SIEMENS 3TB5217-0LF4

3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Tolerance 0.7 ... 1.25 x Us , for Railway Applications
3RT10 motor contactors, 5.5 ... 45 kW
DC operation · DC solenoid system
Screw terminals
For screw and snap-on mounting onto standard mounting rail
Contactor control unit
Solenoid fitted with varistor
Auxiliary contacts1)
Rated data
AC-2 and AC-3
Tu: up to 70 °C
Rating of
induction
Ident.
motors at 50 Hz No.
400 V
400 V
A
kW
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
Version
PG
Weight
per PU
approx.
Price
per PU
3
Rated
operational
current Ie at
Rated control DT
supply voltage
Us
NO
NC
V DC
kg
For screw and snap-on mounting onto
35 mm standard mounting rail
Size S0
17
7.5
---
---
---
24
110
B
B
3RT10 25-1XB40-0LA2
3RT10 25-1XF40-0LA2
1
1
1 unit
1 unit
101
101
0.625
0.340
25
11
---
---
---
24
110
B
B
3RT10 26-1XB40-0LA2
3RT10 26-1XF40-0LA2
1
1
1 unit
1 unit
101
101
0.627
0.445
32
15
---
---
---
24
110
B
B
3RT10 34-1XB40-0LA2
3RT10 34-1XF40-0LA2
1
1
1 unit
1 unit
101
101
1.432
1.505
40
18.5
---
---
---
24
110
B
B
3RT10 35-1XB40-0LA2
3RT10 35-1XF40-0LA2
1
1
1 unit
1 unit
101
101
1.491
1.432
50
22
---
---
---
24
110
B
B
3RT10 36-1XB40-0LA2
3RT10 36-1XF40-0LA2
1
1
1 unit
1 unit
101
101
1.491
1.432
Size S2
For screw and snap-on mounting onto
35 mm and 75 mm standard mounting rail
Size S3
65
30
---
---
---
24
110
B
B
3RT10 44-1XB40-0LA2
3RT10 44-1XF40-0LA2
1
1
1 unit
1 unit
101
101
2.864
2.775
80
37
---
---
---
24
110
B
B
3RT10 45-1XB40-0LA2
3RT10 45-1XF40-0LA2
1
1
1 unit
1 unit
101
101
2.871
2.720
95
45
---
---
---
24
110
B
B
3RT10 46-1XB40-0LA2
3RT10 46-1XF40-0LA2
1
1
1 unit
1 unit
101
101
2.913
2.913
1) Auxiliary switch blocks mountable as standard contactors.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/71
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Tolerance 0.7 ... 1.25 x Us , for Railway Applications
3RT10 motor contactors, 5.5 ... 45 kW
3
DC operation · DC solenoid system
Cage Clamp terminals
For screw and snap-on mounting onto standard mounting rail
Contactor control unit
Solenoid fitted with varistor
3RT10 ..-3X.40-0LA2
Auxiliary contacts1)
Rated data
AC-2 and AC-3
Tu: up to 70 °C
Rated
operational
current Ie at
Rated control DT
supply voltage
Us
Order No.
Version
400 V
Rating of
induction
Ident.
motors at 50 Hz No.
400 V
A
kW
NO
NC
V DC
PU
PS*
(UNIT,
SET, M)
Cage Clamp terminals
for coil connections
PG
Weight
per PU
approx.
Price
per PU
kg
For screw and snap-on mounting onto
35 mm standard mounting rail
Size S0
17
7.5
---
---
---
24
110
B
B
3RT10 25-3XB40-0LA2
3RT10 25-3XF40-0LA2
1
1
1 unit
1 unit
101
101
0.340
0.645
25
11
---
---
---
24
110
B
B
3RT10 26-3XB40-0LA2
3RT10 26-3XF40-0LA2
1
1
1 unit
1 unit
101
101
0.630
0.639
32
15
---
---
---
24
110
C
B
3RT10 34-3XB40-0LA2
3RT10 34-3XF40-0LA2
1
1
1 unit
1 unit
101
101
1.466
1.500
40
18.5
---
---
---
24
110
C
B
3RT10 35-3XB40-0LA2
3RT10 35-3XF40-0LA2
1
1
1 unit
1 unit
101
101
1.486
1.515
50
22
---
---
---
24
110
B
B
3RT10 36-3XB40-0LA2
3RT10 36-3XF40-0LA2
1
1
1 unit
1 unit
101
101
1.489
1.466
Size S2
For screw and snap-on mounting onto
35 mm and 75 mm standard mounting rail
Size S3
65
30
---
---
---
24
110
B
B
3RT10 44-3XB40-0LA2
3RT10 44-3XF40-0LA2
1
1
1 unit
1 unit
101
101
2.855
2.787
80
37
---
---
---
24
110
B
B
3RT10 45-3XB40-0LA2
3RT10 45-3XF40-0LA2
1
1
1 unit
1 unit
101
101
2.720
2.720
95
45
---
---
---
24
110
B
B
3RT10 46-3XB40-0LA2
3RT10 46-3XF40-0LA2
1
1
1 unit
1 unit
101
101
2.913
2.913
1) Auxiliary switch blocks mountable as standard contactors.
* You can order this quantity or a multiple thereof.
3/72
Siemens LV 1 · 2006
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Tolerance 0.7 ... 1.25 x Us , for Railway Applications
3TB5 motor contactors, 55 ... 200 kW
■ Overview
■ Application
EN 60947-4-1.
For requirements according to IEC 60077-1 and IEC 60077-2.
For operation in plants which are subject both to considerable
variations in the control voltage and to high ambient
temperatures, e.g. in railway applications.
The contactors are finger-safe according to EN 50274. Terminal
covers may have to be fitted onto the connecting bars,
depending on the configuration with other devices.
■ Selection and ordering data
Size
3
3TB50 to 3TB56 contactors
With screw terminals
For screw fixing
Solenoid fitted with varistor
Rated data
AC-2 and AC-3
Auxiliary
contacts1)
Rated control supply DT Order No.
voltage Us
NO
NC
V DC
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Ratings of induction motors
Operaat
tional
current Ie
at
400 V
230 V 400 V 500 V 690 V
A
kW
kW
kW
kW
kg
Contactors for switching AC voltage ·
DC operation · DC solenoid system
6
110
37
55
75
90
2
1
24
110
C
C
3TB50 17-0LB4
3TB50 17-0LF4
1 1 unit
1 1 unit
101
101
6.674
6.640
8
170
55
90
110
132
2
1
24
110
C
C
3TB52 17-0LB4
3TB52 17-0LF4
1 1 unit
1 1 unit
101
101
9.250
9.222
10
250
75
132
160
200
2
1
24
110
C
C
3TB54 17-0LB4
3TB54 17-0LF4
1 1 unit
1 1 unit
101
101
16.800
8.845
12
400
115
200
255
355
2
1
110
C
3TB56 17-0LF4
1 1 unit
101
19.793
1) The number of auxiliary contacts cannot be increased.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/73
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
Contactors with Extended Tolerance 0.7 ... 1.25 x Us , for Railway Applications
3TC contactors for switching DC voltage, 2-pole
■ Overview
■ Application
EN 60947-4-1.
For operation in plants which are subject both to considerable
variations in the control voltage and to high ambient
temperatures, e.g. in railway applications.
For requirements according to IEC 60077-1 and IEC 60077-2.
The contactors are finger-safe according to EN 50274
(exception: series resistor). Terminal covers may have to be
fitted onto the connecting bars, depending on the configuration
with other devices.
3
■ Selection and ordering data
With screw terminals
3TC44: for screw and snap-on mounting onto 35 mm standard mounting rail
3TC48 to 3TC56: for screw fixing
Solenoid fitted with varistor
3TC48
Size
Utilization
category
Rated
operational
current Ie at
Rating of AC loads at
Auxiliary Rated control DT Order No.
contacts1) supply
voltage Us
750 V
220 V 440 V 600 V 750 V
A
kW
kW
kW
kW
NO
NC V DC
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Contactors for switching DC voltage ¼
DC operation · DC solenoid system
2
DC-1
DC-3/DC-5
32
7.5
7
5
14
9
19.2
9
24
4
2
1
24
110
B
C
3TC44 17-0LB4
3TC44 17-0LF4
1 1 unit
1 1 unit
101
101
1.321
1.310
4
DC-1
DC-3/DC-5
75
75
16.5
13
33
27
45
38
56
45
2
1
24
110
C
C
3TC48 17-0LB4
3TC48 17-0LF4
1 1 unit
1 1 unit
101
101
4.857
3.710
8
DC-1
DC-3/DC-5
170
170
48
41
97
82
132
110
165
110
2
1
24
110
C
C
3TC52 17-0LB4
3TC52 17-0LF4
1 1 unit
1 1 unit
101
101
10.722
10.830
12
DC-1
DC-3/DC-5
400
400
88
70
176
140
240
200
300
250
2
1
24
110
C
C
3TC56 17-0LB4
3TC56 17-0LF4
1 1 unit
1 1 unit
101
101
24.150
18.190
1) The number of auxiliary contacts cannot be increased.
* You can order this quantity or a multiple thereof.
3/74
Siemens LV 1 · 2006
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
■ Overview
3TC4 and 3TC5
EN 60947-4-1 (VDE 0660 Part 102)
The contactors are finger-safe according to EN 50274.
Terminal covers may have to be fitted onto the connecting bars,
depending on the configuration with other devices.
■ Application
The contactors are suitable for switching and controlling DC
motors as well as all other DC circuits.
A version with an especially large operating range is available
for use in electrically driven vehicles and in switchgear with
significant fluctuations in the operating voltage (see page 3/74).
3
The DC motor ratings given in the tables are applicable to the
DC-3 and DC-5 utilization categories with two-pole switching of
the load or with the two conducting paths of the contactor
connected in series.
One contactor conducting path can switch full power up to
220 V. The ratings for higher voltages are available on request.
3TC7
EN 60947-4-1 (VDE 0660 Part 102).
The contactors are suitable for use in any climate. They are
suitable for switching and controlling DC motors as well as all
other DC loads. The electromagnetic excitation is designed for
a particularly wide coil operating range.
It is between 0.7 or 0.8 to 1.2 ™ Us.
3TC74 contactors can be used at up to 750V/400A and 50 Hz in
AC-1 operation.
Siemens LV 1 · 2006
3/75
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
■ Selection and ordering data
3TC48
3TC44
Rated data DC-3 and DC-51)
Auxiliary
contacts2)
3
Size
OperaRatings of
tional
DC motors at
3)
current Ie
Rated control DT Order No.
supply voltage
Us
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Version
110 V 220 V 440 V 600 V 750 V
A
kW
kW
kW
kW
kW
NO
NC
V
kg
3TC44 to 3TC56 2-pole contactors ¼ Operating voltage up to 440 V
DC operation
Screw and snap-on mounting onto 35 mm standard mounting rail
2
32
2.5
5
9
9
4
2
2
24 DC
110 DC
220 DC
}
}
}
3TC44 17-0AB4
3TC44 17-0AF4
3TC44 17-0AM4
1 1 unit 101
1 1 unit 101
1 1 unit 101
1.050
1.046
1.050
Screw mounting
4
75
6.5
13
27
38
45
2
2
24 DC
110 DC
220 DC
}
}
A
3TC48 17-0AB4
3TC48 17-0AF4
3TC48 17-0AM4
1 1 unit 101
1 1 unit 101
1 1 unit 101
4.680
4.745
4.513
8
2204)
20
41
82
110
110
2
2
24 DC
110 DC
220 DC
C
C
C
3TC52 17-0AB4
3TC52 17-0AF4
3TC52 17-0AM4
1 1 unit 101
1 1 unit 101
1 1 unit 101
10.589
9.826
9.878
12
400
35
70
140
200
250
2
2
24 DC
110 DC
220 DC
C
C
C
3TC56 17-0AB4
3TC56 17-0AF4
3TC56 17-0AM4
1 1 unit 101
1 1 unit 101
1 1 unit 101
17.870
19.318
22.870
220 / 230 AC5) }
110 / 110 AC
}
3TC44 17-0BP0
3TC44 17-0BF0
1 1 unit 101
1 1 unit 101
0.673
0.683
AC operation, 50/Hz
Screw and snap-on mounting onto 35 mm standard mounting rail
2
32
2.5
5
9
9
4
2
2
Screw mounting
4
75
6.5
13
27
38
45
2
2
220 / 230 AC5) }
110 AC
C
3TC48 17-0BP0
3TC48 17-0BF0
1 1 unit 101
1 1 unit 101
3.447
3.487
8
2204)
20
41
82
110
110
2
2
220 / 230 AC5) A
110 AC
C
3TC52 17-0BP0
3TC52 17-0BF0
1 1 unit 101
1 1 unit 101
7.005
7.041
3TC56 17-0BP0
3TC56 17-0BF0
1 1 unit 101
1 1 unit 101
14.437
14.363
12
400
35
70
140
200
250
2
2
220 / 230 AC
110 AC
5)
C
C
For more rated control supply voltages Us, see page 3/77.
1) For the permissible load for utilization category DC-1,
see Technical Specifications.
2) The auxiliary switch complement cannot be altered on DC-operated
contactors.
3) The following rated operational currents are permitted for reversing duty
with 3TC44 to 3TC56 contactors:
Contactor
Rated operating voltage
Type
110 V, 220 V 440 V
3TC44
3TC48
3TC52
3TC56
32 A
75 A
170 A
400 A
7A
75 A
170 A
400 A
4) For > 600 V: Ie = 170 A.
5) Operating range at 220 V: 0.85 to 1.15 x Us.
* You can order this quantity or a multiple thereof.
3/76
Siemens LV 1 · 2006
3RT, 3RH, 3TB, 3TC, 3TH, 3TK Contactors for Special Applications
3TC Contactors for Switching DC Voltage
1- and 2-pole, 32 ... 400 A
Size
Rated data
DC-3 and DC-51)
Auxiliary Rated control DT Order No.
contacts2) supply
voltage Us
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Ratings of DC motors at
Operational
current Ie
110 V 220 V 440 V 600 V 750 V 1200 V 1500 V
A
kW
kW
kW
kW
kW
kW
kW
NO
NC V
kg
3TC74 1-pole contactors ¼ Operating voltage up to 750 V
DC operation
12
400
35
70
140
200
250
--
--
4
4
24 DC
110 DC
C
C
3TC74 14-0EB
3TC74 14-0EF
1 1 unit 101 10.728
1 1 unit 101 10.660
70
140
200
250
--
--
4
4
230 / 220 AC3) C
3TC74 14-1CM
1 1 unit 101 10.850
AC operation, 50 Hz
12
400
35
3TC78 2-pole contactors ¼ Operating voltage up to 1500 V
DC operation
12
400
35
70
140
200
250
400
500
4
4
24 DC
110 DC
C
C
3TC78 14-0EB
3TC78 14-0EF
1 1 unit 101 22.500
1 1 unit 101 15.960
70
140
200
250
400
500
4
4
230 / 220 AC3) C
3TC78 14-1CM
1 1 unit 101 23.824
AC operation, 50 Hz
12
400
35
For more rated control supply voltages Us, see below.
For spare parts, see page 3/144.
1) For the permissible load for utilization category DC-1,
see Technical Specifications.
2) The auxiliary switch complement cannot be altered on DC-operated
contactors.
3) Upper operating range limit at 230 V: 1.14 x Us.
Contactor type
Rated control supply voltage Us
3TC44
3TC48
3TC52/56
3TC74/78
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
AC operation · Coils for 50 Hz
24 V AC
110 V AC
B0
F0
B0
F0
-F0
---
230/220 V AC
240 V AC
P01)
U0
P01)
U0
P01)
--
M2)
--
24 V AC
110 V AC
120 V AC
C2
G2
K2
----
----
----
220 V AC
230 V AC
N2
L2
---
---
---
24 V DC
48 V DC
60 V DC
B4
W4
E4
B4
W4
E4
B4
---
B
---
110 V DC
125 V DC
220 V DC
F4
G4
M4
F4
G4
M4
F4
-M4
F
-M
230 V DC
P4
P4
--
--
AC operation · Coils for 50/60 Hz
DC operation
1) Coil operating range at 220 V or 380 V: 0.85 to 1.15 x Us;
lower operating range limit according to IEC 60947.
2) Upper operating range limit at 230 V: 1.14 x Us.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/77
3
3TC78
3TC74
3RH, 3TH Contactor Relays
3RH1 contactor relays, 4- and 8-pole
■ Overview
The SIRIUS generation of controls is a complete, modular
system family, logically designed right down to the last detail,
from the basic units to the accessories.
AC and DC operation
Contactor relays and coupling relays
Size S00 with accessories
The 3RH1 contactor relays are suitable for use in any climate.
They are finger-safe according to EN 50274.
IEC 60947, EN 60947 (VDE 0660)
The 3RH1 contactor relays have screw or Cage Clamp
terminals. Four contacts are available in the basic unit.
3
3
4
12
5
1
6
13
7
8
2
9
14
10
11
15
16
1
Contactor relay, see page 3/79
2
Coupling relay for auxiliary circuits, see page 3/88
3
Solid-state time-delay block, ON-delay, see page 3/118
4
Solid-state time delay block, OFF-delay, see page 3/118
5
Auxiliary switch block with solid-state time delay, see page 3/117
(versions: ON or OFF-delay)
6
1-pole auxiliary switch block, cable entry from above, see page 3/110
7
2-pole auxiliary switch block, cable entry from above, see page 3/110
8
Single-pole auxiliary switch block, cable entry from below, see page 3/110
9
2-pole auxiliary switch block, cable entry from below, see page 3/110
10 4-pole auxiliary switch block, see page 3/110
(terminal designations according to EN 50011 or EN 50005)
11 2-pole auxiliary switch block, standard design or solid-state compatible
version, see page 3/110
(terminal designations according to EN 50005)
12 Solder pin adapter for contactor relays with 4-pole auxiliary switch block,
see page 3/123
13 Solder pin adapter for contactor relays and coupling relays, see page 3/122
14 Additional load module for increasing the permissible residual current,
see page 3/121
15 Surge suppressor with LED, see page 3/120
16 Surge suppressor without LED, see page 3/120
3/78
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3RH1 contactor relays, 4- and 8-pole
■ Selection and ordering data
3RH11 ..-1...
3RH12 ..-1...
Rated operational
current
Ie/AC-15/AC-14 at
Contacts
230 V
Ident. No. Version
A
3
AC and DC operation
Screw terminals
Rated control supply
voltage Us
NO
DT
Order No.
NC
PU
PS*
(UNIT,
SET, M)
Screw terminals
PG
Weight
per PU
approx.
