
Non-operating
-40°C to +70°C
50°C to 70°C
Derate linearly
ambient
to 50% at +70°C
Cooling
3 orthogonal axes, random vibration, 10 minute test per axis.
Level 3
Hold-up time
20ms
14A rms max.
Level A
Level A
Level A
Compliant
Level 3
GENERAL SPECIFICATIONS
Weight
90 to 264VAC
108 to 264VAC
Notes
1
EN55022/11, FCC part 15
EN55022/11
FCC part 15
Harmonic current emm. EN61000-3-2
Electrical fast
EN61000-4-4
transients/bursts
Surge susceptibility
EN61000-4-5
1200W
Short circuit protection
Current sharing
Radiated noise
Conducted noise
Built-in fan
Relative humidity
Operating
Altitude
Operating
Non-operating
Vibration (See Note 1)
5Hz to 500Hz
Shock
MIL-STD-810E
5% to 85% RH
10,000 feet max.
30,000 feet max.
2.4G rms peak
516.4 Part IV
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
|
1000W AC/DC
1000 Watt
AC/DC PFC front-end for distributed power architectures
OUTPUT CURRENT
OUTPUT
TOTAL
RIPPLE
VOLTAGE
MIN
MAX
-48V
0A
21A
1000mV
±5.0%
+5V
0A
0.5A
100mV
±5.0%
MODEL NUMBER
REGULATION
DPF1000-9617PE
Control and supervisory functions
Protection features
Bias Supply H
(Pin 1)
Isolated 5V bias supply, maximum current 0.5A. Allows the system designer
to power system control circuitry.
Overvoltage protection
The unit will shutdown and latch off if the output voltage exceeds the OVP
threshold. Input power recycling is necessary to restart the unit.
PFC Fail L
(Pin 2)
A failure in the Power Factor Correction stage, i.e. loss of the 400V internal
bus, is indicated by this open collector signal, asserted low.
Overcurrent and short circuit protection
The unit is protected against an overload on its output in the range 25 to 30A,
with automatic recovery on overload removal. Under short circuit conditions,
the unit shuts down.
Bias Return L
(Pin 3)
Return path for the 5V bias supply. All signals are referenced to this return.
Remote Inhibit H
(Pin 4)
The output is inhibited when this signal is tied high. IIL max. = 10mA.
Voltage Trim
(Pin 5)
The output voltage can be adjusted up to -56V by connecting a 100k variable
resistor between pin 5 and pin 14.
Over temperature protection
If the internal temperature of the unit exceeds a safe limit, the unit shuts down
and will need power recycling to re-start.
Input voltage sags
A user supplied jumper inhibits operation of the unit in the 110V range. This
limits the input current to a safe level when operating at 230V to prevent
circuit breakers tripping under brown out. This programmable jumper can be
accessible by removing the cover plate. Refer to view A on page 102.
Current Monitor
(Pins 13, 14)
Value: 0.1 x Iout. Tolerance: 10%. Range: 5 to 25A
Power Good L
(Pin 15)
An open collector signal, asserted low. Threshold asserted: 44.5 to 46V,
deasserted: 56.5 to 58V. See Figure 1.
Figure 1:
AC Input
Fan Fail Detect L
(Pin 16)
An open collector signal, asserted low, indicates fan failure. See Figure 1.
Power Fail Detect H (Pin 17)
An open collector signal, asserted high, indicating AC line failure. The output
voltage will stay within regulation 4ms after PFD is asserted.
48V Output
PFD Signal
PIN CONNECTIONS
Power Good Signal
t1
PIN NUMBER
SIGNAL
1
5V Bias
2
PFC Fail
3
5V Bias Return/Signal Return
4
Remote Inhibit H
5
Voltage Trim
6 to 12
-48V Return
13
Current Monitor +
14
Current Monitor -
15
Power Good L
16
Fan Fail Detect L
17
Power Fail Detect H
18 to 24
-48V
t2
t1 varies with line and load
t2 > = 4ms t1 + t2 > =20ms
Load sharing
The DPF1000-9617PE power supply provides load sharing capability for
implementing parallel operation. An internal OR-ing diode is used in each
output to provide N+1 redundancy. The power supplies will share the load
current within ±10% from full load down to1/3 of the rated current of each
power supply.
Method of current sharing of -48V output shall be via the "droop method", as
illustrated in Figure 2 below:
Figure 2: Droop and Regulation Characteristics
50.4V
(+5%)
+0.10V (48.1V)
48V
International Safety Standard Approvals
Output
Voltage
Setting Tolerance
-0.10V (47.9V)
Total Output
Tolerance
Band
46.9V
46.5V
VDE0805/EN60950/IEC950 File No. 10401-3336-1090
45.6V
(-5%)
UL1950 File No. E136005
CSA C22.2 No. 950 File No. LR50913/LR101320
10A
21A
25A
(1000W) (1200W)
Output Current
Certificate No. PS/606473
http://www.artesyn.com
PAGE 2
1000W AC/DC
|
DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES
1000 Watt
AC/DC PFC front-end for distributed power architectures
3.00
(76.20)
SEE DETAIL 'B'
VIEW A
.98
(24.90)
VIEW B
J1
N
0.25
(6.40)
L
J1
24
12
23
11
22
10
21
9
20
8
19
7
18
6
17
5
16
4
15
3
14
2
13
1
N
6.00
(152.40)
6.52
(165.60)
L
G
DETAIL 'B'
1.606 (40.79)
2.149
(54.58)
SEE DETAIL 'A'
5.00
(127.00)
11.00
(279.40)
VIEW A
VIEW B
24
12
23
11
22
10
21
9
20
8
19
7
18
6
17
5
16
4
15
3
14
2
13
1
J2
DETAIL 'A'
ALL DIMENSIONS IN INCHES (mm)
(J2) DC connector
(J2) DC mating connector
Molex BMI receptacle 42474 part number 15-06-0240 or equivalent with Molex
5556 female crimp terminal part number 39-00-0182 or equivalent.
Molex BMI plug 42475 part number 15-06-0246 or equivalent with Molex 5558
male crimp terminal part number 39-00-0220 or equivalent.
(J1) AC connector
(J1) AC mating connector
Standard IEC connector.
Standard IEC plug.
PAGE 3
http://www.artesyn.com
PAGE 4
DS_DPF1000_19980401.PDF
Data Sheet © Artesyn Technologies® 2000
The information and specifications contained in this data sheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.