MEANWELL RCP-2000

RCP-2000
2000W Front End Power Supply
series
Features :
Universal AC input / Full range
Built-in 5V/0.3A, 12V/0.8A auxiliary power
Built-in active PFC function, PF>0.98
High efficiency up to 92%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage / Over temperature
High Power density 21.4W/inch3
Forced air cooling by built-in DC fan with fan speed control
Low profile:1U height
Remote control for single unit
Built-in remote sense function
Output voltage trimming function
Hot-swap operation
PMBus serial communication
AC OK, DC OK signal, fan fail, OTP alarm signal
Internal OR-ing FET
3 years warranty
Description :
The RCP-2000 series are state of the art AC/DC frond-end rectifiers with 1U compact size and 21.4 W/in3 of high power density. They can
provide up to 2000W per unit for the applications of servers, information technology equipment, networking, telecommunications, and wide
range of industrial applications using distributed power architecture. Equipped with hot-swap function and PMBus communication protocol,
RCP-2000 can be assembled in 1U 19” rack and controlled/monitored by external device such as monitoring unit (RCP-CMU-1) or PC.
SPECIFICATION - Single Unit
MODEL
RCP-2000-12
RCP-2000-24
RCP-2000-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
100A
80A
42A
CURRENT RANGE
0 ~ 100A
0 ~ 80A
0 ~ 42A
RATED POWER
1200W
1920W
2016W
200mVp-p
300mVp-p
21 ~ 28V
1.0%
42 ~ 56V
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
10.5 ~ 14V
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
1.0%
0.5%
0.5%
LOAD REGULATION
1.0%
0.5%
0.5%
1500ms, 60ms/230VAC at full load
SETUP, RISE TIME
16ms/230VAC at 75% load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
Note.5 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.98/230VAC at full load
EFFICIENCY (Typ.)
86%
13A/115VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
10ms/230VAC at full load
127 ~ 370VDC
90.5%
16A/115VAC
7A/230VAC
10A/230VAC
92%
16A/115VAC
10A/230VAC
COLD START 50A
<1.1mA / 230VAC
105 ~ 125% rated output power
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
FUNCTION
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
14.7 ~ 17.5V
29.5 ~ 35V
Protection type : Shut down o/p voltage, re-power on to recover
80
5 (TSW1) detect on heatsink of power bridge
85
57.6 ~ 67.2V
5
(TSW2) detect on heatsink of o/p diode
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
AUXILIARY POWER
REMOTE ON/OFF CONTROL
5V @ 0.3A, 12V @ 0.8A
REMOTE SENSE
DC OK SIGNAL
Compensate voltage drop on the load wiring up to 0.5V
By electrical signal or dry contact
ON:short
OFF:open
The isolated TTL signal out, refer to function manual
AC OK SIGNAL
The isolated TTL signal out, refer to function manual
OUTPUT VOLTAGE TRIM
Adjustment of output voltage, possible between 90 ~ 110% of rated output
OVER TEMP WARNING
Logic " High" for over temperature warning, refer to function manual, isolated signal
FAN FAIL SIGNAL
The isolated TTL signal out, refer to function manual
WORKING TEMP.
-40 ~ +70
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
File Name:RCP-2000-SPEC 2011-05-09
RCP-2000
2000W Front End Power Supply
MODEL
RCP-2000-12
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
OTHERS
RCP-2000-24
RCP-2000-48
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
60.1Khrs min. MIL-HDBK-217F (25
295*127*41mm (L*W*H)
2Kg;6pcs/13Kg/1.04CUFT
DIMENSION
PACKING
series
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Output of all the RCP-2000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
NOTE
Mechanical Specification (Single Unit)
Case No. 974A
Unit:mm
295
41
127
46
SVR1
CN501
DC OK
24
Air flow
direction
33
1 3 5 7 9
2 4 6 8 10
11
14 17
20 23 26 29
12
15 18
21 24 27 30
13
16 19
22 25 28 31
32
34
Input / Output Connector Pin No. Assignment(CN501) : Postronic PCIM34W13M400A1
Pin No.
1,2,3,4
5,6,7,8
9
10
11
Assignment
+V
-V
-V(signal)
+V(signal)
PV
Pin No.
12
13
14
15
16
Assignment
DA
DB
+S
-S
A0
Pin No.
17
18
19
20
21
Assignment
ON/OFF
A1
A2
A3
A4
Pin No.
22
23
24
25
26
Assignment
NC
SDA
SCL
AC-OK
DC-OK
Pin No.
27
28
29
30
31
Assignment
T-ALARM
FAN-FAIL
+5V-AUX
+12V-AUX
GND-AUX
Pin No.