Price
per PU
kg
V
For screw and snap-on mounting onto 35 mm standard mounting rail
AC operation
AC 50/60 Hz1)
• Size S00
Terminal designations according to EN 50011
6
40 E
4
--
24
110
230
}
}
}
3RH11 40-1AB00
3RH11 40-1AF00
3RH11 40-1AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.204
0.202
0.204
31 E
3
1
24
110
230
}
}
}
3RH11 31-1AB00
3RH11 31-1AF00
3RH11 31-1AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.204
0.202
0.203
22 E
2
2
24
110
230
}
}
}
3RH11 22-1AB00
3RH11 22-1AF00
3RH11 22-1AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.203
0.202
0.204
With permanently mounted auxiliary switch block
6
44 E
4
4
230
}
3RH12 44-1AP00
1
1 unit
101
0.254
62 E
6
2
230
}
3RH12 62-1AP00
1
1 unit
101
0.251
DC operation · DC solenoid system
DC
6
40 E
4
--
24
220
}
}
3RH11 40-1BB40
3RH11 40-1BM40
1
1
1 unit
1 unit
101
101
0.264
0.261
31 E
3
1
24
220
}
}
3RH11 31-1BB40
3RH11 31-1BM40
1
1
1 unit
1 unit
101
101
0.262
0.259
22 E
2
2
24
220
}
}
3RH11 22-1BB40
3RH11 22-1BM40
1
1
1 unit
1 unit
101
101
0.264
0.260
With permanently mounted auxiliary switch block
6
44 E
4
4
24
}
3RH12 44-1BB40
1
1 unit
101
0.312
62 E
6
2
24
}
3RH12 62-1BB40
1
1 unit
101
0.313
For other voltages, see page 3/81.
For accessories, see page 3/110 and 3/113.
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
1) Coil operating range
at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/79
3RH, 3TH Contactor Relays
3RH1 contactor relays, 4- and 8-pole
3
AC and DC operation
Cage Clamp terminals
3RH11 ..-2...
3RH12 ..-2...
Rated operational
current
Ie/AC-15/AC-14 at
Contacts
230 V
Ident. No. Version
A
Rated control supply
voltage Us
NO
DT
Cage Clamp terminals
Order No.
NC
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
kg
V
For screw and snap-on mounting onto 35 mm standard mounting rail
AC operation
AC 50/60 Hz1)
• Size S00
Terminal designations according to EN 50011
6
40 E
4
--
24
110
230
}
}
}
3RH11 40-2AB00
3RH11 40-2AF00
3RH11 40-2AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.201
0.199
0.200
31 E
3
1
24
110
230
}
}
}
3RH11 31-2AB00
3RH11 31-2AF00
3RH11 31-2AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.200
0.199
0.199
22 E
2
2
24
110
230
}
}
}
3RH11 22-2AB00
3RH11 22-2AF00
3RH11 22-2AP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.201
0.200
0.199
With permanently mounted auxiliary switch block
6
44 E
4
4
230
B
3RH12 44-2AP00
1
1 unit
101
0.253
62 E
6
2
230
B
3RH12 62-2AP00
1
1 unit
101
0.254
DC operation · DC solenoid system
DC
6
40 E
4
--
24
220
}
B
3RH11 40-2BB40
3RH11 40-2BM40
1
1
1 unit
1 unit
101
101
0.260
0.257
31 E
3
1
24
220
}
B
3RH11 31-2BB40
3RH11 31-2BM40
1
1
1 unit
1 unit
101
101
0.259
0.254
22 E
2
2
24
220
}
B
3RH11 22-2BB40
3RH11 22-2BM40
1
1
1 unit
1 unit
101
101
0.261
0.255
With permanently mounted auxiliary switch block
6
44 E
4
4
24
A
3RH12 44-2BB40
1
1 unit
101
0.311
62 E
6
2
24
A
3RH12 62-2BB40
1
1 unit
101
0.314
For other voltages, see page 3/81.
For accessories, see page 3/110 and 3/113.
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
1) Coil operating range
at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us.
* You can order this quantity or a multiple thereof.
3/80
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3RH1 contactor relays, 4- and 8-pole
Contactor
Type
3RH11
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
AC operation
DC operation
Coils for AC 50 and 60 Hz
Rated control supply
voltage Us
Control supply voltage at
Rated control supply voltage Us
V AC
50/60 Hz1)
V AC
60 Hz
Option
24
42
48
110
220
230
-------
B0
D0
H0
12
24
42
A4
B4
D4
F0
N2
P0
48
60
110
W4
E4
F4
400
--
V0
125
220
230
G4
M4
P4
110
220
440
G6
N6
R6
Option
3
V DC
For Japan2)
100
200
400
For USA and Canada3)
V AC
50 Hz
V AC
60 Hz
110
220
120
240
K6
P6
1) Coil operating range
at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us.
2) Coil operating range
at 50/60 Hz: 0.85 to 1.1 x Us
at 60 Hz: 0.8 to 1.1 x Us.
3) Coil operating range
at 50 Hz: 0.85 to 1.1 x Us
at 60 Hz: 0.8 to 1.1 x Us.
Siemens LV 1 · 2006
3/81
3RH, 3TH Contactor Relays
3RH14 latched contactor relays, 4-pole
■ Overview
RC elements, varistors, diodes or diode assemblies can be fitted
to both coils from the front for damping opening surges in the
coil.
AC and DC operation
IEC 60947, EN 60947 (VDE 0660)
The terminal designations comply with EN 50011.
The contactor coil and the coil of the release solenoid are both
designed for continuous duty.
The contactor relay can also be switched on and released
manually. (For minimum actuating times, see Technical
Specifications).
3
The number of auxiliary contacts can be extended by means of
auxiliary switch blocks (up to 4 poles).
■ Selection and ordering data
3RH14 22-1BB40
Rated operational
current
Ie/AC-15/AC-14 at
Contacts
230 V
Ident. No. acc. to Version
EN 50011
A
Rated control
supply voltage
Us
NO
NC
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V
kg
With screw terminals ¼ for screw and snap-on mounting onto
35 mm standard mounting rail
AC operation
AC 50/60 Hz1)
6
40 E
4
--
24
42
110
230
B
B
B
A
3RH14 40-1AB00
3RH14 40-1AD00
3RH14 40-1AF00
3RH14 40-1AP00
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.385
0.380
0.385
0.384
31 E
3
1
24
42
110
230
B
B
B
B
3RH14 31-1AB00
3RH14 31-1AD00
3RH14 31-1AF00
3RH14 31-1AP00
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.385
0.386
0.385
0.386
22 E
2
2
24
42
110
230
B
B
B
}
3RH14 22-1AB00
3RH14 22-1AD00
3RH14 22-1AF00
3RH14 22-1AP00
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.389
0.388
0.387
0.389
DC operation · DC solenoid system
DC
6
40 E
4
--
24
110
220
}
B
B
3RH14 40-1BB40
3RH14 40-1BF40
3RH14 40-1BM40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.509
0.504
0.502
31 E
3
1
24
110
220
B
B
B
3RH14 31-1BB40
3RH14 31-1BF40
3RH14 31-1BM40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.504
0.510
0.494
22 E
2
2
24
110
220
}
B
B
3RH14 22-1BB40
3RH14 22-1BF40
3RH14 22-1BM40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.504
0.505
0.510
For accessories, see page 3/110 and 3/113.
1) Coil operating range
at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us.
* You can order this quantity or a multiple thereof.
3/82
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3TH4 contactor relays, 8- and 10-pole
■ Overview
AC and DC operation
Terminal designations according to EN 50011
IEC 60947 and EN 60947 (VDE 0660)
In terms of their terminal designations, identification numbers
and identification letters, the 3TH42/3TH43 contactor relays
conform to the standard EN 50011 for "Specific Contactor
Relays".
The 3TH42/3TH43 contactor relays are suitable for use in any
climate. They are finger-safe according to EN 50274.
3
■ Selection and ordering data
3TH42 ..-0...
Contacts Rated operational current
Ie/AC-15/AC-14
at
Contacts
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
230/ 400/ 500 V 690/ Ident. No. Version
220 V 380 V
660 V acc. to
EN 50011
Number
A
A
A
A
NO
NC
NO
NC
kg
With screw terminals ¼ for screw and snap-on mounting onto
35 mm standard mounting rail
AC operation, rated control supply voltage Us = AC 50 Hz 230/220 V1)
8
10
6
4
2
80 E
71 E
62 E
53 E
8
7
6
5
-1
2
3
-----
-----
B
B
B
C
3TH42 80-0AP0
3TH42 71-0AP0
3TH42 62-0AP0
3TH42 53-0AP0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.422
0.420
0.420
0.420
44 E
44 E, U
4
3
4
3
-1
-1
B
B
3TH42 44-0AP0
3TH42 93-0AP0
1
1
1 unit
1 unit
101
101
0.419
0.425
DC operation · DC solenoid system, rated control supply voltage Us = 24 V DC
8
10
6
4
2
80 E
71 E
62 E
53 E
8
7
6
5
-1
2
3
-----
-----
B
B
B
B
3TH42 80-0BB4
3TH42 71-0BB4
3TH42 62-0BB4
3TH42 53-0BB4
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.664
0.663
0.673
0.662
44 E
44 E, U
4
3
4
3
-1
-1
B
B
3TH42 44-0BB4
3TH42 93-0BB4
1
1
1 unit
1 unit
101
101
0.660
0.667
For accessories, see page 3/139.
Spare parts
Magnetic coils:
AC operation: 3TY7 403-0A.
DC operation: 3TY4 803-0B.
(voltages on request)
Contacts:
The contacts cannot be replaced on 3TH42 contactor relays.
1) Operating range at 220 V: 0.85 to 1.1 x Us;
lower operating range limit according to IEC 60947.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/83
3RH, 3TH Contactor Relays
3TH4 contactor relays, 8- and 10-pole
3TH43 ..-0A..
3TH43 ..-0B..
3
Contacts Rated operational current
Ie/AC-15/AC-14
at
Contacts
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
230 V 400 V 500 V 690 V Ident. No. Version
acc. to
EN 50011
Number
A
A
A
A
NO
NC
NO
NC
kg
With screw terminals ¼ for screw and snap-on mounting onto
35 mm standard mounting rail
AC operation, rated control supply voltage Us = AC 50 Hz 230/220 V1)
10
6
10
4
2
100 E
91 E
82 E
73 E
73 E,U
10
9
8
7
6
-1
2
3
2
----1
----1
}
}
}
}
}
3TH43 10-0AP0
3TH43 91-0AP0
3TH43 82-0AP0
3TH43 73-0AP0
3TH43 46-0AP0
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.465
0.465
0.465
0.463
0.466
64 E
55 E
55 E,U
6
5
4
4
5
4
--1
--1
}
}
}
3TH43 64-0AP0
3TH43 55-0AP0
3TH43 94-0AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.462
0.463
0.465
DC operation · DC solenoid system, rated control supply voltage Us = 24 V DC
10
6
10
4
2
100 E
91 E
82 E
73 E
73 E U
10
9
8
7
6
-1
2
3
2
----1
----1
}
}
}
}
}
3TH43 10-0BB4
3TH43 91-0BB4
3TH43 82-0BB4
3TH43 73-0BB4
3TH43 46-0BB4
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.710
0.707
0.705
0.697
0.706
64 E
55 E
55 E U
6
5
4
4
5
4
--1
--1
}
}
}
3TH43 64-0BB4
3TH43 55-0BB4
3TH43 94-0BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.708
0.705
0.707
For accessories, see page 3/139.
Spare parts
Magnetic coils:
AC operation: 3TY7 403-0A.
DC operation: 3TY4 803-0B.
Contacts:
The contacts cannot be replaced on 3TH43 contactor relays.
1) Operating range at 220 V: 0.85 to 1.1 x Us;
lower operating range limit according to IEC 60947.
Contactor
Type
3TH42/3TH43
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
AC operation
DC operation
Coils for AC 50 Hz
Rated control supply Control supply
voltage Us
voltage at
V AC
50 Hz
V AC
60 Hz
24
36
42
Coils for AC 50 and 60 Hz
Rated control supply
voltage Us
Rated control supply
voltage Us
Option
V AC
50/60 Hz
Option
V DC
Option
29
42
50
B0
G0
D0
24
42
110
C2
D2
G2
12
24
30
A4
B4
C4
48
60
110
58
72
132
H0
E0
F0
115
120
220
J2
K2
N2
36
42
48
V4
D4
W4
125/127
230/220
240
150/152
276
288
L0
P01)
U0
230
240
440
L2
P2
R2
60
110
125
E4
F4
G4
400/380
415
500
480/460
500
600
V01)
R0
S0
220
230
240
M4
P4
Q4
100-110
200-220
G62)
N62)
120
240
K62)
P62)
For Japan
100
200
For USA and Canada
110
220
1) Operating range at 220 V or 380 V: 0.85 to 1.1 x Us.
2) Operating range at 60 Hz: 0.85 to 1.1 x Us.
* You can order this quantity or a multiple thereof.
3/84
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3TH2 contactor relays, 4- and 8-pole
■ Overview
AC and DC operation
IEC 60947 (VDE 0660).
The terminal designations comply with EN 50011.
3TH2 contactor relays
The 3TH2 contactor relays are suitable for use in any climate.
3
The contactor relays with screw terminals are finger-safe
according to EN 50274.
3TH27 latched auxiliary contactors
The contactor coil and the coil of the release solenoid are both
designed for continuous duty.
RC elements, varistors, diodes or diode assemblies can be fitted
to both coils from the front for damping opening surges in the
coil.
The contactor relay can also be switched on and released
manually.
Siemens LV 1 · 2006
3/85
3RH, 3TH Contactor Relays
3TH2 contactor relays, 4- and 8-pole
■ Selection and ordering data
Contacts Rated operational current Contacts
Ie/AC-15/AC-14
at
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
230/ 400/ 500 V 690/ Ident. No. Version
220 V 380 V
660 V acc. to
EN 50011
3
Number A
A
A
A
NO NC
kg
Contactor relays with screw terminals ¼
for screw and snap-on mounting onto 35 mm standard mounting rail
AC operation
4
3
2
-1
2
A
A
A
3TH20 40-0AP0
3TH20 31-0AP0
3TH20 22-0AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.194
0.193
0.193
4
3
2
-1
2
A
A
A
3TH20 40-0BB4
3TH20 31-0BB4
3TH20 22-0BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.214
0.215
0.216
For screw and snap-on mounting onto 35 mm standard mounting rail
3TH20 40-3AP0
4
4
3
2
-40 E
4
-B
3TH20 31-3AP0
31 E
3
1
B
22 E
2
2
B
3TH20 22-3AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.166
0.164
0.165
3TH20 40-7AP0
3TH20 31-7AP0
3TH20 22-7AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.161
0.162
0.162
For screw and snap-on mounting onto 35 mm standard mounting rail
4
4
3
2
-40 E
4
-B
3TH20 40-3BB4
3TH20 31-3BB4
31 E
3
1
B
22 E
2
2
B
3TH20 22-3BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.187
0.185
0.185
3TH20 40-7BB4
3TH20 31-7BB4
3TH20 31-7BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.183
0.183
0.183
4
4
3
2
1
40 E
31 E
22 E
DC operation · DC solenoid system
4
4
3
2
1
40 E
31 E
22 E
3TH20 ..-0A..
Contactor relays with 6.3 mm x 0.8 mm flat connectors
AC operation
for screw mounting (diagonal)
3TH20 ..-3...
4
4
3
2
--
40 E
31 E
22 E
4
3
2
-1
2
C
B
B
DC operation · DC solenoid system
for screw mounting (diagonal)
3TH20 ..-7...
4
4
3
2
--
40 E
31 E
22 E
4
3
2
-1
2
C
B
B
Contactor relays with solder pin connectors for printed circuit boards
AC operation
For screw mounting (diagonal)
4
4
3
2
--
40 E
31 E
22 E
4
3
2
-1
2
C
B
C
3TH20 40-6AP0
3TH20 31-6AP0
3TH20 22-6AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.162
0.162
0.162
4
3
2
-1
2
C
B
B
3TH20 40-6BB4
3TH20 31-6BB4
3TH20 22-6BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.184
0.185
0.187
DC operation · DC solenoid system
3TH20.. -6...
For screw mounting (diagonal)
4
4
3
2
--
40 E
31 E
22 E
Contactor relays with permanently mounted auxiliary switch blocks
with screw terminals, width 45 mm ¼
for screw and snap-on mounting onto 35 mm standard mounting rail
AC operation
8
3TH22.. -0A..
4
3
2
--
80 E
71 E
62 E
8
7
6
0
1
2
C
C
C
3TH22 80-0AP0
3TH22 71-0AP0
3TH22 62-0AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.234
0.233
0.235
53 E
44 E
5
4
3
4
C
C
3TH22 53-0AP0
3TH22 44-0AP0
1
1
1 unit
1 unit
101
101
0.234
0.234
80 E
71 E
62 E
8
7
6
0
1
2
C
C
C
3TH22 80-0BB4
3TH22 71-0BB4
3TH22 62-0BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.255
0.256
0.258
53 E
44 E
5
4
3
4
C
C
3TH22 53-0BB4
3TH22 44-0BB4
1
1
1 unit
1 unit
101
101
0.255
0.257
DC operation · DC solenoid system
8
4
3
2
--
For accessories, see page 3/140.
* You can order this quantity or a multiple thereof.
3/86
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3TH2 contactor relays, 4- and 8-pole
Contacts Rated operational current Contacts
Ie/AC-15/AC-14
at
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
230/ 400/ 500 V 690/ Ident. No. Version
220 V 380 V
660 V acc. to
EN 50011
Number
A
A
A
A
NO NC
kg
4
4
3
2
1
40 E
31 E
22 E
4
3
2
-1
2
C
B
B
3TH27 40-0AP0
3TH27 31-0AP0
3TH27 22-0AP0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.350
0.350
0.345
4
3
2
-1
2
B
B
B
3TH27 40-0BB4
3TH27 31-0BB4
3TH27 22-0BB4
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.396
0.401
0.399
DC operation · DC solenoid system
4
4
3
2
1
3TH27
40 E
31 E
22 E
For accessories, see page 3/140.
Contactor
Type
3TH20 ..-0...
Contactor
Type
Rated control supply voltages
(the 10th and 11th position of the order number must be changed)
AC operation
Rated control supply voltages
(the 10th and 11th position of the order number must be changed)
Coils for AC 50 and 60 Hz
Rated control supply voltage Us
Coils for AC 50 Hz
50 Hz
60 Hz
V AC
V AC
24
110
230/220
29
132
276
AC operation
Coils for AC 50 and 60 Hz
Rated control supply voltage Us
B0
F0
P01)
DC operation
Coils for AC 50 Hz
50 Hz
60 Hz
V AC
V AC
230/220
276
P01)
DC operation
Rated control supply voltage Us
Rated control supply voltage Us
V DC
24
110
220
3TH20 ..-3...,
3TH20 ..-6...,
3TH20 ..-7...,
3TH22, 3TH27
B4
F4
M4
V DC
24
B4
1) Operating range at 220 V or 380 V:
0.85 to 1.15 x Us; lower operating range limit according to IEC 60947.
