MEANWELL RSP-750

RSP-750
750W Single Output Power Supply
E¡¡E¡½
¡E¡E
¡EE¡
E¡
E¡
¡E¡E
¡E¡E
¡E¡E
E¡
series
Features :
Universal AC input / Full range
AC input active surge current limiting
High efficiency up to 92%
Built-in 12V/0.1A auxiliary power
Built-in active PFC function, PF>0.97
Protections: Short circuit / Overload / Over voltage / Over temperature / Fan
alarm
Output voltage can be trimmed between 40 ~ 110% by 2 ~ 5.5VDC external
control signal
Output current can be trimmed between 40 ~ 110% by 2 ~ 5.5VDC external
control signal
Forced air cooling by built-in DC with fan speed control function
3
High power density 9.44w/inch
1U low profile 41mm
DC OK Signal
Built-in remote ON-OFF control
Built-in remote sense function
3 years warranty
SPECIFICATION
MODEL
RSP-750-5
RSP-750-12
RSP-750-15
RSP-750-24
RSP-750-27
RSP-750-48
DC VOLTAGE
5V
12V
15V
24V
27V
48V
RATED CURRENT
100A
62.5A
50A
31.3A
27.8A
15.7A
CURRENT RANGE
0 ~ 100A
0 ~ 62.5A
0 ~ 50A
0 ~ 31.3A
0 ~ 27.8A
0 ~ 15.7A
RATED POWER
500W
750W
750W
751.2W
750.6W
753.6W
150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
10 ~ 13.5V
Ó¡ 1.0%
¡Ó0.5%
Ó¡ 0.5%
13.5 ~ 16.5V
Ó¡ 1.0%
¡Ó0.5%
Ó¡ 0.5%
20 ~ 26.4V
Ó¡ 1.0%
¡Ó0.5%
Ó¡ 0.5%
24 ~ 30V
Ó¡ 1.0%
¡Ó0.5%
Ó¡ 0.5%
90.5%
90.5%
92%
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
4.75 ~ 5.5V
VOLTAGE ADJ. RANGE
LOAD REGULATION
Ó¡ 2.0%
¡Ó0.5%
Ó¡ 2.0%
SETUP, RISE TIME
1000ms, 50ms at full load
VOLTAGE TOLERANCE Note.3
LINE REGULATION
16ms/230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
Note.5 90 ~ 264VAC
Ó¡ 1.0%
¡Ó0.5%
Ó¡ 0.5%
43 ~ 55V
16ms/115VAC at full load
127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.97/230VAC
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
82%
5V : 5.6A/115VAC
2.8A/230VAC
25A/115VAC
40A/230VAC
LEAKAGE CURRENT
<2.0mA / 240VAC
0.98/115VAC at full load
87%
89%
12V~48V : 8.2A/115VAC
3.9A/230VAC
105 ~ 125% rated output power
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
AUXILIARY POWER(AUX)
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V
13.8 ~ 16.8V
17 ~ 20.5V
27.6 ~ 32.4V
31 ~ 36.5V
56.6 ~ 66.2V
Protection type : Shut down o/p voltage, re-power on to recover
85
5 (TSW2 ) detect on heatsink of O/P diode; 80
5 (TSW1 ) detect on heatsink of power transistor
¢J¡Ó ¢J
¢J¡Ó ¢J
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
12V @ 0.1A ; tolerance : 10%
¡Ó
REMOTE ON/OFF CONTROL Note.6 Power on : short between on/off(pin13) & 12V-AUX(pin14) on CN50 Power off : open between on/off(pin13) & 12-AUX(pin14) on CN50
FUNCTION DC OK SIGNAL
The TTL signal out, PSU turn on = 0 ~ 1V ; PSU turn off = 3.3 ~ 5.6V
OUTPUT VOLTAGE TRIM Note.6 Adjustment of output voltage is possible between 40 ~ 110% by 2 ~ 5.5VDC external control signal
OUTPUT CURRENT TRIM
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
Adjustment of output current is between 40 ~ 110% by 2 ~ 5.5VDC external control signal
-30 ~ +70
¢J (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
¢J
¡Ó0.03%/¢J (0 ~ 50¢J)
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
¢J
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22), EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
¢J)
120.8K hrs min. MIL-HDBK-217F (25
250*127*41mm (L*W*H)
1.64Kg; 6pcs/10.8Kg/1.1CUFT
¢J
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The power supply unit will have no output if the shorting connector is not assembled. It contains three shorting wires: one is from on/off(pin13) to
12V-AUX(pin14), two is from PC(pin7) to PO(pin8) and the other is from PV(pin5) to PS(pin6). Please refter to function manual for details.