32
33
34
Assignment
FG
AC/L
AC/N
Mating Housing
Postronic
PCIM34W13F400A1
File Name:RCP-2000-SPEC 2011-05-09
RCP-2000
2000W Front End Power Supply
Block Diagram
series
PFC fosc : 110KHz
PWM fosc : 90KHz
+S
EMI
FILTER
I/P
ACTIVE
INRUSH
CURRENT
LIMITING
RECTIFIERS
&
PFC
ORING
FET
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
-S
O.V.P.
DETECTION
CIRCUIT
PWM
CONTROL
PFC
CONTROL
DETECTION
CIRCUIT
ORING FET
CONTROL
PV
TRANSCEIVERS
DA/DB
DATA
ISOLATION
T-Alarm
DC-OK
AC-OK
FAN FAIL
SDA/SCL
MCU
MCU
O.T.P.
AUX
POWER
FAN
PM BUS
RECTIFIERS
&
FILTER
ON/OFF
12V/0.8A
AUX POWER
5V/0.3A
Function Description of CN501
Pin No.
Function
1,2,3,4
+V
Description
Positive output voltage
5,6,7,8
-V
Negative output voltage.
-V Signal
9
-V
10
+V
+V Signal
11
PV
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
12,13
DA,DB
Differential digital signal for parallel control. (Note.1)
14
+S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
15
-S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be
twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
16,18,19,
20,21
A0,A1,A2,
A3,A4
17
ON/OFF
22
NC
Not use.
23
SDA
Serial Data used in the PMBus interface. (Note.2)
24
SCL
Serial Clock used in the PMBus interface. (Note.2)
PMBus interface address lines. (Note.1)
The unit can turn the output on and off by electrical signal or dry contact. (Note.2)
25
AC-OK
Low : When the input voltage is
26
DC-OK
High : When the Vout
27
T-ALARM
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
28
FAN-FAIL
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
29
+5V-AUX
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX (pin 31). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
30
+12V-AUX
Auxiliary voltage output, 10.8~13.2V, referenced to GND-AUX (pin 31). The maximum load current is 0.8A. This output has
the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
31
GND-AUX
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
32
FG
33
AC/L
AC Line connection.
34
AC/N
AC Neutral connection.
87Vrms. High : when the input voltage in
80% 5%. Low : When Vout
75Vrms . (Note.2)
80% 5%. (Note.2)
AC Ground connection.
Note1: Non-isolated signal, referenced to the output terminals (-V).
Note2: Isolated signal, referenced to GND-AUX.
File Name:RCP-2000-SPEC 2011-05-09
RCP-2000
2000W Front End Power Supply
Derating Curve
series
Static Characteristics
100
100
90
80
80
75
70
230VAC
Input only
LOAD (%)
LOAD (%)
60
50
40
20
12V
65
24V,48V
50
40
-40
-25
-10
0
15
30
50
60
70
90
(HORIZONTAL)
100
115
AMBIENT TEMPERATURE ( )
180
264
INPUT VOLTAGE (VAC) 60Hz
EFFICIENCY vs LOAD (48V Model)
DERATING LOAD(%) VS INPUT VOLTAGE
INPUT / VOLTAGE
94
>180VAC
115VAC
100VAC
90VAC
RCP-2000-12
100%
95%
90%
80%
RCP-2000-24
100%
80%
75%
65%
RCP-2000-48
100%
80%
75%
65%
MODEL
EFFICIENCY (%)
92
90
88
86
84
82
10
20
30
40
50
60
70
80
90
100
LOAD
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
RCP-2000
ON/OFF
Between ON/OFF and +5V-AUX
17
SW
+5V-AUX
29
Output
SW Open
OFF
SW Short
ON
2. Voltage Drop Compensation
2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
14
+S
RCP-2000
+V
LOAD
15
-S
-V
-V
Sense lines should be twisted in pairs
File Name:RCP-2000-SPEC 2011-05-09
2000W Front End Power Supply
RCP-2000
series
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
+V
+S
RCP-2000
14
-V
-S
15
3. Output Voltage Trimming
Output voltage can be trimmed between 90~110% of its rated value by the following method.
PV
11
0~5V
RCP-2000
-V Signal
9
Add on 0~5V external voltage
Vout
OUTPUT VOLTAGE(%)
110
100
90
80
70
60
0
0.5
1.5
3
4.5
5
V
EXTERNAL VOLTAGE (DC)
4. Front Panel Indicators & Corresponding Signal at Function Pins
* Signal
Function
LED
Description
AC-OK GREEN When input voltage 87V
0 ~ 0.5V
AC-NG
RED When input voltage 75V
4.5 ~ 5.5V
DC-OK GREEN When output voltage 80% 5% of Vo rated.
0 ~ 0.5V
DC-NG
RED When output voltage 80% 5% of Vo rated.
4.5 ~ 5.5V
T-OK
GREEN When the internal temperature (TSW1 & TSW2 short) is within safe limit
0 ~ 0.5V
T-ALARM RED When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm 4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*Signal between function pin and "GND-AUX".
File Name:RCP-2000-SPEC 2011-05-09