Please inquire about further voltages.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/87
3
Latched contactor relays with screw terminals ¼
for screw and snap-on mounting onto 35 mm standard mounting rail
AC operation
3RH, 3TH Contactor Relays
3RH11 coupling relays for switching
auxiliary circuits, 4-pole
■ Application
The 3RH11 coupling relays for switching auxiliary circuits are
tailored to the special requirements of working with electronic
controls.
DC operation
IEC 60947 and EN 60947 (VDE 0660)
The 3RH11 coupling relays cannot be extended with auxiliary
switch blocks.
3
■ Selection and ordering data
DC operation
Screw terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
3RH11 ..-1.B40
Surge suppressors
Rated
operational
current Ie/
AC-15/AC-14 at
Auxiliary contacts
230 V
Ident. No. acc.
to EN 50011
DT
Version
NO
A
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
kg
NC
For screw and snap-on mounting onto
35 mm standard mounting rail
• Size S00
Terminal designations according to EN 50011
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 2.3 W at 24 V (no auxiliary switch blocks can be mounted)
Diode, varistor or RC
element attachable
6
40 E
31 E
22 E
4
3
2
-1
2
}
}
}
3RH11 40-1HB40
3RH11 31-1HB40
3RH11 22-1HB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.258
0.258
0.259
Built-in diode
6
40 E
31 E
22 E
4
3
2
-1
2
}
}
}
3RH11 40-1JB40
3RH11 31-1JB40
3RH11 22-1JB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.258
0.259
0.260
Built-in varistor
6
40 E
31 E
22 E
4
3
2
-1
2
}
}
}
3RH11 40-1KB40
3RH11 31-1KB40
3RH11 22-1KB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.259
0.259
0.259
Rated control supply voltage Us = 24 V DC, coil operating range 0.85 to 1.85 x Us
Power consumption of the coils 1.4 W at 24 V (no auxiliary switch blocks can be mounted)
Diode, varistor or
RC element attachable
6
40 E
31 E
22 E
4
3
2
-1
2
B
B
A
3RH11 40-1MB40-0KT0
3RH11 31-1MB40-0KT0
3RH11 22-1MB40-0KT0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.259
0.259
0.262
Built-in diode
6
40 E
31 E
22 E
4
3
2
-1
2
B
A
B
3RH11 40-1VB40
3RH11 31-1VB40
3RH11 22-1VB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.260
0.260
0.261
Built-in varistor
6
40 E
31 E
22 E
4
3
2
-1
2
B
A
A
3RH11 40-1WB40
3RH11 31-1WB40
3RH11 22-1WB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.260
0.260
0.261
For accessories, see page 3/110 and 3/113.
* You can order this quantity or a multiple thereof.
3/88
Siemens LV 1 · 2006
3RH, 3TH Contactor Relays
3RH11 coupling relays for switching
auxiliary circuits, 4-pole
3
DC operation
Cage Clamp terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
3RH11 ..-2.B40
Surge suppressors
Rated
Auxiliary contacts
operational
current Ie/
AC-15/AC-14 at
230 V
Ident. No. acc.
to EN 50011
DT
Version
NO
A
PU
PS*
(UNIT,
SET, M)
Cage Clamp terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
kg
NC
For screw and snap-on mounting onto
35 mm standard mounting rail
• Size S00
Terminal designations according to EN 50011
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 2.3 W at 24 V (no auxiliary switch blocks can be mounted)
Diode, varistor or
RC element attachable
6
40 E
31 E
22 E
4
3
2
-1
2
B
B
}
3RH11 40-2HB40
3RH11 31-2HB40
3RH11 22-2HB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.254
0.253
0.255
Built-in diode
6
40 E
31 E
22 E
4
3
2
-1
2
B
}
}
3RH11 40-2JB40
3RH11 31-2JB40
3RH11 22-2JB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.256
0.256
0.255
Built-in varistor
6
40 E
31 E
22 E
4
3
2
-1
2
}
}
}
3RH11 40-2KB40
3RH11 31-2KB40
3RH11 22-2KB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.256
0.254
0.255
Rated control supply voltage Us = 24 V DC, coil operating range 0.85 to 1.85 x Us
Power consumption of the coils 1.4 W at 24 V (no auxiliary switch blocks can be mounted)
Diode, varistor or
RC element attachable
6
40 E
31 E
22 E
4
3
2
-1
2
B
B
B
3RH11 40-2MB40-0KT0
3RH11 31-2MB40-0KT0
3RH11 22-2MB40-0KT0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.255
0.255
0.256
Built-in diode
6
40 E
31 E
22 E
4
3
2
-1
2
B
B
B
3RH11 40-2VB40
3RH11 31-2VB40
3RH11 22-2VB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.256
0.256
0.256
Built-in varistor
6
40 E
31 E
22 E
4
3
2
-1
2
B
B
B
3RH11 40-2WB40
3RH11 31-2WB40
3RH11 22-2WB40
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.255
0.256
0.255
For accessories, see page 3/110 and 3/113.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/89
3RT Coupling Relays
3RT10 coupling relays (interface),
for switching motors, 3-pole, 3 ... 11 kW
■ Application
The 3RT10 1 coupling relays cannot be extended with auxiliary
switch blocks.
DC operation
IEC 60947, EN 60947 (VDE 0660)
Two single-pole auxiliary switch blocks can be fitted to the
3RT10 2 coupling relays.
The 3RT10 coupling relays for switching motors are tailored to
the special requirements of working with electronic controls.
3
■ Selection and ordering data
DC operation
Screw terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
Surge
suppressors
Rated data
AC-2 and AC-3,
Tu: up to 60 °C
Operational
current Ie
up to
Rating of
induction
motors at
50 Hz and
400 V
400 V
A
kW
Auxiliary contacts
DT
Ident. Version
No.
NO
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
kg
NC
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S00
Terminal designations according to EN 50012
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 2.3 W at 24 V (no auxiliary switch blocks can be mounted)
3
10
1
-}
Diode, varistor 7
3RT10 15-1HB41
or RC element,
3RT10 15-1HB42
01
-1
}
attachable
1 unit
1 unit
101
101
0.259
0.258
7
3
10
01
1
--
-1
}
}
3RT10 15-1JB41
3RT10 15-1JB42
1
1
1 unit
1 unit
101
101
0.259
0.261
Built-in varistor 7
3
10
01
1
--
-1
}
}
3RT10 15-1KB41
3RT10 15-1KB42
1
1
1 unit
1 unit
101
101
0.261
0.259
Diode, varistor 9
or RC element,
attachable
4
10
01
1
--
-1
}
}
3RT10 16-1HB41
3RT10 16-1HB42
1
1
1 unit
1 unit
101
101
0.258
0.260
Built-in diode
9
4
10
01
1
--
-1
}
}
3RT10 16-1JB41
3RT10 16-1JB42
1
1
1 unit
1 unit
101
101
0.261
0.261
Built-in varistor 9
4
10
01
1
--
-1
}
}
3RT10 16-1KB41
3RT10 16-1KB42
1
1
1 unit
1 unit
101
101
0.260
0.260
Diode, varistor 12
or RC element,
attachable
5.5
10
01
1
--
-1
A
B
3RT10 17-1HB41
3RT10 17-1HB42
1
1
1 unit
1 unit
101
101
0.260
0.260
Built-in diode
12
5.5
10
01
1
--
-1
}
}
3RT10 17-1JB41
3RT10 17-1JB42
1
1
1 unit
1 unit
101
101
0.258
0.258
Built-in varistor 12
5.5
10
01
1
--
-1
}
}
3RT10 17-1KB41
3RT10 17-1KB42
1
1
1 unit
1 unit
101
101
0.261
0.261
Built-in diode
3RT10 1.-1HB4.
1
1
For accessories, see page 3/119.
* You can order this quantity or a multiple thereof.
3/90
Siemens LV 1 · 2006
3RT Coupling Relays
3RT10 coupling relays (interface),
for switching motors, 3-pole, 3 ... 11 kW
DC operation
Cage Clamp terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
Rated data
AC-2 and AC-3,
Tu: up to 60 °C
Auxiliary contacts
Operational
current Ie
up to
Rating of Ident. Version
induction No.
motors at
50 Hz and
400 V
400 V
A
kW
DT
PU
PS*
(UNIT,
SET, M)
Cage Clamp terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
3
Surge
suppressors
NO
NC
kg
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S00
Terminal designations according to EN 50012
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 2.3 W at 24 V (no auxiliary switch blocks can be mounted)
3RT10 15-2HB41
Diode, varistor 7
3
10
-1
}
or RC element,
3RT10 15-2HB42
01
1
-}
attachable
1 unit
1 unit
101
101
0.254
0.254
7
3
10
01
-1
1
--
}
}
3RT10 15-2JB41
3RT10 15-2JB42
1
1
1 unit
1 unit
101
101
0.255
0.255
Built-in varistor 7
3
10
01
-1
1
--
}
}
3RT10 15-2KB41
3RT10 15-2KB42
1
1
1 unit
1 unit
101
101
0.257
0.256
Diode, varistor 9
or RC element,
attachable
4
10
01
-1
1
--
B
B
3RT10 16-2HB41
3RT10 16-2HB42
1
1
1 unit
1 unit
101
101
0.254
0.256
Built-in diode
9
4
10
01
-1
1
--
}
}
3RT10 16-2JB41
3RT10 16-2JB42
1
1
1 unit
1 unit
101
101
0.256
0.256
Built-in varistor 9
4
10
01
-1
1
--
}
}
3RT10 16-2KB41
3RT10 16-2KB42
1
1
1 unit
1 unit
101
101
0.255
0.255
Diode, varistor 12
or RC element,
attachable
5.5
10
01
-1
1
--
B
B
3RT10 17-2HB41
3RT10 17-2HB42
1
1
1 unit
1 unit
101
101
0.257
0.253
Built-in diode
12
5.5
10
01
-1
1
--
}
}
3RT10 17-2JB41
3RT10 17-2JB42
1
1
1 unit
1 unit
101
101
0.255
0.256
Built-in varistor 12
5.5
10
01
-1
1
--
}
}
3RT10 17-2KB41
3RT10 17-2KB42
1
1
1 unit
1 unit
101
101
0.256
0.256
Built-in diode
3RT10 1.-2JB4
1
1
For accessories, see page 3/119.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/91
3RT Coupling Relays
3RT10 coupling relays (interface),
for switching motors, 3-pole, 3 ... 11 kW
DC operation
Screw terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
3
Surge
suppressors
Rated data
AC-2 and AC-3,
Tu: up to 60 °C
Operational
current Ie
up to
Rating of
induction
motors at
50 Hz and
400 V
400 V
A
kW
Auxiliary contacts
DT
Ident. Version
No.
NO
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
NC
kg
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S00
Terminal designations according to DIN 50012
Rated control supply voltage Us = 24 V DC, coil operating range 0.85 to 1.85 x Us
Power consumption of the coils 1.4 W at 24 V (no auxiliary switch blocks can be mounted)
3RT10 15-1MB41-0KT0
Diode, varistor 7
3
10
1
-B
or RC element,
3RT10 15-1MB42-0KT0
01
-1
B
attachable
1 unit
1 unit
101
101
0.260
0.260
7
3
10
01
1
--
-1
B
B
3RT10 15-1VB41
3RT10 15-1VB42
1
1
1 unit
1 unit
101
101
0.262
0.260
Built-in varistor 7
3
10
01
1
--
-1
A
B
3RT10 15-1WB41
3RT10 15-1WB42
1
1
1 unit
1 unit
101
101
0.260
0.260
Diode, varistor 9
or RC element,
attachable
4
10
01
1
--
-1
B
B
3RT10 16-1MB41-0KT0
3RT10 16-1MB42-0KT0
1
1
1 unit
1 unit
101
101
0.261
0.261
Built-in diode
9
4
10
01
1
--
-1
B
B
3RT10 16-1VB41
3RT10 16-1VB42
1
1
1 unit
1 unit
101
101
0.261
0.260
Built-in varistor 9
4
10
01
1
--
-1
B
B
3RT10 16-1WB41
3RT10 16-1WB42
1
1
1 unit
1 unit
101
101
0.260
0.260
Diode, varistor 12
or RC element,
attachable
5.5
10
01
1
--
-1
B
B
3RT10 17-1MB41-0KT0
3RT10 17-1MB42-0KT0
1
1
1 unit
1 unit
101
101
0.262
0.260
Built-in diode
12
5.5
10
01
1
--
-1
B
B
3RT10 17-1VB41
3RT10 17-1VB42
1
1
1 unit
1 unit
101
101
0.260
0.261
Built-in varistor 12
5.5
10
01
1
--
-1
B
B
3RT10 17-1WB41
3RT10 17-1WB42
1
1
1 unit
1 unit
101
101
0.261
0.260
Built-in diode
3RT10 1.-1VB4.
1
1
For accessories, see page 3/119.
* You can order this quantity or a multiple thereof.
3/92
Siemens LV 1 · 2006
3RT Coupling Relays
3RT10 coupling relays (interface),
for switching motors, 3-pole, 3 ... 11 kW
DC operation
Cage Clamp terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
Rated data
AC-2 and AC-3,
Tu: up to 60 °C
Auxiliary contacts
Operational
current Ie
up to
Rating of Ident. Version
induction No.
motors at
50 Hz and
400 V
400 V
A
kW
DT Cage Clamp terminals
Order No.
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
3
Surge
suppressors
NO
NC
kg
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S00
Terminal designations according to DIN 50012
Rated control supply voltage Us = 24 V DC, coil operating range 0.85 to 1.85 x Us
Power consumption of the coils 1.4 W at 24 V (no auxiliary switch blocks can be mounted)
Diode, varistor 7
3
10
1
-B 3RT10 15-2MB41-0KT0
or RC element,
01
-1
B 3RT10 15-2MB42-0KT0
attachable
1 unit
1 unit
101
101
0.255
0.257
7
3
10
01
1
--
-1
B
B
3RT10 15-2VB41
3RT10 15-2VB42
1
1
1 unit
1 unit
101
101
0.258
0.257
Built-in varistor 7
3
10
01
1
--
-1
B
B
3RT10 15-2WB41
3RT10 15-2WB42
1
1
1 unit
1 unit
101
101
0.257
0.258
Diode, varistor 9
or RC element,
attachable
4
10
01
1
--
-1
B
B
3RT10 16-2MB41-0KT0
3RT10 16-2MB42-0KT0
1
1
1 unit
1 unit
101
101
0.257
0.257
Built-in diode
9
4
10
01
1
--
-1
B
B
3RT10 16-2VB41
3RT10 16-2VB42
1
1
1 unit
1 unit
101
101
0.258
0.255
Built-in varistor 9
4
10
01
1
--
-1
B
B
3RT10 16-2WB41
3RT10 16-2WB42
1
1
1 unit
1 unit
101
101
0.255
0.257
Diode, varistor 12
or RC element,
attachable
5.5
10
01
1
--
-1
B
B
3RT10 17-2MB41-0KT0
3RT10 17-2MB42-0KT0
1
1
1 unit
1 unit
101
101
0.256
0.250
Built-in diode
12
5.5
10
01
1
--
-1
B
B
3RT10 17-2VB41
3RT10 17-2VB42
1
1
1 unit
1 unit
101
101
0.255
0.255
Built-in varistor 12
5.5
10
01
1
--
-1
B
B
3RT10 17-2WB41
3RT10 17-2WB42
1
1
1 unit
1 unit
101
101
0.256
0.257
Built-in diode
3RT10 1.-2WB4.
1
1
For accessories, see page 3/119.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/93
3RT Coupling Relays
3RT10 coupling relays (interface),
for switching motors, 3-pole, 3 ... 11 kW
DC operation
Screw terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
3
Surge
Rated data
suppressors AC-2 and AC-3,
Tu: up to 60 °C
Operational
current Ie
up to
Rating of
induction
motors at
50 Hz and
400 V
400 V
A
kW
Auxiliary contacts
DT
Ident. Version
No.
NO
PU
(UNIT,
SET, M)
Screw terminals
Order No.
PS*
PG
Weight
per PU
approx.
Price
per PU
NC
kg
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S0
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 4.2 W at 24 V (2 single-pole auxiliary switch blocks can be mounted)
3RT10 24-1KB40
Varistor
12
5.5
---}
mounted
3RT10 25-1KB40
17
7.5
---}
3RT10 26-1KB40
25
11
---}
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.576
0.577
0.582
3RT10 2.-1KB40
For accessories, see page 3/112.
DC operation
Cage Clamp terminals
Low power consumption
Extended operating range of the coils
Integrated coil circuit
Surge
Rated data
suppressors AC-2 and AC-3,
Tu: up to 60 °C
Operational
current Ie
up to
Rating of
induction
motors at
50 Hz and
400 V
400 V
A
kW
Auxiliary contacts
Ident. Version
No.
NO
DT
Cage Clamp terminals
Order No.
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
NC
For screw and snap-on mounting onto 35 mm standard mounting rail
Size S0
Rated control supply voltage Us = 24 V DC, coil operating range 0.7 to 1.25 x Us
Power consumption of the coils 4.2 W at 24 V (2 single-pole auxiliary switch blocks can be mounted)
3RT10 24-3KB40
1
Varistor
12
5.5
---B
mounted
17
7.5
---}
3RT10 25-3KB40
1
3RT10 26-3KB40
1
25
11
---}
1 unit
1 unit
1 unit
101
101
101
0.578
0.580
0.581
3RT10 2.-3KB40
For accessories, see page 3/112.
* You can order this quantity or a multiple thereof.
3/94
Siemens LV 1 · 2006
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Relay couplers
■ Application
The input and output coupling links differ with regard to the
positioning of the terminals and the LEDs. For equipment
identification purposes, each coupling link has a blank legend
plate.
AC and DC operation
DIN VDE 0110 Part 1, DIN VDE 0435, DIN VDE 0660 and
EN 50005
In the coupling links in double-decker format, the connections
are arranged on two levels; the units are extremely compact.
Connection method: Screw terminals or spring-loaded
terminals. For test purposes, versions are available with manual
0 automatic switches.
3
In accordance with the technical specifications of electronic
systems, the coupling elements have a lower power
consumption.
