LEM AKR5B420L

IPN = 2..200A
AC Current transducer AKR-B420L
A Split Core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Jumper selectable ranges
and True RMS 4-20mA current output.
Electrical data
Primary Nominal Current
Features
Analogue Output Signal1)
IPN (A.t.RMS)
Type
• VFD and SCR waveforms current
RoHS
IOUT (mA)
measurement
Date Code
• True RMS responding
2,5
4-20
AKR 5 B420L
10,20,50
4-20
AKR 50 B420L planned
JUNE 2006
100,150,200
4-20
AKR 200 B420L planned
• Split core box
• Current output
• Loop powered transducers
• Panel mounting
Vc
Supply voltage (Loop powered)
24
RL
Vb
Vd
Load resistance
see power supply diagram
Rated voltage (CAT III, PD2)
150
RMS Isolation voltage test, 50 Hz, 1mn
3
f
Frequency bandwith
V DC
• Jumper selectable ranges
V AC
kV AC
Advantages
10-400
Hz
• Large aperture
• High isolation between primary and
Accuracy - Dynamic performance data
secondary circuits
X
Accuracy @ IPN, TA=25°C
±1
tr
Response time @ 90% of IPN
< 600
• Easy to mount
%
mS
General data
Applications
• VFD Controlled Loads: VFD output
indicates how the motor and
TA
Ambient operating temperature (0-95% RH)
- 20 ..+ 50
°C
TS
Ambient storage temperature
- 20 ..+ 85
°C
m
Mass
Safety
EMC
120
IEC 61010-1
EN 61326
g
attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs.
• Switching Power Supplies and
Electronic Ballasts: True RMS sensing
Note:
1)
For 4-20mA output model, no saturation output up to 23 mA.
Selecting the transducer
is the most accurate way to
measure power supply or ballast
input power.
VFD (Variable Frequency Drive) and SCR (Semi Conductor Rectifier) output
waveforms are rough approximations of a sine wave. There are numerous spikes
and dips in each cycle. AKR transducers use a mathematical algorithm called
“True RMS,” which integrates the actual waveform over time. True RMS is the only
Options on request
• DIN mounting
way to accurately measure distorted AC waveforms. Select AKR transducers for
nonlinear loads or in “noisy” power environments.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
060816/5
Page 1/2
www .lem.com
Dimensions
AKR-B420L
(unit : mm, 1mm = 0.0394 inch)
3.2
57.2
13
21.7
61
13
30
21.7
89.7
61
4.5
77.3
Mechanical characteristics
• General tolerance
± 1 mm
• Primary aperture
21.7 mm sq.
• Panel mounting
2 holes ∅ 4.5mm
Distance between holes
Power Supply diagram
77.3 mm
Connections
• 2 x UNC8 Cylindric Head
Remark
• Temperature of the primary conductor should not
exceed 60°C.
060816/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/2
www .lem.com