7. Please consult MEAN WELL for applications of more units connecting in parallel.
File Name:RSP-750-SPEC 2012-08-27
RSP-750
750W Single Output Power Supply
Mechanical Specification
Case No.212A
series
Unit:mm
236
25.4
20.5
7.8
6
3-M4 L=6
250
231.5
41
63.5
18.5
33.5
-V
CN50
SVR51
2
1
14
13
7
3
2
1
10
Air flow
direction
90
127
+V
3-M4 L=4
TB1
6
236
Control Pi n No. Assignment (CN50) : HRS DF11-14DP-2DS or equivalent
AC Input Terminal
Pin No. Assignment
Pin No.
1
2
3
7.8
20.5
25.4
3-M4 L=6
Pin No.
1
2
3
4
5
Assignment
AC/N
AC/L
FG
Pin No.
6
7
8
9
10,11
Assignment
+S
+VS
-S
-VS
PV
Pin No.
12
13
14
Assignment
PS
PC
PO
DC-OK
GND
Assignment
G-AUX
ON/OFF
12V-AUX
Mating Housing
Terminal
HRS DF11-14DS
or equivalent
HRS DF11-**SC
or equivalent
Block Diagram
+S
ACTIVE
INRUSH
CURRENT
LIMITING
EMI
FILTER
I/P
RECTIFIERS
&
PFC
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
PFC fosc : 90KHz
PWM fosc : 70KHz
-S
O.L.P.
PFC
CONTROL
DETECTION
CIRCUIT
PWM
CONTROL
DC OK
V_TRIM
O.V.P.
RECTIFIERS
CONTROL
ON/OFF
AUX
POWER
Derating Curve
FAN
ON/OFF
AUX POWER(12V/0.1A)
RECTIFIERS
&
FILTER
AUX GND
Static Characteristics
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
50
40
20
-30
60
50
40
0
10
20
30
40
50
¢J
AMBIENT TEMPERATURE ( )
60
70 (HORIZONTAL)
90
95
100
115
264
INPUT VOLTAGE (VAC) 60Hz
File Name:RSP-750-SPEC 2012-08-27
RSP-750
750W Single Output Power Supply
series
Function Description of CN50
Pin No. Function Description
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
+S
1
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
2
+VS
3
-S
4
-VS
5
PV
6
PS
7
PC
8
PO
9
10,11
12
13
14
+V Signal. The +VS should be connected to the +S to reduce the noise when "output voltage TRIM" function is in use.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
-V Signal. The -VS should be connected to the -S to reduce the noise when "output voltage TRIM" function is in use.
Connect to external DC voltage source for output voltage triming, referenced to pin 10,11 (GND). Output voltage can be trimmed between
40 ~ 110% of the rated output voltage.
Short connecting between PV (pin5) and PS (pin6) if "output voltage TRIM" function is not used.
Connect to external DC voltage source for output current triming, referenced output current can be trimmed between 40 ~ 110% of the rated
output current. Please refer to function manual for details.
Short connecting between PC (pin7) and PO (pin8) if output current trim function is not used.
Open collector signal, referenced to pin10,11(GND). Low when PSU turns on. The maximum sink current is 10mA and the maximum
DC_OK external voltage is 5.6V.
GND These pins connect to the negative terminal (-V). Return for DC_OK Signal output.
G-AUX Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).
ON/OFF Turns the output on and off by electrical or dry contact between pin 13 ( ON/OFF) and pin 14 (12V-AUX). Short: Power ON, Open: Power OFF.
Auxiliary voltage output, 10.8~13.2V, referenced to pin 12(G-AUX). The maximum load current is 0.1A. This output is not controlled by the
12V-AUX "remote ON/OFF control".
Function Manual
1."Remote ON/OFF" and "Output voltage trim" and "Output current trim" functions are not used.
(1)The power supply unit will have no output if the shorting connector (accessory comes along with the PSU) is not assembled. It contains
three shorting wires : one is from ON/OFF (pin13) to 12V-AUX (pin14), two is from PV(pin5) to PS (pin6) and the other is from PC (pin7) to PO (pin8).