■ Selection and ordering data
AC and DC operation · for snap-on mounting onto 35 mm standard mounting rail
Rated control supply
voltage Us
Contacts
Version
Width
DT
Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
AC 50/60 Hz
V
NO
CO
mm
kg
3TX7 002 relay coupling links with screw terminals
Output coupling links
24
1
11)
---
11.5
}
}
3TX7 002-1AB00
3TX7 002-1AB02
1
1
1 unit
1 unit
101
101
0.033
0.032
24
230
--
1
17.5
}
}
3TX7 002-1BB00
3TX7 002-1BF00
1
1
1 unit
1 unit
101
101
0.041
0.042
24
22)
--
-21) 2)
22.5
}
}
3TX7 002-1CB00
3TX7 002-1FB02
1
1
1 unit
1 unit
101
101
0.055
0.055
24
110
1
--
11.5
}
}
3TX7 002-2AB00
3TX7 002-2AE00
1
1
1 unit
1 unit
101
101
0.032
0.032
2302)
1
--
11.5
}
}
3TX7 002-2AF00
3TX7 002-2AF05
1
1
1 unit
1 unit
101
101
0.033
0.039
17.5
}
3TX7 002-2BF02
1
1 unit
101
0.043
Input coupling links
3TX7 002-1....
230
--
1
1) 3)
3TX7 002-2....
3TX7 003 relay coupling links with spring-loaded terminals
Output coupling links
24
1
--
11.5
}
3TX7 003-1AB00
1
1 unit
101
0.030
24
--
1
17.5
}
3TX7 003-1BB00
1
1 unit
101
0.039
24
22)
--
22.5
}
3TX7 003-1CB00
1
1 unit
101
0.050
Input coupling links
230
1
--
11.5
A
3TX7 003-2AF00
1
1 unit
101
0.031
3TX7 003
Note:
For coil voltages which are not listed, see SITOP power DC Power Supplies, e.g. 6EP1 331-2BA10 and 6EP1 731-2BA00, in "Power Supplies".
1) Hard gold-plated contacts.
2) The same potential must be applied to the output contacts of the
2 NO/2 CO relays.
3) Observe max. permissible conductor length, see Technical
Specifications.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/95
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Relay couplers
Rated control supply Contacts
voltage Us
Version
Manual-0- Width
automatic
switch for
testing
purposes
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
AC 50/60 Hz
V
NO
CO
mm
kg
3TX7 004 relay couplers with screw terminals
3
Output coupling links
3TX7 004-1LB0.
24
230
----
1
1
1
without
without
without
24
--
12)
without
24
230
1
1
---
without
without
24
--
1
with
12)
12)
12)
----
without
without
without
6.2
}
6.2
}
12.51) }
3TX7 004-1LB00
3TX7 004-1LF00
3TX7 004-1BF05
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.033
0.034
0.057
6.2
}
3TX7 004-1LB02
1
1 unit
101
0.033
6.2
6.2
}
}
3TX7 004-1MB00
3TX7 004-1MF00
1
1
1 unit
1 unit
101
101
0.037
0.037
12.5
}
3TX7 004-1BB10
1
1 unit
101
0.052
6.2
6.2
6.2
}
}
}
3TX7 004-2MB02
3TX7 004-2ME02
3TX7 004-2MF02
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.037
0.037
0.038
6.2
6.2
}
}
3TX7 005-1LB00
3TX7 005-1LF00
1
1
1 unit
1 unit
101
101
0.028
0.030
Input coupling links
24
110
230
3TX7 005 relay couplers with spring-loaded terminals
Output coupling links
24
230
---
1
1
without
without
24
--
12)
without
6.2
}
3TX7 005-1LB02
1
1 unit
101
0.028
24
230
1
1
---
without
without
6.2
6.2
}
}
3TX7 005-1MB00
3TX7 005-1MF00
1
1
1 unit
1 unit
101
101
0.034
0.034
12)
12)
---
without
without
6.2
6.2
C
B
3TX7 005-2MB02
3TX7 005-2MF02
1
1
1 unit
1 unit
101
101
0.034
0.034
Input coupling links
24
230
3TX7 005-2MB02
Note:
For replacement products, see 3RS18 coupling links with industrial housing or other 3TX7 0 products.
For coil voltages which are not listed, see SITOP power DC Power Supplies, e.g. 6EP1 331-2BA10 and 6EP1 731-2BA00, in "Transformers and Power Supplies".
1) For long conductors.
2) Hard gold-plated contacts.
■ Accessories
For coupling link
Version
DT
Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Type
kg
Connecting combs
3TX7 004
24 terminals, blue
Width 6.2 mm
}
3TX7 004-8AA00
1
1 unit
101
0.017
3TX7 002, 3TX7 003,
3TX7 004, 3TX7 005
24 terminals with
supply, blue
A
3TX7 004-8BA00
1
1 unit
101
0.050
Connecting leads
* You can order this quantity or a multiple thereof.
3/96
Siemens LV 1 · 2006
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Relay couplers with plug-in design
• Device variants with hard gold-plated contacts, hence high
contact reliability
• 24 V DC version also available as variant with NO contact
• Integrated reverse polarity protection and EMC arcsuppression diode
• Clearly visible functional state of the relay coupler by yellow
LED
• Safe isolation according to EN 50178
• 230 V AC/DC versions available
Advantages
• Plug-in relay with spring-loaded terminals and 6.2 mm width
• Fast exchange with permanent wiring (plug-in relay)
• The wire inlet and terminals can be reached from the front.
This results in faster wiring time and wiring errors are
prevented.
• Tested complete units “ short mounting time
• Single relays available as components
• Linking of supply voltage and control signals with 16-pole
connecting comb
• Galvanic isolation plate for isolating different voltages for
neighboring units
■ Selection and ordering data
Rated control supply voltage Us
Contacts
DT
Order No.
Version
V
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
NO
CO
kg
24 DC
24 DC
1
--
-1
A
A
3TX7 014-1AM00
3TX7 014-1BM00
1
1
5 units
5 units
101
101
0.035
0.035
24 AC/DC
115 AC/DC
230 AC/DC
----
1
1
1
A
A
A
3TX7 014-1BB00
3TX7 014-1BE00
3TX7 014-1BF00
1
1
1
5 units
5 units
5 units
101
101
101
0.035
0.045
0.041
Plug-in relays with screw terminals, 6.2 mm,
complete with relay
3TX7 014-1AM00
Plug-in relays with screw terminals, 6.2 mm,
complete with relay and hard gold-plating1)
24 DC
--
1
A
3TX7 014-1BM02
1
5 units
101
0.035
24 AC/DC
115 AC/DC
230 AC/DC
----
1
1
1
A
A
A
3TX7 014-1BB02
3TX7 014-1BE02
3TX7 014-1BF02
1
1
1
5 units
5 units
5 units
101
101
101
0.035
0.041
0.035
Plug-in relays with spring-loaded terminals, 6.2 mm,
complete with relay
24 DC
24 DC
1
--
-1
A
A
3TX7 015-1AM00
3TX7 015-1BM00
1
1
5 units
5 units
101
101
0.045
0.045
24 AC/DC
115 AC/DC
230 AC/DC
----
1
1
1
A
A
A
3TX7 015-1BB00
3TX7 015-1BE00
3TX7 015-1BF00
1
1
1
5 units
5 units
5 units
101
101
101
0.045
0.045
0.045
Plug-in relays with spring-loaded terminals, 6.2 mm,
complete with relay and hard gold-plating1)
24 DC
--
1
A
3TX7 015-1BM02
1
5 units
101
0.045
24 AC/DC
115 AC/DC
230 AC/DC
----
1
1
1
A
A
A
3TX7 015-1BB02
3TX7 015-1BE02
3TX7 015-1BF02
1
1
1
5 units
5 units
5 units
101
101
101
0.040
0.045
0.045
1) The variants with hard gold-plated contacts feature high contact reliability
(also for low currents) and are therefore especially suitable for steadystate inputs of programmable logic controllers.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/97
3
■ Benefits
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Relay couplers with plug-in design
Rated control Used for
supply
voltage Us
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
V
kg
3
Individual relay modules1), 6.2 mm, 1 changeover contact
12 DC
Complete units 24 V AC/DC A
Complete units, 24 V AC/DC, A
hard gold-plated
3TX7 014-7BQ00
3TX7 014-7BQ02
1 20 units
1 20 units
101
101
0.035
0.035
24 DC
Complete units 24 V DC
Complete units 24 V DC,
hard gold-plated
A
A
3TX7 014-7BM00
3TX7 014-7BM02
1 20 units
1 20 units
101
101
0.035
0.035
60 DC
Complete units 115 V and
230 V AC/DC
Complete units 115 V and
230 V AC/DC,
hard gold-plated
A
3TX7 014-7BP00
1 20 units
101
0.035
A
3TX7 014-7BP02
1 20 units
101
0.035
A
for linking the same potentials,
16-pole,
current carrying capacity for infeed max. 6 A
3TX7 014-7AA00
1
5 units
101
0.035
3TX7 014 and 3TX7 015
3TX7 014-7CE00
1 10 units
101
0.035
Connecting combs 16-pole, blue
Galvanic isolation plates
A
1) The variants with hard gold-plated contacts feature high contact reliability
(also for low currents) and are therefore especially suitable for steadystate inputs of programmable logic controllers.
2 4 V
Complete device
L Y A A 0 2 4 Y
D C
Single device
A P E 3 0 0 2 4
S P U L E :2 4 V
V 2 3 0 9 2 -A 1 0 2 4 -A 3 0 1
2 4 V
NO (13/14)
3TX7 014-..
3TX7 015-..
(+)A1/(-)A2
CO (11/12/14)
3TX7 014-..
FTR-LY..
APE..
V23092-..
..1AM001)
24 V DC
NO
..7BM001)
..CA024Y
..30024
..A1024-A301
1)
..A1024-A301
1)
24 V DC
CO
..7BM00
..CA024Y
..30024
..1BB001)
24 V AC/DC
CO
..7BQ001)
..CA012Y
..30012
..A1012-A301
..1BE001)
115 V AC/DC
CO
..7BP001)
--
..30060
..A1060-A301
..1BF001)
230 V AC/DC
CO
..7BP001)
--
..30060
..A1060-A301
..1BM022)
24 V DC
CO
..7BM022)
..CA024V
..30124
..A1024-A201
2)
..1BM00
2)
..1BB02
24 V AC/DC
CO
..7BQ02
..CA012V
..30112
..A1012-A201
..1BE022)
115 V AC/DC
CO
..7BP022)
--
..30160
..A1060-A201
..1BF022)
230 V AC/DC
CO
..7BP022)
--
..30160
..A1060-A201
1)
2)
NSB0_01617
F &T
NSB0_01616
Versions to be supplied
NSB0_01615
Selective help to assign relay single modules
= AgSn0
= AgSn0+Au
* You can order this quantity or a multiple thereof.
3/98
Siemens LV 1 · 2006
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Semiconductor couplers
■ Overview
The input and output coupling links differ with regard to the
positioning of the terminals and the LEDs. For equipment
identification purposes, each coupling link has a blank legend
plate.
DIN VDE 0110 Part 1, DIN VDE 0435, DIN VDE 0660 and
EN 50005 optocouplers: DIN VDE 0884, DIN VDE 0411
Part 500, IEC 61131-2 (programmable logic controllers).
In the coupling links in double-decker format, the connections
are arranged on two levels; the units are extremely compact.
Connection method: Screw terminals or spring-loaded
terminals. For test purposes, versions are available with manual
0 automatic switches.
In accordance with the technical specifications of electronic
systems, the coupling elements have a lower power
consumption.
3
AC and DC operation
■ Selection and ordering data
AC and DC operation · for snap-on mounting onto 35 mm standard mounting rail
Rated control supply
voltage Us
Contacts
AC 50/60 Hz
Version
Switching Width DT
current
V
A
Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
mm
kg
3TX7 002 semiconductor couplers with screw terminals
Output coupling links
1 transistor
1 transistor
1.8
1.5
12.5
11.5
}
}
3TX7 002-3AB00
3TX7 002-3AB01
1
1
1 unit
1 unit
101
101
0.033
0.035
24 AC/DC
110 … 240 AC
1 transistor
1 transistor
0.1
0.1
12.5
12.5
}
}
3TX7 002-4AB00
3TX7 002-4AG00
1
1
1 unit
1 unit
101
101
0.031
0.035
Rated control supply
voltage Us
Switching
voltage
Switching Manual-0current
automatic
switch for
testing
purposes
Width DT
V
A
mm
24 DC
Input coupling links
3TX7 002
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
AC 50/60 Hz
V
kg
3TX7 004 semiconductor couplers with screw terminals
Output coupling links
3TX7 004-3AB04
24 DC
ˆ 48 V DC 0.5
24 DC
ˆ 30 V DC 1.5
24 DC
ˆ 30 V DC 3
110 ... 230 AC/DC
ˆ 30 V DC 3
24 DC
ˆ 30 V DC 5
24 DC
ˆ 30 V DC 5
with
24 DC
24 ...
250 V AC
without
12.5
without
2
without
without
without
}
3TX7 004-3AB04
1 1 unit
101
0.034
}
3TX7 004-3PB54
1 1 unit
101
0.029
}
3TX7 004-3PB74
1 1 unit
101
0.032
}
3TX7 004-3PG74
1 1 unit
101
0.033
}
3TX7 004-3AC04
1 1 unit
101
0.052
B
3TX7 004-3AC14
1 1 unit
101
0.061
}
3TX7 004-3AC03
1 1 unit
101
0.060
6.2
}
3TX7 004-4PG24
1 1 unit
101
0.034
6.2
6.2
12.5
Input coupling links
AC/DC 110 ... 230
ˆ 30 V DC 0.1
3TX7 005 semiconductor couplers with spring-loaded terminals
Output coupling links
24 DC
24 DC
ˆ 48 V DC 0.5
ˆ 30 V DC 1.5
without
6.2
}
}
3TX7 005-3AB04
3TX7 005-3PB54
1 1 unit
1 1 unit
101
101
0.031
0.025
24 DC
110 ... 230 AC/DC
ˆ 30 V DC 3
without
6.2
A
A
3TX7 005-3PB74
3TX7 005-3PG74
1 1 unit
1 1 unit
101
101
0.027
0.027
24 DC
24 DC
ˆ 30 V DC 5
without
with
12.5
}
C
3TX7 005-3AC04
3TX7 005-3AC14
1 1 unit
1 1 unit
101
101
0.047
0.051
24 DC
24 ...
250 V AC
without
12.5
C
3TX7 005-3AC03
1 1 unit
101
0.056
without
6.2
}
3TX7 005-4PG24
1 1 unit
101
0.031
2
Input coupling links
110 ... 230 AC/DC
ˆ 30 V DC 0.1
Note:
For replacement products, see 3RS18 coupling links with industrial housing or other 3TX7 0 products.
For coil voltages which are not listed, see SITOP power DC Power Supplies, e.g. 6EP1 331-2BA10 and 6EP1 731-2BA00, in "Power Supplies".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/99
3TX7, 3RS18 Coupling Relays
3TX7 Coupling Relays, Narrow Design
Semiconductor couplers
■ Accessories
For coupling link
Version
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Type
Weight
per PU
approx.
kg
3
Connecting combs
3TX7 004
24 terminals, blue
Width 6.2 mm
}
3TX7 004-8AA00
1
1 unit
101
0.017
3TX7 002, 3TX7 003,
3TX7 004, 3TX7 005
24 terminals with supply, blue
A
3TX7 004-8BA00
1
1 unit
101
0.050
Connecting leads
* You can order this quantity or a multiple thereof.
3/100
Siemens LV 1 · 2006
3TX7, 3RS18 Coupling Relays
3RS18 Coupling Relays with Industrial Housing
Relay couplers
■ Overview
■ Benefits
• Wide-range voltage: One product for all voltages
• The industrial housing supports the same connection
methods as the timing relay including spring-loaded
terminals, 2 wires can be clamped
• Versions with electronically optimized outputs (hard goldplated)
• Up to 3 changeover contacts with 22.5 mm width
The new 3RS18 coupling relays are couplers in the well-proven
standard 22.5 mm timing relay housing. The series comprises
relays with 1, 2 and 3 changeover contacts with screw and
spring-loaded terminals for combined voltages and wide
voltage ranges.
The relay coils are protected internally with suppression diodes.
3
■ Selection and ordering data
Rated control supply voltage Contacts
Us
Version
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
AC 50/60 Hz
V
CO
kg
Coupling relays with industrial housing with screw terminals,
22.5 mm
Wide-range voltage
24 ... 240 AC/DC
2
3
31)
A
C
C
3RS18 00-1BW00
3RS18 00-1HW00
3RS18 00-1HW01
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.143
0.168
0.168
24 AC/DC and
110 ... 120 AC
1
2
3
31)
C
C
C
C
3RS18 00-1AQ00
3RS18 00-1BQ00
3RS18 00-1HQ00
3RS18 00-1HQ01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.116
0.142
0.173
0.173
24 AC/DC and
220 ... 240 AC
1
2
3
31)
C
C
C
C
3RS18 00-1AP00
3RS18 00-1BP00
3RS18 00-1HP00
3RS18 00-1HP01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.112
0.142
0.166
0.170
2
3
31)
C
C
C
3RS18 00-2BW00
3RS18 00-2HW00
3RS18 00-2HW01
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.128
0.144
0.145
24 AC/DC and
10 ... 120 AC
1
2
3
31)
C
C
C
C
3RS18 00-2AQ00
3RS18 00-2BQ00
3RS18 00-2HQ00
3RS18 00-2HQ01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.104
0.120
0.147
0.147
24 AC/DC and
20 ... 240 AC
1
2
3
31)
C
C
C
C
3RS18 00-2AP00
3RS18 00-2BP00
3RS18 00-2HP00
3RS18 00-2HP01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.104
0.122
0.143
0.147
Combination voltage
Coupling relays with industrial housing with spring-loaded
terminals, 22.5 mm
Wide-range voltage
24 ... 240 AC/DC
Combination voltage
1) Hard gold-plated contacts.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/101
LZX Plug-in Relays
Relay couplers
Version
Rated control
supply voltage
Us
Contacts Width
Version
V
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
mm
kg
3
Complete units, 11- and 14-pole, PT series
LZX:PT3A5L24
Complete units with
socket
For snap-on mounting
onto 35 mm standard
mounting rail
Consisting of:
Plug-in relay, socket,
LED module (24-V-DCLED module with
freewheel diode,
AC without freewheel
diode), fixing/ejection
bracket and label
Complete units with
socket (logical
isolation)
For snap-on mounting
onto 35 mm standard
mounting rail
Consisting of:
Plug-in relay, socket with
logical isolation, LED
module (24-V-DC-LED
module with freewheel
diode, AC without
freewheel diode),
fixing/ejection bracket
and label
24 DC
24 AC
115 AC
230 AC
24 DC
24 AC
115 AC
115 AC
230 AC
3
4
3
4
27
C
C
C
C
LZX:PT3A5L24
LZX:PT5A5L24
LZX:PT3A5R24
LZX:PT5A5R24
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.099
0.099
0.099
0.100
3
4
3
4
27
C
C
C
C
LZX:PT3A5S15
LZX:PT5A5S15
LZX:PT3A5T30
LZX:PT5A5T30
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.099
0.099
0.099
0.099
3
4
4
3
27
C
C
C
C
LZX:PT3B5L24
LZX:PT5B5L24
LZX:PT5B5R24
LZX:PT3B5S15
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.106
0.112
0.112
0.105
4
3
4
27
C
C
C
LZX:PT5B5S15
LZX:PT3B5T30
LZX:PT5B5T30
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.112
0.106
0.112
1
2
1
2
15.5
}
}
C
C
LZX:RT3A4L24
LZX:RT4A4L24
LZX:RT3A4R24
LZX:RT4A4R24
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.061
0.061
0.060
0.060
1
2
1
2
15.5
C
C
A
}
LZX:RT3A4S15
LZX:RT4A4S15
LZX:RT3A4T30
LZX:RT4A4T30
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.060
0.060
0.060
0.060
1
2
1
2
15.5
C
A
C
C
LZX:RT3B4L24
LZX:RT4B4L24
LZX:RT3B4R24
LZX:RT4B4R24
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.065
0.065
0.064
0.064
1
2
1
2
15.5
C
C
C
C
LZX:RT3B4S15
LZX:RT4B4S15
LZX:RT3B4T30
LZX:RT4B4T30
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.064
0.065
0.064
0.064
1
15.5
C
LZX:RY1A4L24
1
1 unit
101
0.048
C
C
LZX:RY213024
LZX:RY78626
1
1
1 unit
1 unit
101
101
0.009
0.035
}
LZX:RPML0024
1
1 unit
101
0.003
C
LZX:RY16016
100 10 units
101
0.100
Complete units, 8-pole, 5 mm pinning, RT series
Complete units with
socket
For snap-on mounting
onto 35 mm standard
mounting rail
Consisting of:
Print relay, standard
socket, LED module (24V-LED-DC with
freewheel diode, AC
without freewheel
diode), fixing/ejection
bracket and label
LZX:RT4B4AT30
Complete units with
socket (logical
isolation)
For snap-on mounting
onto 35 mm standard
mounting rail
Consisting of:
Print relay with safe
isolation, socket with
logical isolation, LED
module (24-V-DC-LED
module with freewheel
diode, AC without
freewheel diode),
fixing/ejection bracket
and label
24 DC
24 AC
115 AC
230 AC
24 DC
24 AC
115 AC
230 AC
Complete units, 5-pole, 3.2 mm pinning, RY series
LZX:RY1A4L24
Complete units with
socket (logical
isolation)
For snap-on mounting
onto 35 mm standard
mounting rail
Consisting of:
Print relays
Sockets with
logical isolation
LED modules
(24-V-DC-LED module
with freewheel diode)
Fixing/ejection
brackets and label
24 DC
Note:
Logical isolation: The terminals for the contacts and the terminals for the coil are arranged on separate levels, e.g. above for contacts and below for coil.
