LEM AK200C5

AC Current transducer AK-C-
IPN = 10 .. 200 A
Transducer for the electronic measurement of AC sinusoidal waveforms,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit). Jumper selectable ranges and
self powered transducers.
Electrical data
Primary Nominal Current
Analogue Output Signal1)
IPN (A.t.RMS)
10,20,50
VOUT (V DC)
5
Type
RoHS
Date code
AK 50 C5
planned
• AC sinusoïdal measurement
10,20,50
10
AK 50 C10
MAY 2006
100,150,200
5
AK 200 C5
planned
100,150,200
10
AK 200 C10 JUNE 2006
Vc
Supply voltage
RL
Load resistance
1
Vb
Rated voltage (CAT III, PD2)
150
Vd
RMS Isolation voltage test, 50 Hz, 1mn
3
f
Frequency bandwith
50-60
Features
• Average responding
• Self powered transducers
• Panel mounting
• Voltage output
• Jumper selectable ranges
Self Powered
MΩ
V AC
kV AC
Hz
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA=25°C
±1
tr
Response time @ 90% of IPN
< 100
%
mS
Applications
• Automation systems
General data
TA
Ambient operating temperature (0-95% RH)
- 20 ..+ 50
°C
TS
Ambient storage temperature
- 20 ..+ 85
°C
m
Mass
Safety
EMC
120
IEC 61010-1
EN 61326
Note :
1)
g
Analog current reading for remote
monitoring (e.g. motor).
• Data loggers
Self-powered transducer does not
drain data logger batteries.
• Panel meters
Simple connection displays power
consumption.
Options on request
For 0-5 V output model, no saturation output up to 8.2 V
and for 0-10 V output model, no saturation output up to 15 V.
• DIN mounting
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
060816/6
Page 1/2
www .lem.com
Dimensions
AK-C-
(unit : mm, 1mm = 0.0394 inch)
61.0
49
24.5
55.4
19
3.2
23.5
23.7
88.9
15
4.5
39
78
Mechanical characteristics
Remark
• General tolerance
± 1 mm
• Primary aperture
19 mm
• Panel mounting
2 holes ∅ 4.5mm
Distance between holes
• Temperature of the primary conductor should not
exceed 60°C.
78 mm
Connections
• 2 x UNC8 Cylindric Head
060816/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/2
www .lem.com