LEM AKR200C420L

IPN = 2..200A
AC Current transducer AKR-C420L
Transducer for the electronic measurement AC waveforms current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit). Jumper selectable ranges and
True RMS 4-20mA current output.
Electrical data
Primary Nominal CurrentAnalogue Output Signal1)
IPN (A.t.RMS)
Type
IOUT (mA)
Features
RoHS
Date Code
2,5
4-20
AKR 5 C420L
10,20,50
4-20
AKR 50 C420L
100,150,200
4-20
AKR 200 C420L
Vc
Supply voltage (Loop powered)
24
RL
Vb
Vd
Load resistance
see power supply diagram
Rated voltage (CAT III, PD2)
150
RMS Isolation voltage test, 50 Hz, 1mn
3
f
Frequency bandwith
JULY 2006
planned
JULY 2006
V DC
VAC
kV AC
20-100
Hz
• VFD and SCR waveforms current
measurement
• True RMS responding
• 4-20 mA Current output
• Loop powered transducers
• Panel mounting
• Accurate
• Jumper selectable ranges
Advantages
• Large aperture
Accuracy - Dynamic performance data
• High isolation between primary and
secondary circuits
X
Accuracy @ IPN, TA=25°C
±1
%
tr
Response time @ 90% of IPN
< 600
mS
• Easy to mount
Applications
TA
Ambient operating temperature (0-95% RH)
-20 ..+ 50
°C
TS
Ambient storage temperature
-20 ..+ 85
°C
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
m
Mass
Safety
EMC
90
IEC 61010-1
EN 61326
g
Acurate measurement of phase
General data
angle fired or burst fired (time
proportioned) SCRs.
• Switching Power Supplies and
Note:
1)
For 4-20mA output model, no saturation output up to 23 mA.
Electronic Ballasts:
True RMS sensing is the most
Selecting the transducer
accurate way to measure power
VFD (Variable Frequency Drive) and SCR (Semi Conductor Rectifier) output
supply or ballast input power.
waveforms are rough approximations of a sine wave. There are numerous spikes
and dips in each cycle. AKR transducers use a mathematical algorithm called
Options on request
“True RMS,” which integrates the actual waveform over time. True RMS is the only
way to accurately measure distorted AC waveforms. Select AKR transducers for
• DIN mounting
nonlinear loads or in “noisy” power environments.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
060816/6
Page 1/2
www .lem.com
Dimensions
AKR-C420L
(unit : mm, 1mm = 0.0394 inch)
61.0
49
24.5
55.4
19
3.2
23.5
23.7
88.9
15
4.5
39
78
Mechanical characteristics
• General tolerance
± 1 mm
• Primary aperture
19 mm
• Panel mounting
2 holes ∅ 4.5mm
Distance between holes
Power Supply diagram
78 mm
Connections
• 2 x UNC8 Cylindric Head
Remark
• Temperature of the primary conductor should not
exceed 60°C.
060816/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/2