IPN = 100..1000 A AC/DC Current transducer DHR-C10 The transducer for the electronic measurement of DC & distorted AC waveform currents, with galvanic isolation between the primary circuit (power) and the secondary circuit (measurement). True RMS 0-10V voltage output. Features Electrical data Primary Nominal DC & AC Current I PN (A.t.RMS) Primary AC Current Max. Peak Value I P (A) (*) Output voltage (Analog) V OUT (VDC) 600 600 1000 1000 1800 1800 1800 0-10 0-10 0-10 0-10 0-10 0-10 0-10 100 200 300 400 500 600 1000 RL VC IC VSL ÎP Load resistance Supply voltage Current Consumption Output voltage limitation (0-10V) Overload capability (Ampere Turns) • VFD and SCR waveforms current Type DHR 100 C10 DHR 200 C10 DHR 300 C10 DHR 400 C10 DHR 500 C10 DHR 600 C10 DHR 1000 C10 ≥ 10 kΩ + 20 .. 50 V DC 30 mA < 14 V 30000 A.t ε Accuracy @ IPN, TA = 25°C (excluding offset) Linearity error (1% of IPN .. ± IPN) Electrical offset voltage, TA = 25°C Temperature coefficient of VOE ( 0..+60 °C) (-40..+70 °C) Temperature coefficient of VOUT (% of reading) Response time tp 90% of IPN step Frequency bandwidth (±1dB) L VOE TCVOE TCVOUT tr BW < ± 1 % of IPN < ± 1.0 % of IPN < ± 1.0 % of IPN ± 2.0 mV/K ± 4.0 mV/K ± 0.1 %/K < 150 ms DC 20..6000Hz Ambient operating temperature Ambient storage temperature Mass Protection degree • Insulated plastic case recognized according to UL94-V0 Advantages • Large aperture for cable up to Ø32mm • High isolation between primary and Applications • VFD Controlled Loads VFD output indicates how the motor and attached load are operating. • SCR Controlled Loads Acurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current General data TA TS m IPxx • Panel mounting • Eliminates insertion loss secondary circuits • Easy installation Performance data X measurement • True RMS output - 40 .. + 70 - 40 .. + 85 260 IP20 °C °C g measurement gives faster response than temperature measurement. • Switching Power Supplies and Electronic Ballasts True RMS sensing is the most Note : ( ) * The Max. Peak AC Current is the highest peak level of the primary signal that is taken into account for accurate True RMS calculation. Yet the device is designed for maximum continuous True RMS value equal to I PN, whereas the output is limited by the above specified output limitation. accurate way to measure power supply or ballast input power. Application domain • Energy and Automation Page 1/3 061128/14 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Current Transducer DHR-C10 Isolation characteristics Vb Rated isolation voltage rms 300 V with IEC 61010-1 acc. to the 61326 standards and following conditions : - Reinforced isolation - Over voltage category CAT III - Pollution degree PD2 - Heterogeneous field Rms voltage for AC isolation test 1), 50 Hz, 1min 4.6 kV Creepage distance 8.89 mm Clearance distance 8.89 mm Comparative tracking index (Group I) > 600 Vd dCp dCl CTI Note : 1) Between primary (completely filling the aperture) and secondary. Output polarity with DC input Output in V 10 -Ipn 0 +Ipn Safety This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the manufacturer’s operating instructions. Installation and maintenance should be done with main power supply disconnected. The operator must have an accreditation to install this material. Caution! Risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (e.g. primary conductor, power supply). Ignoring this warning can lead to injury and/or cause serious damage. The user must take care of all protection guarantee against electrical shock. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Page 2/3 061128/14 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Dimensions DHR-C10 (in mm. 1 mm = 0.0394 inch) 25 70 32 4. 60 70 60 40 10 6.8 0 15 25 2 2.2 8 8.30 6 .80 2 .50 90 4 25.60 4 .60 7 8.30 33 .80 15 6 78 Connections Mechanical characteristics • Wires up to 2 mm ∅ • General tolerance ±1 mm • Female connector provided (screw terminals) • Primary aperture • Panel mounting ∅ 32.0 mm 4 holes ∅ 4.6 mm • Distance between holes 70.0 mm & 78 mm (see above dimensions) DHR-C5/10 DHR For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness. Output Connector 1(Vcc) 2(NC) 3(Vout) 4(GND) 24 VDC Power Remarks (+) (-) 10k (-) (+) Load (Controller, meter etc) +24VDC • VOUT is positive when IP flows in the direction of the arrow. • The return busbar and primary conductor elbow must be located at least at 2.5 x window length more far away from the transducer case. • The temperature of the primary busbar can not exceed 90 °C. • Dynamic performances are the best with a primary busbar completely filling the primary aperture. • This is a standard model. For different versions (supply voltages, different outputs, bidirectional measurements...), please contact us. Is OUT Ip GND Page 3/3 061128/14 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com