XPPOWER HPU1K5PS48

ACDC
1500 Watts
HPU1K5 Series
xppower.com
•
Medical Safety Approvals (M Versions)
•
Variable Fan Speed To Reduce Audible Noise
•
20 °C to +70 °C Operation
•
AC OK, DC OK, Inhibit & 5 V Standby Supply
•
Fault & Overtemperature Signals
•
SEMI F47 Compliant
•
3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
Earth Leakage Current
Input Protection
General
•
•
•
•
•
•
85-264 VAC, see derating curve
47-63 Hz
13 A/6.5 A typical at 115/230 VAC
35 A maximum at 264 VAC
>0.9
1.1 mA max at 264 VAC 60Hz, <500 µA at
264 VAC max, <300 µA at 130 VAC (-M)
• Internal T20 A/250 VAC fuse in line and
neutral
Output
• See model table
• Via potentiometer or external voltage,
see model tables
Initial Set Accuracy
• ±1% of nominal with 50% load
Minimum Load
• No minimum load required
Line Regulation
• ±0.5% maximum
Load Regulation
• V1: ±0.5%, V2: ±5%
Start Up Delay
• 1 s typical
Over/Undershoot
• 0.5% typical
Transient Response
• 4% deviation, recovery to within 2% in
500 µs for 50-75-50% load change
Ripple & Noise
• 24-48 V models: 1% max pk-pk
12 V models: 2% max pk-pk
V Standby: 3% max pk-pk,
20 MHz bandwidth
Overvoltage Protection • 115-140% of V1 nominal, recycle input
AC to reset
Overtemperature
• Protects the unit against overtemperature.
Protection
Auto restart
Overcurrent Protection • 110 - 140% V1, V Standby power limited
Short Circuit Protection • Continuous, trip and restart (hiccup mode)
Temperature
• 0.02%/°C (after 20 minute warm up)
Coefficient
Remote Sense
• Compensates for 0.5 V total drop
Current Share
• Share upto 8 units maximum, units
share current within 10% of each other
at full load.
Output Voltage
Output Voltage Trim
Efficiency
Isolation
Switching Frequency
Power Density
Signals
MTBF
• 90% typical
• 4000 VAC Input to Output 2 x MOPP,
1500 VAC Input to Ground 1 x MOPP
500 VDC Output to Ground
• 70 kHz (PFC), 130 kHz (main converter)
typical
• 18 W/in3
• AC OK, DC OK, Inhibit, Fault
(see Signals page)
• 470 kHrs to Telecordia SR-332 at 25 °C, GB
Environmental
Operating Temperature • -20 °C to +70 °C, derate linearly from
+50 °C at 2.5 %/°C to 50% load at +70°C
Cooling
• Internal load dependant variable speed fans
Operating Humidity
• 95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude
• 3000 m
Shock
• ±3 shocks in each axis (total 18 shocks)
30 g 11 ms (half sine). Compliant with
EN60068-2-27.
Vibration
• 2 g 10-500 Hz 10 sweeps. Compliant with
EN60068-2-6.
EMC & Safety
Emissions
Immunity
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
• EN55011 level A conducted & radiated,
EN55022 level A conducted & radiated
• Compliant with EN61204-3:2000
high severity levels
• EN61000-3-2 class A,
EN61000-3-2 class C for loads ≥10%
• EN61000-3-3
• EN61000-4-2, level 3, Perf Criteria A
• EN61000-4-3, level 3, Perf Criteria A
• EN61000-4-4, level 3, Perf Criteria A
• EN61000-4-5, installation class 3
Perf Criteria A, SEMI F47
• EN61000-4-6, level 3, Perf Criteria A
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms, Perf Criteria
A, A, A, B
• EN60601-1, ANSI/AAMI ES60601-1,
CSA22.2 No.60601-1 per cUL, Including
Risk Management M Versions, EN60950,
UL60950
Output Power(1)
Output Voltage
V1
Voltage Adj
V1
1200 W
1500 W
1500 W
12.0 VDC
24.0 VDC
48.0 VDC
11-14 V
22-28 V
45-52 V
Output Current V1
<180 VAC
>180 VAC
100 A
100 A
50 A
63 A
25 A
31 A
Standby Supply
V2
Model Number
5 V/1 A
5 V/1 A
5 V/1 A
HPU1K5PS12†^
HPU1K5PS24†^
HPU1K5PS48†^
Notes
1. See derating curves.
2. For medical version, add suffix ‘-M’ to model number.
† Available from Farnell & element14. See pages 284-290.
^ Available from Newark. See pages 291-296.
Mechanical Details
1.70 (43.2)
0.10 (2.5)
12.75 (323.9)
1.55
(39.4)
Voltage Adj.