(2)Factory setting is shorted as Fig1.1
-V
CN50
+V
TB1
1
13
2
14
LOAD
-
+
CN50
1
3
5
7
13
+S
-S
PV
PC DC_OK GND ON/OFF
+VS
-VS
PS
PO
2
Fig 1.1
4
6
GND G-AUX 12V-AUX
8
14
(Shorting connector)
File Name:RSP-750-SPEC 2012-08-27
RSP-750
750W Single Output Power Supply
series
2.Remote ON/OFF
The PSU can be turned ON/OFF by using the "Remote
ON/OFF" function
Between ON/OFF(pin13) and 12V-AUX(pin14)
Output Status
SW close (Short)
PSU ON
SW open (Open)
PSU OFF
-V
CN50
+V
TB1
1
13
2
14
CN50
LOAD
-
1
+
3
5
-S
+S
13
7
PV
PC DC_OK GND ON/OFF
SW
Fig 2.1
+VS
PS
-VS
PO
GND G-AUX 12V-AUX
8
6
4
2
14
3.DC_OK signal
"DC_OK" is an open collector signal.
It indicates the output status of the PSU. It can operate
in two ways : One is sinking current from external TTL
signal ; the other is sending out a TTL voltage signal.
3-1 Sink current :
The maximum sink current is 10mA and the maximum
external voltage is 5.6V.
-V
3-2 TTL voltage signal :
Between DC- OK(pin9) and GND(pin10&11)
CN50
+V
TB1
1
13
2
14
Output Status
0 ~ 1V
PSU ON
3.3 ~ 5.6V
PSU OFF
CN50
LOAD
-
1
+
3
5
7
9
11
13
+S
-S
PV
PC DC_OK GND ON/OFF
+VS
-VS
PS
PO
Fig 3.1
4
2
6
8
5
7
GND G-AUX 12V-AUX
14
4.Remote Sense
The remote sensing compensates voltage drop on the
load wiring up to 0.5V.
-V
CN50
+V
1
2
TB1
13
14
Sense lines should
be twisted in pairs
-S
(Pin3)
LOAD
-
+S
+ (Pin1)
Fig 4.1
CN50
1
3
+S
-S
PV
PC DC_OK GND ON/OFF
+VS
-VS
PS
PO
6
8
13
GND G-AUX 12V-AUX
14
File Name:RSP-750-SPEC 2012-08-27
RSP-750
750W Single Output Power Supply
series
5.Output Voltage TRIM
Output voltage of RSP-750 can be trimmed between
40% ~ 110% of its rated value by the following methods :
(1)Using an external DC source (1~5.5VDC) between
"PV"(pin5) and "GND"(pin10,11) that is shown in Fig5.1
OVP 120%(Typ.)
OUTPUT VOLTAGE (%)
Vout
-V
CN50
+V
120
110
100
80
TB1
1
13
2
14
Non-Linear
LOAD
60
-
+
40
External Voltage (1~5.5VDC)
20
UVP 10%(Typ.)
1
2
3
4
PV(Referenced to GND)
5 5.5 6
1
EXTERNAL VOLTAGE (VDC)
Note: External voltage<0.5V Vo may be the UVP need to restart.
3
5
7
CN50
11
13
+S
-S
PV
PC DC_OK GND ON/OFF
+VS
-VS
PS
PO
2
4
GND G-AUX 12V-AUX
8
14
Fig 5.1
6.Output Current TRIM
Output current of RSP-750 can be trimmed between 40% ~ 110% of its rated value by the following methods :
(1)Using external voltage source between "PC"(pin7) and "GND"(pin10,11) that is shown in Fig6.1
Io 115%(Typ.)
OUTPUT CURRENT (%)
Io
External Voltage (1~5.5VDC)
120
110
100
1
80
CN50 11
7
13
PV
PC DC_OK GND ON/OFF
+VS
-VS
PS
PO
2
40
5
-S
Non-Linear
60
3
+S
4
GND G-AUX 12V-AUX
14
6
20
1
2
3
4
5 5.5 6
PC(Referenced to GND)
Fig 6.1
EXTERNAL VOLTAGE (VDC)
File Name:RSP-750-SPEC 2012-08-27