Logical isolation is not necessarily safe isolation (see the technical specifications of the relay types).
Safe isolation: Safe isolation prevents voltage of one circuit affecting another circuit with sufficient protection (DIN VDE 106 Part 101).
* You can order this quantity or a multiple thereof.
3/102
Siemens LV 1 · 2006
LZX Plug-in Relays
Relay couplers
Version
Rated control supply
voltage Us
Contacts Width
Version
V
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
mm
Print relays
24 DC
• With hard gold-plating 24 AC
230 AC
1
1
1
12.7
12.7
12.7
C
C
C
LZX:RT315024
LZX:RT315524
LZX:RT315730
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.016
0.013
0.015
24 DC
24 DC
24 AC
24 AC
1
2
1
2
12.7
12.7
12.7
12.7
}
}
C
}
LZX:RT314024
LZX:RT424024
LZX:RT314524
LZX:RT424524
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.016
0.015
0.007
0.014
115 AC
115 AC
230 AC
230 AC
1
2
1
2
12.7
12.7
12.7
12.7
C
}
}
}
LZX:RT314615
LZX:RT424615
LZX:RT314730
LZX:RT424730
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.013
0.012
0.007
0.010
--
--
15.5
}
LZX:RT78625
1
1 unit
101
0.042
-Sockets
with logical isolation, for
mounting onto
standard mounting rail
--
15.5
}
LZX:RT78626
1
1 unit
101
0.047
--
15.5
Print relays
LZX:RT314024
Standard sockets for
mounting onto
standard mounting rail
LZX:RT78625
LZX:RT78626
Accessories for RT
LED modules
• Red
with freewheel diode
LZX:RPML0024
24 DC
without freewheel diode 24 AC/DC
110 ... 230 AC/DC
---
}
LZX:RPML0024
1
1 unit
101
0.003
}
}
LZX:RPML0524
LZX:RPML0730
1
1
1 unit
1 unit
101
101
0.003
0.003
• Green
with freewheel diode
LZX:RY16016
24 DC
without freewheel diode 24 AC/DC
110 ... 230 AC/DC
}
LZX:RPMG0024
1
1 unit
101
0.003
---
C
}
LZX:RPMG0524
LZX:RPMG0730
1
1
1 unit
1 unit
101
101
0.003
0.003
--
C
LZX:RY16016
100 10 units
101
0.100
100 20 units
--
15.5
Fixing/ejection
brackets
--
Labels
--
--
15.5
}
LZX:PT16040
101
0.100
RC elements
24 ... 48 AC
110 ... 230 AC
--
15.5
C
}
LZX:RPMU0548
LZX:RPMU0730
1
1
1 unit
1 unit
101
101
0.004
0.003
Freewheel diodes
with connection to A1
6 ... 230 DC
--
15.5
}
LZX:RPMT00A0
1
1 unit
101
0.002
LZX:RY16040
Print relays, 5-pole, RY series
Individual modules for customer assembly
LZX:RY78626
24 DC
Print relays
Label on relay:
RY213024, RY613024 or
JS24N-K
1
10.7
C
LZX:RY213024
1
1 unit
101
0.009
-Sockets
with logical isolation, for
mounting onto
standard mounting rail
--
15.5
C
LZX:RY78626
1
1 unit
101
0.035
--
--
C
LZX:RY16016
100 10 units
101
0.100
Fixing/ejection
brackets
Note
For coil voltages which are not listed, see SITOP power DC Power Supplies, e.g. 6EP1 331-2BA10 and 6EP1 731-2BA00, in "Power Supplies".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/103
3
Print relays, 8- and 11-pole, 5 mm pinning, RT series
Individual modules for customer assembly
LZX Plug-in Relays
Relay couplers
Version
Rated control supply
voltage Us
Contacts Width DT Order No.
Version
V
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
mm
Industrial relays, 8-, 11-, and 14-pole, PT series
Individual modules for customer assembly
3
Mini industrial relays
LZX:PT570024
LZX:PT78702
2
3
4
22.5
}
}
}
LZX:PT270024
LZX:PT370024
LZX:PT570024
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.030
0.031
0.031
2
3
4
22.5
C
A
}
LZX:PT270524
LZX:PT370524
LZX:PT570524
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.030
0.031
0.031
115 AC
2
3
4
22.5
C
A
}
LZX:PT270615
LZX:PT370615
LZX:PT570615
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.028
0.030
0.030
230 AC
2
3
4
22.5
}
}
}
LZX:PT270730
LZX:PT370730
LZX:PT570730
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.029
0.030
0.030
• With hard goldplating
24 DC
230 AC
4
22.5
}
}
LZX:PT580024
LZX:PT580730
1 1 unit
1 1 unit
101
101
0.031
0.031
• Without test bracket
24 DC
24 AC
230 AC
4
22.5
C
C
C
LZX:PT520024
LZX:PT520524
LZX:PT520730
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.031
0.032
0.031
--
27
}
}
}
LZX:PT78702
LZX:PT78703
LZX:PT78704
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.051
0.062
0.063
--
12.5
• With test bracket and 24 DC
mechanical contact
position indicator,
without LED1)
24 AC
Sockets for mounting -onto standard
mounting rail
Accessories for PT
LED modules
• Red
LZX:RPML0024
with freewheel diode
24 DC
without freewheel
diode
24 AC/DC
110 … 230 AC/DC
}
LZX:RPML0024
1 1 unit
101
0.003
}
}
LZX:RPML0524
LZX:RPML0730
1 1 unit
1 1 unit
101
101
0.003
0.003
• Green
LZX:PT16016
LZX:PT16040
}
LZX:RPMG0024
1 1 unit
101
0.003
C
}
LZX:RPMG0524
LZX:RPMG0730
1 1 unit
1 1 unit
101
101
0.003
0.003
26
}
LZX:PT16016
100 10 units
101
0.100
--
26
}
LZX:PT16040
100 10 units
101
0.100
--
26
C
}
LZX:RPMU0548
LZX:RPMU0730
1 1 unit
1 1 unit
101
101
0.004
0.003
26
}
LZX:RPMT00A0
1 1 unit
101
0.002
C
C
C
LZX:PT78802
LZX:PT78803
LZX:PT78804
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.063
0.070
0.075
C
C
LZX:PT78602
LZX:PT78604
1 1 unit
1 1 unit
101
101
0.043
0.051
with freewheel diode
24 DC
without freewheel
diode
24 AC
110 … 230 AC/DC
Fixing/ejection
brackets
--
Labels
--
RC elements
24 ... 48 AC
110 … 230 AC
--
Freewheel diodes
6 … 230 DC
with connection to A1
--
--
12.5
for PT relays2)
Logical sockets
with logical arrangement of the contacts
2 CO contacts
3 CO contacts
4 CO contacts
LZX:PT78802
Sockets with top slide, pinning 3.5 mm
2 different conductor cross-sections can be connected,
without LEDs
2 CO contacts
4 CO contacts
LZX:PT78604
1) The test bracket is designed to be non-latching. If the test bracket is
pressed further until 90° has been reached, two small lugs break off and
the test bracket can be latched in position.
2) Accessories for LZX:RPM LED modules and LZX:PT16016 fixing/ejection
brackets cannot be used with these sockets.
* You can order this quantity or a multiple thereof.
3/104
Siemens LV 1 · 2006
LZX Plug-in Relays
Relay couplers
Version
Rated control supply
voltage Us
Contacts Width DT Order No.
Version
V
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
mm
Industrial relays, 11-pole, MT series
Individual modules for customer assembly
LZX:MT326024
without LED
with LED
24 DC
3
35.5
A
}
LZX:MT321024
LZX:MT323024
1 1 unit
1 1 unit
101
101
0.088
0.088
without LED
with LED
24 AC
3
35.5
A
C
LZX:MT326024
LZX:MT328024
1 1 unit
1 1 unit
101
101
0.089
0.089
without LED
with LED
115 AC
3
35.5
C
C
LZX:MT326115
LZX:MT328115
1 1 unit
1 1 unit
101
101
0.087
0.088
without LED
with LED
230 AC
3
35.5
A
A
LZX:MT326230
LZX:MT328230
1 1 unit
1 1 unit
101
101
0.089
0.089
Sockets for mounting -onto standard
mounting rail
--
38
}
LZX:MT78750
1 1 unit
101
0.063
--
--
}
LZX:MT28800
1 1 unit
101
0.001
LZX:MT78750
Fixing brackets
Note:
For coil voltages which are not listed, see SITOP power DC Power Supplies, e.g. 6EP1 331-2AB10 and 6EP1 731-2AB00, in "Power Supplies".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/105
3
Industrial relays with test bracket
3TG10 Power Relays/Miniature Contactors
4-pole, 4 kW
■ Overview
■ Application
Version
The 3TG10 power relays/miniature contactors with 4 main
contacts are available with 6.3 mm ... 0.8 mm screw terminals or
flat connectors. The versions with screw terminals are climateproof and finger-safe in accordance with DIN VDE 0106
Part 100.
The 3TG10 power relays/miniature contactors are small.
Their width is 36 mm.
Because they are hum-free they are suitable for use in
household appliances and distribution boards in office and
residential areas. They can also be used for applications where
there is little space such as air conditioners, heating systems,
pumps, and fans, i.e. for simple electrical controls.
AC and DC operation
EN 60947-4-1 (VDE 0660 Part 102)
3
Surge suppression
The 3TG10 power relays/miniature contactors have an
integrated protective circuit against opening surges.
Overload and short-circuit protection
The 3UA7 overload relay can be used for overload protection.
This applies to mounting onto contactors and to stand-alone
installation.
Information about short-circuit protection by means of
contactors can be found in the Technical specifications.
■ Selection and ordering data
Rated data
Utilization category
AC -1
AC-2 and AC-3
Switching of resistive
loads at 55 °C
Main
Rated control DT
contacts supply
voltage Us
Operating
current Ie
up to
400 V
Power of
threephase
loads at
50 Hz and
400 V
Operating
current Ie
up to
400 V1)
Power of Version
threephase
loads at
50 Hz and
400 V
A
kW
A
kW
NO NC
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
V
Weight
per PU
approx.
kg
With screw terminals, 4-pole
For screw and snap-on mounting onto 35 mm standard mounting rail ¼
hum-free
AC operation, 45 ... 450 Hz
20
13
8.4
4
4 --
24
110
230
}
A
}
3TG10 10-0AC2
3TG10 10-0AG2
3TG10 10-0AL2
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.157
0.158
0.156
3 1
24
110
230
}
D
}
3TG10 01-0AC2
3TG10 01-0AG2
3TG10 01-0AL2
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.157
0.158
0.157
4 -3 1
24
24
}
}
3TG10 10-0BB4
3TG10 01-0BB4
1 1 unit
1 1 unit
101
101
0.157
0.157
DC operation
20
13
8.4
4
3TG10 ..-0...
With 6.3 × 0.8 mm flat connectors, 4-pole
For screw and snap-on mounting onto 35 mm standard mounting rail ¼
hum-free
AC operation, 45 ... 450 Hz
16
10
8.4
4
4 --
24
110
230
D
D
}
3TG10 10-1AC2
3TG10 10-1AG2
3TG10 10-1AL2
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.146
0.146
0.145
3 1
24
110
230
D
D
}
3TG10 01-1AC2
3TG10 01-1AG2
3TG10 01-1AL2
1 1 unit
1 1 unit
1 1 unit
101
101
101
0.147
0.146
0.144
4 -3 1
24
24
D
D
3TG10 10-1BB4
3TG10 01-1BB4
1 1 unit
1 1 unit
101
101
0.146
0.146
DC operation
16
10
3TG10 ..-1...
8.4
8.4
4
4
* You can order this quantity or a multiple thereof.
3/106
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
Snap-on auxiliary contact blocks
The timing relays are suitable for both AC and DC operation.
The auxiliary switch blocks and the maximum number of blocks
that can be mounted are described in "Motor Contactors" and
"Contactor Relays".
Size S00
Solid-state time-delay auxiliary switch block
The timer module, which is available in "ON-delay" and "OFFdelay" versions, allows time-delayed functions up to 100 s
(3 distinct delay ranges).
It contains a relay with one NO contact and one NC contact;
depending on the version, the relay is switched either after an
ON-delay or after an OFF-delay.
The version for size S00 contactors is fitted onto the front of the
contactor (with the supply voltage switched off) and then slid
into its latched position; at the same time, the timing relay is
connected by means of plug-in contacts to coil terminals A1 and
A2 of the contactor. Any contactor coil terminals which are not
required are sealed off by means of covers on the enclosure of
the time-delay block, to prevent them from being connected
inadvertently.
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
The timer module with "WYE-DELTA FUNCTION" is equipped
with one delayed and one instantaneous NO contact, with an
interval time of 50 ms between the two. The delay time of the
NO contact can be set between 1.5 s and 30 s.
The solid-state, time-delay block cannot be mounted on size S00
coupling relays.
Wye-delta function:
The time-delay block for size S0 to S3 contactors is plugged into
coil terminals A1 and A2 on top of each contactor; the timing
relay is connected both electrically and mechanically by means
of pins.
37/38
t
50 ms
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
The contactor on which the solid-state, time-delay auxiliary
switch block is mounted operates without a delay.
Note on configuration
Size S00
a)
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
The solid-state, time-delay auxiliary switch block cannot be
mounted on size S00 coupling relays.
Sizes S0 to S12
The solid-state, time-delay auxiliary switch block is fitted onto the
front of the contactor.
The timer module is supplied with power through two terminals
(A1/A2); the time delay of the auxiliary switch block can be
activated either by a parallel link to any contactor coil or by any
power source.
The OFF-delay variant operates without an auxiliary power
supply; minimum on-time: 200 ms.
A single-pole auxiliary switch block can be snapped onto the
front of the contactor in addition to the timer module.
The timer module has no integrated components for damping
opening surges.
Solid-state time-delay block with semiconductor output
The timer module, which is available in "ON-delay" and "OFFdelay with auxiliary voltage" versions, allows time-delayed
functions up to 100 s (3 distinct delay ranges). Contactors fitted
with a time-delay block close or open after a delay according to
the set time.
The ON-delay variant of the timing relay is connected in series
with the contactor coil; terminal A1 of this coil must not be
connected.
With the OFF-delay variant of the timing relay, the contactor coil
is contacted directly through the relay; terminals A1 and A2 of
the contactor coil must not be connected.
L1
S1
1
2
N
A1 B1 A2
A1
A2
K3
1
NSB00454
The solid-state, time-delay auxiliary switch block is fitted onto the
front of the contactor. The timer module is supplied with power
directly by plug-in contacts through the coil terminals of the
contactor, in parallel with A1/A2. The timing function is activated
by closing the contactor on which the auxiliary switch block is
mounted. The OFF-delay variant operates without an auxiliary
power supply; minimum on-time: 200 ms.
b)
L1
2
K3
S1
A1 B1 A2
K3
A1
A2
N
NSB00455
NSB00453a
A1/A2
Y 27/28
Sizes S0 to S3
$ Timing relay block
% Contactor
The activation of loads parallel to the start input is not
permissible when using AC control voltage (see (a) in the circuit
diagram).
The 3RT19 16-2D... / 3RT19 26-2D... OFF-delay timing relay
blocks have a zero potential start input B1. This means that if
there is a parallel load on terminal B1, activation can be
simulated with AC voltage. In this case, the additional load
(e.g. contactor K3) must be wired in accordance with (b).
OFF-delay device for size S00 to S3 contactors
AC and DC operation
IEC 60947, EN 60947
For screw and snap-on mounting onto 35 mm standard
mounting rail. The OFF-delay devices have screw terminals.
The OFF-delay device prevents a contactor from dropping out
unintentionally when there is a short-time voltage dip or voltage
failure. It supplies a downstream, DC-operated contactor with
the necessary power during a voltage dip, ensuring that the
contactor does not trip. The 3RT19 16 OFF-delay devices are
specifically designed for operation with the 3RT contactors and
3RH contactor relays of the SIRIUS series.
The OFF-delay device operates without external voltage on a
capacitive basis, and can be energized with either AC or DC
(24 V version only for DC operation). Voltage matching, which is
only necessary with AC operation, is performed using a rectifier
bridge.
A contactor opens after a delay when the capacitors of the
contactor coil, built into the OFF-delay device, are switched in
parallel. In the event of voltage failures, the capacitors are
discharged via the coil and thereby delay the opening of the
contactor.