+V BUSS BAR
-V BUSS BAR
4.00
(101.6)
E
L
N
Logic J3 Connector
1.00 (25.4)
4X M3 THD on both side faces 0.15 (3.8) max screw penetration
0.35 (8.9)
0.25 (6.4)
2.90
(73.7)
8.00 (203.2)
0.53 (13.3)
AIR FLOW
2.95 (74.9)
AIR FLOW
4X M3 THD
0.15 (3.8) Max Screw Penetration
Logic Connector: J3, JST, PN S20B-PHDSS (LF) SN)
Function
Pin
Function
Pin
Function
+ Sense
8
NC
15
DC OK
+ Sense
9
Inhibit
16
NC
- Sense
10
NC
17
Signal GND
- Sense
11
Fault
18
NC
Current Share
12
NC
19
5 V Standby Rtn (V2)
Current Share
13
AC OK
20
5 V Standby (V2)
V Trim
14
NC
Mates with JST PN PHDR-20VS, Crimp contacts JST PN SPHD-00IT-P0.5
Notes
1. All dimensions are in inches (mm).
20
1
2
0.25 (6.4)
1.00 (25.4)
Pin
1
2
3
4
5
6
7
19
10.50 (266.7)
2. Weight 5.2 lb (2.35 kg)
ACDC
HPU1K5
Models and Ratings
ACDC
HPU1K5
Signals
AC OK/Power Fail
DC OK
AC OK is an isolated signal providing a minimum of 3 ms warning of loss of
output regulation. The signal is fully isolated and the collector and emitter must
be connected externally.
DC OK is an isolated signal providing warning that the output voltage has fallen
below 90% of nominal. The signal is fully isolated and the collector and emitter
must be connected externally.
Maximum sink current 2 mA, maximum voltage 20 V.
Maximum sink current 2 mA, maximum voltage 20 V.
POWER SUPPLY
POWER SUPPLY
5 V Standby
Pin 20
3300R
5 V Standby
Pin 20
3300R
DC OK Collector
Pin 15
AC OK Collector
Pin13
Transistor On (<0.8 V): DC OK
Transistor Off (>4.5 V): DC NOT OK
Transistor On (<0.8 V): AC OK
Transistor Off (>4.5 V): AC NOT OK
AC OK Emitter
Pin 17
DC OK Emitter
Pin 17
5 V Standby
Return Pin 19
5 V Standby
Return Pin 19
J3 Connector
J3 Connector
Inhibit
Fault
Inhibit is an isolated control signal which can turn the power supply and fans off
by supplying 2 to 5 mA into the pin.
Fault is an isolated signal providing warning of either Power Fail or DC fail.
The signal is fully isolated and the collector and emitter must be connected
externally.
Maximum sink current 2 mA, maximum voltage 20 V.
800R
POWER SUPPLY
5 V Standby
Pin 20
2-5 mA
POWER SUPPLY
100R
0 V or Floating: Power Supply On
2-5 mA: Power Supply Off
5 V Standby
Pin 20
Inhibit
Pin 9
3300R
Fault Collector
Pin 11
Inhibit
Return Pin 17
Transistor On (<0.8 V): FAULT
Transistor Off (>4.5 V): OK
Fault Emitter
Pin 17
5 V Standby
Return Pin 19
J3 Connector
5 V Standby
Return Pin 19
J3 Connector
V Program
Current Share
V Program allows remote voltage adjustment within the range ±10%
Connecting pins 5 or 6 and 3 or 4 of like voltage units (8 maximum) will force the
current to share between the outputs. Units share current within 10% of each
other at full load. Derate output to 90% of total combined load.
POWER SUPPLY
V Trim
Pin 7
- Sense
Pin 3 & 4
J3 Connector
V Program V Output
0V
-10%
5V
+10%
Open
Circuit
Factory
Set Voltage
PSU 1
Pin
5 or 6
Pin
3 or 4
PSU 2
Pin
5 or 6
Pin
3 or 4
PSU 8
Pin
5 or 6
Pin
3 or 4
Parallel Load & Current Share Connections
HPU1K5PSXX (1)
V1 Output
-
Current
Share
e
-S
s
en
+
e
+
se
en
-S
ns
e
Se
V1 Output
-
Current
Share
+ Sens
+
+
Se
ns
e
+
- Sense
-
HPU1K5PSXX (3)
HPU1K5PSXX (2)
V1 Output
-
+
Load
Parallel AC OK Connection
(DC OK follows same format)
HPU1K5PSXX(1)
5 V Standby
Pin 20
330R
AC OK Collector
Pin 13
AC OK Emitter
Pin 17
5 V Standby
Return Pin 19
J3 Connector
HPU1K5PSXX(2)
OK Collector
Pin 13
OK Emitter
Pin 17
J3 Connector
HPU1K5PSXX(3)
AC OK
Collector
Pin 13
Transistor On (<0.8 V): AC OR DC OK
Transistor Off (>4.5 V): AC OR DC NOT OK
AC OK Emitter
Pin 17
J3 Connector
Derating Curves
Input Derating Curve
Thermal Derating Curve
1500
1400
1600
1400
1200
1200
Output Power (W)
Output Power (W)
HPU1K5PS24 & 48
1300
1100
1000
HPU1K5PS12
900
800
HPU1K5PS24, 48, >180VAC Input
1000
800
600
HPU1K5PS12
& HPU1K5PS24, 48, <180VAC Input
400
85
90
110
120
180
190
250
200
210
Input Voltage (VAC)
220
230
240
250
260
260 264
-20
-10
0
10
20
30
40
50
60
70
80
Ambient (ºC)
07-Nov-12
ACDC
HPU1K5
Signals