Siemens LV 1 · 2006
3/107
3
■ Overview
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
If the command devices are upstream of the OFF-delay device
in the circuit, the OFF-delay takes effect with every opening
operation. If the opening operation is downstream of the OFFdelay device, an OFF-delay only applies in the event of failure of
the mains voltage.
NSB0_00456b
Accessories for 3RT, 3RH contactors and
contactor relays
4000 V
V
Operation
The mean value of the OFF-delay is approximately 1.5 times the
specified minimum time.
Surge suppressors
• Without LED (also for Cage Clamp terminals)
Sizes S00, S0, S2, S3, S6 to S12
• With LED (also for Cage Clamp terminals)
Size S00
All 3RT1 contactors and 3RH1 contactor relays can be retrofitted
with RC elements or varistors for damping opening surges in the
coil. Diodes or diode assemblies (comprising noise suppression
diodes and Zener diodes for rapid switch-off) can be used.
The surge suppressors are plugged onto the front of size S00
contactors. Space is provided for them next to a snap-on
auxiliary switch block.
With all size S0 to S3 contactors, varistors, RC elements and
diode assemblies can be plugged on directly at the coil
terminals, either on the top or underneath.
The plug-in direction of the diodes and diode assemblies is
determined by a coding device.
Coupling relays are supplied either without overvoltage
damping or with a varistor or diode connected as standard,
according to the version.
Note:
The OFF-delay times of the NO contacts and the ON-delay times
of the NC contacts increase if the contactor coils are damped
against voltage peaks (noise suppression diode 6 to 10 times;
diode assemblies 2 to 6 times, varistor +2 to 5 ms).
500 ms
t
Capacitive input to various analog and digital signals makes it
necessary to suppress interference in the load circuit.
Reducing contact arcing
The connection between the main conducting path and the EMC
interference suppression module enables contact arcing, which
is responsible for contact erosion and the majority of clicking
noises, to be reduced; this in turn is conducive to an electromagnetically compatible design.
Higher operational reliability
Since the EMC interference suppression module achieves a
significant reduction in radio-frequency components and the
voltage level in three phases, the contact endurance is also
improved considerably. This makes an important contribution
towards enhancing the reliability and availability of the system as
a whole.
Dispensing with fine graduations
There is no need for fine graduations within each performance
class, as smaller motors inherently have a higher inductance, so
that one solution for all fixed-speed drives up to 5.5 kW is
adequate.
Two electrical variants are available:
• The advantages of the RC circuit lie mainly in the reduction in
the rate of rise and in its RF damping ability. The selected
values ensure effective interference suppression over a wide
range.
NSB0_00457b
A DC-operated contactor is connected to the output in
accordance with the input voltage that is applied.
400 V
V
Electromagnetic interference suppression module, 3-phase
for size S00 contactors
930 V
400 V
500 ms
t
• The varistor circuit can absorb a high energy level and can
also be used for frequencies ranging from 10 to 400 Hz
(closed-loop controlled drives). There is no limiting below the
knee-point voltage, however.
NSB0_00458b
3
In the case of the versions for rated control supply voltages of
110 V and 230 V, either AC voltage or DC voltage can be applied
on the line side, whereas the variant for 24 V is designed for
DC operation only.
V
A so-called counter-e.m.f. (electromotive force) is produced
when motors or various inductive loads are turned off. Voltage
peaks of up to 4000 V may occur as a result, with a frequency
spectrum from 1 kHz to 10 MHz and a rate of voltage variation
from 0.1 to 20 V/ns.
3/108
Siemens LV 1 · 2006
950 V
400 V
500 ms
t
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
Coupling links for mounting on contactors of sizes
S0 to S3
DC operation
IEC 60947 and EN 60947
The coupling link is suitable for use in any climate. It is fingersafe according to EN 50274. The terminal designations comply
with EN 50005.
System-compatible operation with 24 DC V, operating range
17 V to 30 V.
Low power consumption in conformity with the technical
specifications of the solid-state systems. A light-emitting diode
indicates the circuit state.
Surge suppression
The 3RH19 24-1GP11 coupling link has an integrated surge
suppressor (varistor) for the contactor coil being switched.
Mounting
The 3RH19 24-1GP11 coupling link is mounted directly on the
contactor coil.
Solder pin adapters
The solder pin adapters for the size S00 contactors are available
in two versions:
• Solder pin adapter for contactors with one integrated auxiliary
contact
• Solder pin adapter for contactors with mounted 4-pole
auxiliary switch block
Screw adapters
Plug-on adapters improve the accessibility of the screw fixing for
size S0 contactors. As a result it is possible to position the
screwdriver vertically even when using insulated screwdrivers or
power screwdrivers.
Optionally the adapters can be rotated through 90° before
mounting.
Sealable covers for sizes S00 to S12
When contactors and contactor relays are used in safetyoriented applications, it must be ensured that it is impossible to
operate the contactors manually.
For SIRIUS contactors there are sealable covers available for
this purpose as accessories; these prevent accidental manual
operation. These are transparent molded-plastic caps with a
bracket that enables the contactor to be sealed.
Siemens LV 1 · 2006
3/109
3
Additional load module
• Size S00 for plugging onto the front of the contactors with and
without auxiliary switch block
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
3
■ Selection and ordering data
3RH19 21-1HA..
For contactors
Auxiliary contacts
Ident. No.
Type
3RH19 11-1LA..
3RH19 11-1AA.
3RH19 11-1HA..
3RH19 11-1FA..
DT Screw terminals
Version
NO
PU
PS*
(UNIT,
SET, M)
Order No.
NC
NO
PG
Weight
per PU
approx.
Price
per PU
NC
kg
Auxiliary switch blocks for snapping onto the front
according to EN 50012
Size S00
For assembling contactors with 2, 4 and 5 auxiliary contacts
3RT10 1.-1...1,
3RT10 1.-2...1
Ident. No. 10 E
11 E
22 E
23 E
32 E
-1
1
2
1
2
3
2
-----
-----
}
}
}
}
3RH19 11-1HA01
3RH19 11-1HA12
3RH19 11-1HA13
3RH19 11-1HA22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.035
0.046
0.051
0.052
3
2
1
2
1
2
3
2
-----
-----
}
}
}
B
3RH19 21-1HA31
3RH19 21-1HA22
3RH19 21-1HA13
3RH19 21-1XA22-0MA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.074
0.073
0.073
0.073
Sizes S0 ... S121)
4-pole
3RT10 2,
3RT1. 3 ... 3RT1. 7
31
22
13
22 2)
Auxiliary switch blocks for snapping onto the front
according to EN 50005
Size S00
2 or 4-pole auxiliary switch blocks for assembling contactors with 3 and 5 auxiliary contacts
3RT1. 1,
3RH11,
3RH14
20
11
02
11 U
2
1
---
-1
2
--
---1
---1
}
}
}
}
3RH19 11-1FA20
3RH19 11-1FA11
3RH19 11-1FA02
3RH19 11-1FB11
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.041
0.041
0.040
0.040
40
31
22
22 U
11, 11 U
4
3
2
-1
-1
2
-1
---2
1
---2
1
}
}
}
}
}
3RH19 11-1FA40
3RH19 11-1FA31
3RH19 11-1FA22
3RH19 11-1FC22
3RH19 11-1FB22
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.052
0.052
0.052
0.052
0.052
1 and 2-pole auxiliary switch blocks. Cable entry from one side
• Cable entry from above
3RT1. 1,
3RH11,
3RH14
-----
3RT1. 1,
3RH11,
3RH14
-----
1
-1
2
-1
1
--
-----
-----
}
}
}
}
3RH19 11-1AA10
3RH19 11-1AA01
3RH19 11-1LA11
3RH19 11-1LA20
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.016
0.016
0.052
0.052
-----
-----
}
}
}
}
3RH19 11-1BA10
3RH19 11-1BA01
3RH19 11-1MA11
3RH19 11-1MA20
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.015
0.016
0.052
0.053
• Cable entry from below
1
-1
2
-1
1
--
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
1) Exception: 3RT16.
2) With location digits 5, 6, 7, 8.
* You can order this quantity or a multiple thereof.
3/110
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
3RH19 21-2HA .
3RH19 21-2FA..
For contactors
Auxiliary contacts
Ident. No.
Type
DT
Version
NO
Order No.
NC
NO
PU
PS*
(UNIT,
SET, M)
Cage Clamp terminals
PG
Weight
per PU
approx.
Price
per PU
3
3RH19 11-2HA .
NC
kg
Auxiliary switch blocks for snapping onto the front
according to EN 50012
Size S00
For assembling contactors with 2, 4 and 5 auxiliary contacts
3RT10 1.-1...1,
3RT10 1.-2...1
Ident. No. 10 E
11 E
22 E
23 E
32 E
-1
1
2
1
2
3
2
-----
-----
}
}
}
}
3RH19 11-2HA01
3RH19 11-2HA12
3RH19 11-2HA13
3RH19 11-2HA22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.040
0.052
0.058
0.059
3
2
1
2
1
2
3
2
-----
-----
}
}
}
D
3RH19 21-2HA31
3RH19 21-2HA22
3RH19 21-2HA13
3RH19 21-2XA22-0MA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.070
0.069
0.068
0.071
Sizes S0 ... S121)
4-pole
3RT10 2,
3RT1. 3 ... 3RT1. 7
31
22
13
22 2)
Auxiliary switch blocks for snapping onto the front
according to EN 50005
Size S00
2 and 4-pole auxiliary switch blocks for assembling contactors with 3 and 5 auxiliary contacts
3RT1. 1,
3RH11,
3RH14
20
11
02
11 U
2
1
---
-1
2
--
---1
---1
}
}
}
A
3RH19 11-2FA20
3RH19 11-2FA11
3RH19 11-2FA02
3RH19 11-2FB11
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.045
0.045
0.046
0.046
40
31
22
22 U
11, 11 U
4
3
2
-1
-1
2
-1
---2
1
---2
1
}
}
}
}
B
3RH19 11-2FA40
3RH19 11-2FA31
3RH19 11-2FA22
3RH19 11-2FC22
3RH19 11-2FB22
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.059
0.057
0.058
0.058
0.058
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
1) Exception: 3RT16.
2) With location digits 5, 6, 7, 8
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/111
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
3RH19 21-1F..
3RH19 21-1C..
For contactors
Auxiliary contacts
3RH19 21-1MA..
DT
Version
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
3
Ident. No.
3RH19 21-1LA..
Type
NO
NC
NO
NC
----2
----2
kg
Auxiliary switch blocks for snapping onto the front
according to EN 50005
Sizes S0 to S121)
4-pole auxiliary switch blocks
3RT1. 2,
3RT1. 3
...
3RT1. 7
40
31
22
04
22 U
4
3
2
---
-1
2
4
--
}
}
}
}
}
3RH19 21-1FA40
3RH19 21-1FA31
3RH19 21-1FA22
3RH19 21-1FA04
3RH19 21-1FC22
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.074
0.074
0.073
0.072
0.074
3RH19 21-1CA10
3RH19 21-1CA01
3RH19 21-1CD10
3RH19 21-1CD01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.020
0.019
0.020
0.019
1-pole auxiliary switch blocks to EN 50005 and EN 50012
3RT1. 2
...
3RT1. 7
-----
1
----
-1
---
--1
--
---1
}
}
}
}
2-pole auxiliary switch blocks with cable entry from one side
• Cable entry from above
3RT1. 2,
3RT1. 3
...
3RT1. 7
----
3RT1. 2,
3RT1. 3
...
3RT1. 7
----
1
2
--
1
-2
----
----
}
}
}
3RH19 21-1LA11
3RH19 21-1LA20
3RH19 21-1LA02
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.074
0.075
0.074
1
-2
----
----
}
}
}
3RH19 21-1MA11
3RH19 21-1MA20
3RH19 21-1MA02
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.074
0.076
0.073
DT
Cage Clamp terminals
• Cable entry from below
1
2
--
1) Exception: 3RT16.
2RH19 21-2F..
3RH19 21-2C..
For contactors
Auxiliary contacts
Ident. No.
Type
Version
NO
Order No.
NC
NO
NC
----2
----2
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
kg
Auxiliary switch blocks for snapping onto
the front according to EN 50005
Sizes S0 to S121)
4-pole auxiliary switch blocks
3RT1. 2,
3RT1. 3
...
3RT1. 7
40
31
22
04
22 U
4
3
2
---
-1
2
4
--
}
}
}
A
A
3RH19 21-2FA40
3RH19 21-2FA31
3RH19 21-2FA22
3RH19 21-2FA04
3RH19 21-2FC22
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.071
0.070
0.069
0.068
0.069
3RH19 21-2CA10
3RH19 21-2CA01
1
1
1 unit
1 unit
101
101
0.018
0.017
1-pole auxiliary switch blocks to EN 50005 and EN 50012
3RT1. 2
...
3RT1. 7
---
1
--
-1
---
---
}
}
1) Exception: 3RT16.
* You can order this quantity or a multiple thereof.
3/112
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
Snap-on auxiliary switch blocks according to EN 50011 for assembling contactor relays with 8 contacts.
For contactor relays
Contacts
Ident. No.
DT
Version
NO
PU
PS*
(UNIT,
SET, M)
Screw terminals
Order No.
PG
Weight
per PU
approx.
Price
per PU
NC
kg
Snap-on auxiliary switch blocks according to EN 50011
For assembling contactor relays with 8 contacts
3RH11 40,
3RH14 40
(Ident. No. 40 E)
80 E
71 E
62 E
53 E
44 E
4
3
2
1
--
-1
2
3
4
}
}
}
}
}
3RH19 11-1GA40
3RH19 11-1GA31
3RH19 11-1GA22
3RH19 11-1GA13
3RH19 11-1GA04
DT
Cage Clamp terminals
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.052
0.052
0.052
0.052
0.052
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
3RH19 11-2GA..
For contactor relays
Contacts
Ident. No.
Version
NO
Order No.
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
NC
kg
Snap-on auxiliary switch blocks according to EN 50011
For assembling contactor relays with 8 contacts
3RH11 40,
(Ident. No. 40 E)
80 E
71 E
62 E
53 E
44 E
4
3
2
1
--
-1
2
3
4
}
}
}
}
}
3RH19 11-2GA40
3RH19 11-2GA31
3RH19 11-2GA22
3RH19 11-2GA13
3RH19 11-2GA04
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.059
0.059
0.058
0.058
0.058
For multi-unit packing and reusable packaging,
see Appendix -> Ordering Notes.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/113
3
3RH19 11-1GA..
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
3RH19 21-1EA..
3RH19 21-1KA..
For contactors
Auxiliary contacts
DT
PU
PS*
(UNIT,
SET, M)
Screw terminals
3
3RH19 21-1DA11
3RH19 21-1JA11
Version
Type
NO
Order No.
PG
Weight
per PU
approx.
Price
per PU
NC
kg
Laterally mountable auxiliary switch blocks according to
EN 50012
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
1
1
}
3RH19 21-1DA11
1
1 unit
101
0.047
1
1 unit
101
0.047
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.048
0.048
0.048
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.048
0.048
0.048
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
1
1
}
3RH19 21-1JA11
Laterally mountable auxiliary switch blocks according to
EN 50005
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
2
1
--
-1
2
}
}
}
3RH19 21-1EA20
3RH19 21-1EA11
3RH19 21-1EA02
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
2
1
--
-1
2
}
}
}
3RH19 21-1KA20
3RH19 21-1KA11
3RH19 21-1KA02
* You can order this quantity or a multiple thereof.
3/114
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
3RH19 21-2DA11
3RH19 21-2JA11
3RH19 21-2EA..
3RH19 21-2KA..
For contactors
Auxiliary contacts
DT
Version
Type
Cage Clamp terminals
Order No.
NO
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
NC
kg
Laterally mountable auxiliary switch blocks according to EN 50012
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
1
}
1
3RH19 21-2DA11
1
1 unit
101
0.050
1
1 unit
101
0.051
1
1
1 unit
1 unit
101
101
0.050
0.051
1
1
1 unit
1 unit
101
101
0.049
0.050
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
1
1
B
3RH19 21-2JA11
Laterally mountable auxiliary switch blocks according to EN 50005
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
2
--
}
}
-2
3RH19 21-2EA20
3RH19 21-2EA02
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
-2
C
C
3RH19 21-2KA20
3RH19 21-2KA02
DT
Screw terminals
3RH19 21-1FE22
3RH19 11-1NF ..
For contactors
2
--
Version
Contacts
Version
Type
NO
NO
Order No.
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
NC
NC
kg
----
----
1
-2
}
}
}
3RH19 11-1NF11
3RH19 11-1NF20
3RH19 11-1NF02
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.042
0.041
0.041
1
1
1
}
3RH19 21-1FE22
1
1 unit
101
0.073
Solid-state compatible auxiliary switch blocks,
for snapping onto the front, according to EN 50005
Size S00
3RT1. 1,
3RH11,
3RH14
1
For use in dusty atmosphere and
solid-state circuits with rated
2
operating currents Ie/AC-14 and
-DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
No mirror contacts.
Sizes S0 ... S12
3RT1. 2
...
3RT1. 7
1
For use in dusty atmosphere and
solid-state circuits with rated
operating currents Ie/AC-14 and
DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
Mirror contacts according to
EN 60947-4-1, Appendix F
1 NO + 1 NC standard auxiliary
switches: For technical
specifications, see LV 1 T.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/115
3
Accessories for 3RT, 3RH contactors and
contactor relays
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
3
Accessories for 3RT, 3RH contactors and
contactor relays
3RH19 21-2JE22
3RH19 11-2NF ..
For contactors
Version
3RH19 21-2DE11
3RH19 21-2JE11
Contacts
DT
Version
Type
NO
NO
Cage Clamp terminals
Order No.
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
NC
NC
kg
----
----
1
-2
}
}
}
3RH19 11-2NF11
3RH19 11-2NF20
3RH19 11-2NF02
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.047
0.047
0.046
1
1
1
B
3RH19 21-2FE22
1
1 unit
101
0.070
1
1 unit
101
0.049
1
1 unit
101
0.052
Solid-state compatible auxiliary switch blocks,
for snapping onto the front, according to EN 50005
Size S00
3RT1. 1,
3RH11,
3RH14
For use in dusty atmosphere and
1
solid-state circuits with rated
2
operating currents Ie/AC-14 and
-DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
No mirror contacts.
Sizes S0 ... S12
3RT1. 2
...
3RT1. 7
1
For use in dusty atmosphere and
solid-state circuits with rated
operating currents Ie/AC-14 and
DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
Mirror contacts according to
EN 60947-4-1, Appendix F
1 NO + 1 NC standard auxiliary
switches: For technical
specifications, see LV 1 T.
Solid-state compatible auxiliary switch blocks, laterally mountable,
according to EN 50012
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2
...
3RT1. 7
1 NO + 1 NC solid-state compatible 1
auxiliary switches
For use in dusty atmosphere and
solid-state circuits with rated
operating currents Ie/AC-14 and
DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
Mirror contacts according to
EN 60947-4-1, Appendix F
--
--
1
}
3RH19 21-2DE11
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4
...
3RT1. 7
1 NO + 1 NC solid-state compatible 1
auxiliary switches
For use in dusty atmosphere and
solid-state circuits with rated
operating currents Ie/AC-14 and
DC-13 from 1 mA to 300 mA at 3 V to
60 V.
Hard gold-plated contacts.
Mirror contacts according to
EN 60947-4-1, Appendix F
--
--
1
B
3RH19 21-2JE11
* You can order this quantity or a multiple thereof.
3/116
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors
Auxiliary
contacts
Type
Rated control supply Time setting DT
voltage Us1)
range t
V
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
s
kg
Solid-state time-delay auxiliary switch blocks,
for snapping onto the front, terminal designations
according to DIN 46199, Part 5
Size S00
1 NO + 1 NC 24 AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
B
3RT19 16-2EJ11
3RT19 16-2EJ21
3RT19 16-2EJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.085
0.084
0.086
100 ... 127 AC3)
0.05 ... 1
0.5 ... 10
5 ... 100
C
}
}
3RT19 16-2EC11
3RT19 16-2EC21
3RT19 16-2EC31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.087
0.087
0.086
200 ... 240 AC3)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2ED11
3RT19 16-2ED21
3RT19 16-2ED31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.088
0.089
0.090
OFF-delay without auxiliary voltage (varistor integrated)4)
3RT19 16-2....
3RT1. 1,
3RH112)
3RH14
1 NO + 1 NC 24 AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 16-2FJ11
3RT19 16-2FJ21
3RT19 16-2FJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.087
0.088
0.089
100 ... 127 AC/DC3) 0.05 ... 1
0.5 ... 10
5 ... 100
D
}
B
3RT19 16-2FK11
3RT19 16-2FK21
3RT19 16-2FK31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.086
0.087
0.088
200 ... 240 AC/DC3) 0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2FL11
3RT19 16-2FL21
3RT19 16-2FL31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.089
0.089
0.089
B
B
B
3RT19 16-2LJ21
3RT19 16-2LC21
3RT19 16-2LD21
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.083
0.085
0.085
1.5 ... 30
1.5 ... 30
1.5 ... 30
}
D
}
3RT19 16-2GJ51
3RT19 16-2GC51
3RT19 16-2GD51
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.086
0.087
0.090
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
A
3RT19 26-2EJ11
3RT19 26-2EJ21
3RT19 26-2EJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.081
0.081
0.082
100 ... 127 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
C
}
D
3RT19 26-2EC11
3RT19 26-2EC21
3RT19 26-2EC31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.083
0.083
0.083
200 ... 240 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
B
3RT19 26-2ED11
3RT19 26-2ED21
3RT19 26-2ED31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.085
0.085
0.085
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 26-2FJ11
3RT19 26-2FJ21
3RT19 26-2FJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.085
0.084
0.085
100 ... 127 AC/DC5) 0.05 ... 1
0.5 ... 10
5 ... 100
D
}
C
3RT19 26-2FK11
3RT19 26-2FK21
3RT19 26-2FK31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.087
0.086
0.087
200 ... 240 AC/DC5) 0.05 ... 1
0.5 ... 10
5 ... 100
D
A
A
3RT19 26-2FL11
3RT19 26-2FL21
3RT19 26-2FL31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.086
0.084
0.086
1.5 ... 30
}
3RT19 26-2GJ51
1
1 unit
101
0.084
1.5 ... 30
}
3RT19 26-2GC51
1
1 unit
101
0.085
1.5 ... 30
}
3RT19 26-2GD51
1
1 unit
101
0.088
OFF-delay with auxiliary voltage
3RT10 1
3RH11
1 CO
24 AC/DC
100 ... 127 AC
200 ... 240 AC
0.5 ... 10
0.5 ... 10
0.5 ... 10
Wye-delta function (varistor integrated)
24 AC/DC3)
3RT10 12) 1 NO
delayed +
100 ... 127 AC3)
1 NO, instan- 200 ... 240 AC3)
taneous,
dead time
50 ms
Sizes S0 ... S12
With ON-delay
3RT10,
3RT13,
3RT14,
3RT15
1 NO + 1 NC 24 AC/DC5)
3RT19 26-2....
OFF-delay without auxiliary voltage4)
3RT10,
3RT13,
3RT14,
3RT15
1 NO + 1 NC 24 AC/DC5)
Wye-delta function
3RT10,
3RT13,
3RT14,
3RT15
24 AC/DC5)
1 NO,
delayed +
100 ... 127 AC5)
1 NO, instan200 ... 240 AC5)
taneous,
dead time
50 ms
1) The AC voltages are valid for 50 Hz and 60 Hz.
2) Cannot be fitted onto coupling relays.
3) The terminals for the control supply voltage are connected to the
contactor by the integrated spring contacts of the solid-state time
auxiliary switch above it when this switch is mounted
5) Terminals A1 and A2 for the control supply voltage of the solid-state timedelay auxiliary switch must be connected to the associated contactor by
means of connecting leads.
4) Setting of output contacts in as-supplied state not defined (bistable relay).
Application of the control supply voltage once results in contact
changeover to the correct setting.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/117
3
ON-delay (varistor integrated)
3RT1. 1,
3RH112)
3RH14
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors
Rated control supply Time setting
voltage Us
range t
Type
V
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
s
kg
Solid-state time-delay blocks with semiconductor output
Size S00
For mounting onto the front of contactors
• ON-delay (varistor integrated)
3
3RT1. 1,
3RH111)
3RH14
3RT19 16-2C...
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
B
}
B
3RT19 16-2CG11
3RT19 16-2CG21
3RT19 16-2CG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.051
0.051
0.054
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2CH11
3RT19 16-2CH21
3RT19 16-2CH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.052
0.052
0.051
• OFF-delay with auxiliary voltage (varistor integrated)
3RT1. 1,
3RH111)
3RH14
3RT19 16-2D...
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
C
B
B
3RT19 16-2DG11
3RT19 16-2DG21
3RT19 16-2DG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.057
0.057
0.057
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
B
3RT19 16-2DH11
3RT19 16-2DH21
3RT19 16-2DH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.053
0.060
0.058
Sizes S0 ... S3
For mounting onto coil terminals on top of the contactors
• ON-delay (varistor integrated)
3RT10 2,
3RT10 3,
3RT10 4,
3RT132)
3RT15
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
B
D
3RT19 26-2CG11
3RT19 26-2CG21
3RT19 26-2CG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.048
0.049
0.048
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 26-2CH11
3RT19 26-2CH21
3RT19 26-2CH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.048
0.047
0.048
3RT19 26-2C...
• OFF-delay with auxiliary voltage (varistor integrated)
3RT10 2,
3RT10 3,
3RT10 4,
3RT132)
3RT15
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
D
D
3RT19 26-2DG11
3RT19 26-2DG21
3RT19 26-2DG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.051
0.051
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
C
D
C
3RT19 26-2DH11
3RT19 26-2DH21
3RT19 26-2DH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
3RT19 26-2D...
OFF-delay devices
3RT1. 1,
3RT1. 2,
3RH1 ...-1BF40
110 AC/DC
D
3RT19 16-2BK01
1
1 unit
101
0.143
3RT1. 1,
3RT1. 2,
3RH1 ...-1BM40
220/230 AC/DC
D
3RT19 16-2BL01
1
1 unit
101
0.144
}
3RT19 16-2BE01
1
1 unit
101
0.114
3RT1. 1 ... 3RT1. 4, 24 DC
3RH1 ...-1BB40
3RT19 16.-2B.01
Pneumatic delay blocks,
terminal designation according to EN 50005
3RT1. 2
For mounting onto the front of size S03) contactors
Auxiliary contacts 1 NO and 1 NC
• ON-delay
0.1 ... 30
1 ... 60
C
C
3RT19 26-2PA01
3RT19 26-2PA11
1
1
1 unit
1 unit
101
101
0.078
0.078
0.1 ... 30
1 ... 60
C
C
3RT19 26-2PR01
3RT19 26-2PR11
1
1
1 unit
1 unit
101
101
0.078
0.078
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.122
0.130
0.125
• OFF-delay
3RT19 26-2P...
Mechanical latching blocks
Sizes S0 and S2
For mounting on 1 contactor,
contactor remains in the energized state even after a voltage failure
3RT1. 2,
3RT1. 3
3RT19 26-3A.31
24 AC/DC
110 AC/DC
230 AC/DC
A
B
B
3RT19 26-3AB31
3RT19 26-3AF31
3RT19 26-3AP31
1) Cannot be fitted onto coupling relays.
2) Not to be used for 3RT10 4. and 3RT13 4. contactors with Us ˆ 42 V.
3) In addition to these, no other auxiliary contacts are permitted.
* You can order this quantity or a multiple thereof.
3/118
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For con- Version
tactors
Type
Rated control supply
voltage Us1)
AC
operation
DC
operation
V AC
V DC
DT
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors without LED
(also for Cage Clamp terminals)
Size S00
Varistors
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
A
}
A
3RT19 16-1BB00
3RT19 16-1BC00
3RT19 16-1BD00
3RT19 16-1BE00
3RT19 16-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.008
0.008
0.008
0.008
0.009
3RT1.,
3RH1
RC elements
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
}
3RT19 16-1CB00
3RT19 16-1CC00
3RT19 16-1CD00
3RT19 16-1CE00
3RT19 16-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.009
0.009
0.009
0.009
0.009
3RT1.,
3RH1
Noise suppression
diodes
--
12 ... 250
}
3RT19 16-1DG00
1
1 unit
101
0.007
3RT1.,
3RH1
Diode assembly
(diode and Zener
diode) for
DC operation
--
12 ... 250
}
3RT19 16-1EH00
1
1 unit
101
0.008
3RT19 16-1DG00
Size S0
For fitting onto the coil terminals at top or bottom
3RT1. 2
Varistors
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 26-1BB00
3RT19 26-1BC00
3RT19 26-1BD00
3RT19 26-1BE00
3RT19 26-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.023
0.023
0.024
0.028
0.029
3RT1. 2
RC elements
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 26-1CB00
3RT19 26-1CC00
3RT19 26-1CD00
3RT19 26-1CE00
3RT19 26-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.023
0.023
0.023
0.024
0.027
3RT1. 2
Diode assembly
For DC operation
• Connectable at the -top (e.g. for contactor -with overload relay)
24
30 ... 250
}
}
3RT19 26-1ER00
3RT19 26-1ES00
1
1
1 unit
1 unit
101
101
0.023
0.024
• Connectable at the -bottom (e.g. for
-fuseless load feeders)
24
30 ... 250
}
A
3RT19 26-1TR00
3RT19 26-1TS00
1
1
1 unit
1 unit
101
101
0.024
0.023
3RT19 26-1B0.00
1) Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
2) For packs of 10 units, the Order No. must be supplemented with "Z" and
the order code "X90".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/119
3
For plugging onto the front side of the contactors with and without auxiliary switch blocks
3RT1.,
3RH1
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors
Version
Rated control supply
voltage Us1)
Type
AC
operation
DC
operation
V AC
V DC
DT
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors without LED
(also for Cage Clamp terminals)
Sizes S2 and S3
For fitting onto the coil terminals at top or bottom
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
--
}
}
}
}
B
3RT19 26-1BB00
3RT19 26-1BC00
3RT19 26-1BD00
3RT19 26-1BE00
3RT19 26-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.023
0.023
0.024
0.028
0.029
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 36-1CB00
3RT19 36-1CC00
3RT19 36-1CD00
3RT19 36-1CE00
3RT19 36-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.039
0.039
0.039
0.041
0.040
• Connectable at the top
(e.g. for contactor with
overload relay)
24
30 ... 250
}
}
3RT19 36-1ER00
3RT19 36-1ES00
1
1
1 unit
1 unit
101
101
0.024
0.024
• Connectable at the
bottom (e.g. for fuseless
load feeders)
24
30 ... 250
}
B
3RT19 36-1TR00
3RT19 36-1TS00
1
1
1 unit
1 unit
101
101
0.024
0.024
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.033
0.032
0.033
0.033
0.035
Varistors
3
3RT1. 3,
3RT1. 4
3RT19 261B0.00
3RT1. 33), RC elements
3RT1. 4
3RT19 36-1C.00
3RT1. 3,
3RT1. 4
Diode assembly
For DC operation
Sizes S6 ... S12
For connecting to withdrawable coil with screw terminals with contactors with
• 3RT1. ..-.A... conventional operating mechanism
• 3RT1. ..-.N... solid-state operating mechanism
3RT1. 5,
3RT1. 6,
3RT19 56-1C.00 3RT1. 7
RC elements
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
--
1) Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
}
}
}
}
C
3RT19 56-1CB00
3RT19 56-1CC00
3RT19 56-1CD00
3RT19 56-1CE00
3RT19 56-1CF00
3) Mountable only at the top for 3RT1. 3/AC operating mechanism.
2) For packs of 10 or 5 units, the Order No. must be supplemented with "Z"
and the order code "X90".
For
Version
contactors
Type
Rated control supply
voltage Us1)
AC
operation
DC
operation
V AC
V DC
Power con- DT
sumption of
LEDs
at Us
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors with LED
(also for Cage Clamp terminals)
Size S00
For plugging onto the front side of the contactors with and without auxiliary switch blocks
3RT1,
3RH1.
Varistors
24 ... 48
48 ... 127
127 ... 240
--
3RT1,
3RH1.
Noise sup- -pression
-diodes
--
12 ... 24
24 ... 70
70 ... 150
150 ... 250
10 ... 120
20 ... 470
50 ... 700
160 ... 950
}
}
}
A
3RT19 16-1JJ00
3RT19 16-1JK00
3RT19 16-1JL00
3RT19 16-1JP00
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.008
0.008
0.009
0.008
24 ... 70
50 ... 150
150 ... 250
20 ... 470
50 ... 700
160 ... 950
}
}
}
3RT19 16-1LM00
3RT19 16-1LN00
3RT19 16-1LP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.007
0.007
0.007
3RT19 16-1L.00
1) Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
2) For packs of 10 or 5 units, the Order No. must be supplemented with "-Z"
and the order code "X90".
* You can order this quantity or a multiple thereof.
3/120
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
EMC suppression modules; 3-phase ˆ 5.5 kW
Size S00 (for contactors with AC or DC operation)1)
RC elements (3 x 220 W/0.22 µF)
}
A
C
3RT19 16-1PA1
3RT19 16-1PA2
3RT19 16-1PA3
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.078
0.078
0.081
A
B
D
3RT19 16-1PB1
3RT19 16-1PB2
3RT19 16-1PB3
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.084
0.090
0.087
C
3RT19 66-1PV3
1
1 unit
101
0.380
C
Rated operating voltage
Ue = 1000 V AC
For damping overvoltages and
protecting motor windings against
multiple re-ignition when switching off
induction motors. For connection on the
contactor feeder side (2-T1/4-T2/6-T3).
For separate installation.
3RT19 66-1PV4
1
1 unit
101
0.775
For increasing the permissible residual }
current and for limiting the residual
voltage. Ensures safe opening of
contactors with direct control via 230 V
AC semiconductor outputs of SIMATIC
controllers. Also performs the function of
a surge damping circuit.
Rated voltage: AC 50/60 Hz,
180 V to 255 V.
Operating range: 0.8 to 1.1 x Us
3RT19 16-1GA00
1
1 unit
101
0.008
For manual operation of the contactor
contacts for start-up and service3)
3RK1 903-0CA00
1
1 unit
121
0.015
up to 400 V
up to 575 V
up to 690 V
3RT10 1
Varistors
up to 400 V
up to 575 V
up to 690 V
3RT19 16-1PA
Main conducting path surge suppression modules for 3RT12
vacuum contactors
Size S10 and S12
3RT12
Rated operating voltage
Ue = 690 V AC
Additional load modules
Size S00 (also for Cage Clamp terminal)
For plugging onto the front side of the
contactors with and without auxiliary
switch blocks2)
3RT1. 1,
3RH1.
3RT19 16-1GA00
Control kits
Size S00
3RT1. 1,
3RH1.
A
1) See also description on page 3/108.
2) For packs of 10 units, the Order No. must be supplemented with "-Z" and
the order code "X90".
3) See "Load Feeders", Motor Starters and Soft Starters -> ET 200 S Motor
Starters, 3RK1 903-0CA00.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/121
3
3RT10 1
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For
Version
contactors
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Coupling links for control by PLC
Sizes S0 ... S3
For mounting onto the coil terminals of the contactors
3
3RT1. 2,
3RT1. 3,
3RT1. 4
3RH19 24-1GP11
}
3RH19 24-1GP11
1
1 unit
101
0.056
B
For snapping into the location hole of an
identification label on the front of a
contactor either directly on the contactor or
on the front auxiliary switch.
The LED module is connected to coil
terminals A1 and A2 of the contactor and
indicates its energized state. Yellow LED.
Rated voltage: 24 to 240 V AC/DC,
polarized.
(1 pack = 5 units)
3RT19 26-1QT00
1
5 units
101
0.007
For connection of auxiliary and control
cables to the main conductor connections
(for one side)
3RT19 46-4F
1
1 unit
101
0.033
3RT19 16-4KA1
1
4 sets
101
0.030
Operating range DC 17 V to 30 V
Power consumption: 0.5 W at 24 V DC
Permissible residual current of the
electronics (with 0 signal): 2.5 mA
Rated operating current Ie:
AC-15/AC-14 at 230 V: 3 A, DC-13
at 230 V: 0.1 A
With LED for indicating circuit state.
With integrated varistor for damping
opening surges.
LED modules for indicating contactor operation
(also for Cage Clamp terminals)
Sizes S0 ... S12 1)
3RT1. 2,
3RT1. 3,
3RT1. 4
3RT19 26-1QT00
mounted to contactor
Auxiliary terminals, 3-pole
Size S3
3RT10 4.
B
3RT19 46-4F
Solder pin adapters for contactors
Size S00
3RT1. 1,
3RH11
Installation kit for soldering contactors onto A
a printed circuit board.
For 1 contactor, 1 set is required.
1) For sizes S6 ... S12 the connecting leads have to be extended.
* You can order this quantity or a multiple thereof.
3/122
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Solder pin adapters for contactors with mounted
4-pole auxiliary switch block
Size S00
Installation kit for soldering
contactors with an auxiliary switch
block onto a printed circuit board
For 1 contactor, 1 set is required.
B
3RT19 16-4KA2
1
4 sets
101
0.070
3RT19 26-4P
1
10 sets
101
0.002
3
3RT1. 1,
3RH11
Screw adapters with screw or Cage Clamp terminal
Size S0
3RT1.2.
NSB0_01470
Screw adapter for easy screw fixing, C
2 units required per contactor
(1 pack contains 10 sets for
10 contactors)
3RT19 16-4BB31
3RT19 16-4BB41
3RT19 36-4BB31
Size
For contactors
Max. conductor cross-sections
Type
mm2
3RT19 56-4BA31
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Links for paralleling
3-pole, with connection terminal1)2)
S00
3RT10 1
25
}
3RT19 16-4BB31
1
1 unit
101
0.015
S0
3RT10 2.
35, stranded
}
3RT19 26-4BB31
1
1 unit
101
0.018
S2
3RT10 3.
95
}
3RT19 36-4BB31
1
1 unit
101
0.107
}
3RT19 46-4BB31
1
1 unit
101
0.197
3-pole, with through hole (star jumpers)1)2)
S3
3RT10 4.
3RT14 4.
185
S6
3RT1. 5
--
}
3RT19 56-4BA31
1
1 unit
101
0.161
S10/S12
3RT1. 6,
3RT1. 7
--
}
3RT19 66-4BA31
1
1 unit
101
0.533
C
3RT19 16-4BB41
1
1 unit
101
0.015
4-pole, with connection terminal1)2)
S00
3RT1. 1
25
1) The links for paralleling can be reduced by one pole.
2) Sizes S00 to S2: The links for paralleling are insulated.
Size S3: A cover is included for touch protection. (Can only be used when
the box terminal is removed.)
Sizes S6 to S12: The 3RT19 56-4EA1 (for S6) or 3RT19 66-4EA1 (for S10
and S12) cover can be used for touch protection.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/123
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
For contactors
Version
Size
Type
S6
3RT1. 5
Up to 70 mm² 2)
(3RB10 5) Up to 120 mm²
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Box terminal blocks
For round and ribbon cables1)
3
Auxiliary conductor
connection for box terminal
}
3RT19 55-4G
1
1 unit
101
}
3RT19 56-4G
1
1 unit
101
0.270
B
3TX7 500-0A
1
1 unit
101
0.008
}
3RT19 66-4G
1
1 unit
101
0.676
0.237
S10/S12
Up to 240 mm²
3RT1. 6,
With auxiliary conductor
3RT1. 7
(3RB10 6) connection
S2
3RT10 3
Additional touch protection for }
fitting to box terminals
(2 units per contactor
required)
3RT19 36-4EA2
1
1 unit
101
0.016
S3
3RT10 4,
3RT14 4
}
3RT19 46-4EA2
1
1 unit
101
0.023
3RT19 5.-4G
Covers
Terminal covers for box terminals
3RT19 36-4EA2
S6
3RT1. 5
Length: 25 mm
}
3RT19 56-4EA2
1
1 unit
101
0.028
S10/S12
3RT1. 6,
3RT1. 7
Length: 30 mm
}
3RT19 66-4EA2
1
1 unit
101
0.038
S3
3RT10 4,
3RT14 4
For maintaining the voltage
clearances and as touch
protection if box terminal is
removed4)
(2 units per contactor
required)
}
3RT19 46-4EA1
1
1 unit
101
0.037
Terminal covers for cable lug and busbar connection3)
3RT19 46-4EA1
S6
3RT1. 5
Length: 100 mm
}
3RT19 56-4EA1
1
1 unit
101
0.067
S10/S12
3RT1. 6,
3RT1. 7
Length: 120 mm
}
3RT19 66-4EA1
1
1 unit
101
0.124
For rail cover between
contactor and 3RB10 overload
relay or wiring connector for
contactor assemblies
3RT1. 5
Length: 27 mm
}
3RT19 56-4EA3
1
1 unit
101
0.021
S10/S12 5) 3RT1. 6,
3RT1. 7
Length: 42 mm
}
3RT19 66-4EA3
1
1 unit
101
0.062
Sealable cover for preventing
manual operation
A
3RT19 16-4MA10
1
5 units
101
0.005
B
3RT19 26-4MA10
1
5 units
101
0.006
S6
Sealable covers
S00
3RT1. 1,
3RH1.6)
S0 ... S12 3RT1. 2 ... 1 unit required per contactor
3RT1. 76)
NSB0_01471
1) For connectable cross-sections, see Technical specifications of
contactors in Catalog LV 1 T.
4) Observe the note in Catalog LV 1 T, Technical specifications,
conductor cross-sections.
2) As standard for 3RT10 54-1 contactor (55 kW).
5) The 3RT19 66-4EA3 cover is required in addition for use in contactor
assemblies (reversing/wye delta).
3) Also fits on contactors S6 ... S12 with box terminals.
6) Exception: Contactors and contactor relays auxiliary switch block
mounted onto the front.
* You can order this quantity or a multiple thereof.
3/124
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors and
contactor relays
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
3RT19 16-4JA02
Insulation stop strip can be inserted in cable entry of B
Cage Clamp (2 strips per contactor required, can be
removed in pairs) Fits into cable entries of all SIRIUS
devices with Cage Clamp terminals of cable crosssection up to 2.5 mm2.
3RT19 16-4JA02
100
20 units
101
0.100
Tools for opening Cage Clamp connection
Length: approx.
175 mm; 3.5 x 0.5
(green; partially
isolated)
A
8WA2 880
1
1 unit
041
0.012
Length: approx.
175 mm; 3.5 x 0.5
(green)
A
8WA2 803
1
1 unit
041
0.024
• 10 mm × 7 mm, pastel turquoise
D
3RT19 00-1SB10
100 816 units
101
0.239
• 20 mm × 7 mm, pastel turquoise
C
3RT19 00-1SB20
100 340 units
101
0.220
• 19 mm × 6 mm, pastel turquoise
D
3RT19 00-1SB60
100
3060
units
101
0.153
• 19 mm × 6 mm, zinc/yellow
C
3RT19 00-1SD60
100
3060
units
101
0.120
For all SIRIUS devices with
Cage Clamp terminals, up to
max. 2.5 mm² conductor crosssection
8WA2 880
Blank labeling plates
Device labeling plates for "SIRIUS"
NSK-7237
Labels for sticking for "SIRIUS"
3RT19 00-1SB10
Computer labeling system
Obtainable from:
For individual inscription of
device identification labeling plates
murrplastik
Systemtechnik GmbH
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/125
3
Insulation stop for securely holding back the conductor insulation
on conductors up to 1 mm2 for contactors with Cage Clamp terminals
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
■ Selection and ordering data
For contactor
Rated control supply voltage DT
Us
Order No.
Size
PU
PS*
(UNIT,
SET, M)
Screw terminals
PG
Weight
per PU
approx.
Price
per PU
50 Hz
50/60 Hz 60 Hz
Type
V
V
V
3RT10 2.,
3RT13 2.,
3RT15 2.
24
42
48
110
-----
-----
}
B
A
}
3RT19 24-5AB01
3RT19 24-5AD01
3RT19 24-5AH01
3RT19 24-5AF01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.092
0.092
0.092
0.090
230
400
---
---
}
}
3RT19 24-5AP01
3RT19 24-5AV01
1
1
1 unit
1 unit
101
101
0.090
0.092
-----
24
42
48
110
-----
}
B
B
}
3RT19 24-5AC21
3RT19 24-5AD21
3RT19 24-5AH21
3RT19 24-5AG21
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.090
0.089
0.091
0.093
---
220
230
---
B
B
3RT19 24-5AN21
3RT19 24-5AL21
1
1
1 unit
1 unit
101
101
0.095
0.095
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 24-5AK61
3RT19 24-5AP61
3RT19 24-5AG61
3RT19 24-5AN61
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.095
0.096
0.069
0.093
kg
Magnetic coils ¼ AC operation
3
S0
3RT19 24-5A.01
S2
3RT10 34
3RT19 34-5A.01
3RT10 35,
3RT10 36,
3RT13 3.,
3RT15 3.
--
400
440
B
3RT19 24-5AR61
1
1 unit
101
0.090
24
42
48
110
-----
-----
}
B
B
}
3RT19 34-5AB01
3RT19 34-5AD01
3RT19 34-5AH01
3RT19 34-5AF01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.109
0.110
0.109
0.114
230
400
---
---
A
B
3RT19 34-5AP01
3RT19 34-5AV01
1
1
1 unit
1 unit
101
101
0.109
0.115
-----
24
42
48
110
-----
}
B
B
B
3RT19 34-5AC21
3RT19 34-5AD21
3RT19 34-5AH21
3RT19 34-5AG21
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.112
0.112
0.114
0.112
---
220
230
---
C
B
3RT19 34-5AN21
3RT19 34-5AL21
1
1
1 unit
1 unit
101
101
0.111
0.114
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 34-5AK61
3RT19 34-5AP61
3RT19 34-5AG61
3RT19 34-5AN61
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.112
0.115
0.088
0.115
--
400
440
B
3RT19 34-5AR61
1
1 unit
101
0.113
24
42
48
110
-----
-----
}
B
B
}
3RT19 35-5AB01
3RT19 35-5AD01
3RT19 35-5AH01
3RT19 35-5AF01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.104
0.106
0.108
0.110
230
400
---
---
}
B
3RT19 35-5AP01
3RT19 35-5AV01
1
1
1 unit
1 unit
101
101
0.108
0.112
-----
24
42
48
110
-----
}
B
B
A
3RT19 35-5AC21
3RT19 35-5AD21
3RT19 35-5AH21
3RT19 35-5AG21
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.110
0.110
0.108
0.108
---
220
230
---
B
B
3RT19 35-5AN21
3RT19 35-5AL21
1
1
1 unit
1 unit
101
101
0.108
0.111
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 35-5AK61
3RT19 35-5AP61
3RT19 35-5AG61
3RT19 35-5AN61
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.108
0.107
0.111
0.088
--
400
440
C
3RT19 35-5AR61
1
1 unit
101
0.111
* You can order this quantity or a multiple thereof.
3/126
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply voltage DT
Us
Cage Clamp terminals
Order No.
Size
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
50 Hz
50/60 Hz 60 Hz
Type
V
V
V
3RT10 2.,
3RT13 2.,
3RT15 2.
24
42
48
110
-----
-----
B
C
B
B
3RT19 24-5AB02
3RT19 24-5AD02
3RT19 24-5AH02
3RT19 24-5AF02
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.093
0.089
0.095
0.090
230
400
---
---
B
C
3RT19 24-5AP02
3RT19 24-5AV02
1
1
1 unit
1 unit
101
101
0.091
0.092
-----
24
42
48
110
-----
B
C
C
B
3RT19 24-5AC22
3RT19 24-5AD22
3RT19 24-5AH22
3RT19 24-5AG22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.090
0.069
0.092
0.092
---
220
230
---
B
B
3RT19 24-5AN22
3RT19 24-5AL22
1
1
1 unit
1 unit
101
101
0.094
0.093
110
220
---
--100
200
120
240
110
220
B
C
C
C
3RT19 24-5AK62
3RT19 24-5AP62
3RT19 24-5AG62
3RT19 24-5AN62
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.090
0.094
0.094
0.094
kg
S0
3RT19 24-5A.02
S2
3RT10 34
3RT10 35,
3RT10 36,
3RT13 3.,
3RT15 3.
--
400
440
C
3RT19 24-5AR62
1
1 unit
101
0.091
24
42
48
110
-----
-----
B
B
B
B
3RT19 34-5AB02
3RT19 34-5AD02
3RT19 34-5AH02
3RT19 34-5AF02
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.105
0.087
0.095
0.116
230
400
---
---
B
B
3RT19 34-5AP02
3RT19 34-5AV02
1
1
1 unit
1 unit
101
101
0.107
0.115
-----
24
42
48
110
-----
B
B
B
B
3RT19 34-5AC22
3RT19 34-5AD22
3RT19 34-5AH22
3RT19 34-5AG22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.109
0.109
0.113
0.109
---
220
230
---
B
B
3RT19 34-5AN22
3RT19 34-5AL22
1
1
1 unit
1 unit
101
101
0.125
0.112
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 34-5AK62
3RT19 34-5AP62
3RT19 34-5AG62
3RT19 34-5AN62
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.110
0.117
0.083
0.083
--
400
440
B
3RT19 34-5AR62
1
1 unit
101
0.109
24
42
48
110
-----
-----
B
B
B
B
3RT19 35-5AB02
3RT19 35-5AD02
3RT19 35-5AH02
3RT19 35-5AF02
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.102
0.088
0.085
0.104
230
400
---
---
B
B
3RT19 35-5AP02
3RT19 35-5AV02
1
1
1 unit
1 unit
101
101
0.104
0.107
-----
24
42
48
110
-----
B
B
B
B
3RT19 35-5AC22
3RT19 35-5AD22
3RT19 35-5AH22
3RT19 35-5AG22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.106
0.106
0.107
0.103
---
220
230
---
B
B
3RT19 35-5AN22
3RT19 35-5AL22
1
1
1 unit
1 unit
101
101
0.105
0.107
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 35-5AK62
3RT19 35-5AP62
3RT19 35-5AG62
3RT19 35-5AN62
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.110
0.104
0.083
0.083
--
400
440
B
3RT19 35-5AR62
1
1 unit
101
0.110
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/127
3
Magnetic coils ¼ AC operation
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply voltage DT
Us
Screw terminals
AC
Order No.
DC
PG
Weight
per PU
approx.
Price
per PU
50 Hz 50/60 Hz 60 Hz
Size
PU
PS*
(UNIT,
SET, M)
kg
Type
V
V
V
V
3RT10 44
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 44-5AB01
3RT19 44-5AD01
3RT19 44-5AH01
3RT19 44-5AF01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.191
0.188
0.186
0.189
230
400
---
---
---
B
B
3RT19 44-5AP01
3RT19 44-5AV01
1
1
1 unit
1 unit
101
101
0.180
0.194
-----
24
42
48
110
-----
-----
B
B
B
B
3RT19 44-5AC21
3RT19 44-5AD21
3RT19 44-5AH21
3RT19 44-5AG21
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.182
0.199
0.195
0.184
---
220
230
---
---
B
B
3RT19 44-5AN21
3RT19 44-5AL21
1
1
1 unit
1 unit
101
101
0.179
0.184
110
220
---
--100
200
120
240
110
220
-----
B
B
B
B
3RT19 44-5AK61
3RT19 44-5AP61
3RT19 44-5AG61
3RT19 44-5AN61
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.193
0.130
0.185
--
400
440
--
B
3RT19 44-5AR61
1
1 unit
101
0.190
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 45-5AB01
3RT19 45-5AD01
3RT19 45-5AH01
3RT19 45-5AF01
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.169
0.166
0.180
0.170
230
400
---
---
---
}
C
3RT19 45-5AP01
3RT19 45-5AV01
1
1
1 unit
1 unit
101
101
0.169
0.173
-----
24
42
48
110
-----
-----
A
B
B
B
3RT19 45-5AC21
3RT19 45-5AD21
3RT19 45-5AH21
3RT19 45-5AG21
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.168
0.172
0.181
0.169
---
220
230
---
---
B
B
3RT19 45-5AN21
3RT19 45-5AL21
1
1
1 unit
1 unit
101
101
0.173
0.171
110
220
---
--100
200
120
240
110
220
-----
B
B
B
C
3RT19 45-5AK61
3RT19 45-5AP61
3RT19 45-5AG61
3RT19 45-5AN61
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.179
0.180
0.130
0.176
--
400
440
--
B
3RT19 45-5AR61
1
1 unit
101
0.170
-----
-----
-----
24
42
48
60
B
B
B
B
3RT19 34-5BB41
3RT19 34-5BD41
3RT19 34-5BW41
3RT19 34-5BE41
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.600
0.637
0.618
0.630
-----
-----
-----
110
125
220
230
B
B
B
B
3RT19 34-5BF41
3RT19 34-5BG41
3RT19 34-5BM41
3RT19 34-5BP41
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.605
0.632
0.617
0.720
-----
-----
-----
24
42
48
60
B
C
B
B
3RT19 44-5BB41
3RT19 44-5BD41
3RT19 44-5BW41
3RT19 44-5BE41
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.997
1.040
0.974
1.035
-----
-----
-----
110
125
220
230
B
B
B
B
3RT19 44-5BF41
3RT19 44-5BG41
3RT19 44-5BM41
3RT19 44-5BP41
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.970
0.960
1.004
0.956
Magnetic coils ¼ AC operation
3
S3
3RT19 44-5A.01
3RT10 45,
3RT10 46,
3RT13 4.,
3RT14 46,
3RT15 4.
3RT19 45-5A.01
Magnetic coils ¼ DC operation
S2
S3
3RT10 3.,
3RT13 3.,
3RT15 3.
3RT10 4.,
3RT13 4.,
3RT14 4.,
3RT15 4.
* You can order this quantity or a multiple thereof.
3/128
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply voltage DT
Us
Cage Clamp terminals
AC
Order No.
DC
50 Hz 50/60 Hz 60 Hz
Size
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
Type
V
V
V
V
3RT10 44
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 44-5AB02
3RT19 44-5AD02
3RT19 44-5AH02
3RT19 44-5AF02
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.130
0.171
0.185
230
400
---
---
---
B
B
3RT19 44-5AP02
3RT19 44-5AV02
1
1
1 unit
1 unit
101
101
0.185
0.190
-----
24
42
48
110
-----
-----
B
B
B
B
3RT19 44-5AC22
3RT19 44-5AD22
3RT19 44-5AH22
3RT19 44-5AG22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.183
0.130
0.190
0.185
---
220
230
---
---
B
B
3RT19 44-5AN22
3RT19 44-5AL22
1
1
1 unit
1 unit
101
101
0.130
0.178
110
220
---
--100
200
120
240
110
220
-----
B
B
B
B
3RT19 44-5AK62
3RT19 44-5AP62
3RT19 44-5AG62
3RT19 44-5AN62
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.188
0.188
0.123
0.123
kg
S3
3RT19 45-5A.02
3RT10 45,
3RT10 46,
3RT13 4.,
3RT14 46,
3RT15 4.
--
400
440
--
B
3RT19 44-5AR62
1
1 unit
101
0.177
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 45-5AB02
3RT19 45-5AD02
3RT19 45-5AH02
3RT19 45-5AF02
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.165
0.130
0.130
0.169
230
400
---
---
---
B
B
3RT19 45-5AP02
3RT19 45-5AV02
1
1
1 unit
1 unit
101
101
0.170
0.157
-----
24
42
48
110
-----
-----
B
B
B
B
3RT19 45-5AC22
3RT19 45-5AD22
3RT19 45-5AH22
3RT19 45-5AG22
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.166
0.130
0.174
0.161
---
220
230
---
---
B
B
3RT19 45-5AN22
3RT19 45-5AL22
1
1
1 unit
1 unit
101
101
0.170
0.163
110
220
---
--100
200
120
240
110
220
-----
B
B
B
B
3RT19 45-5AK62
3RT19 45-5AP62
3RT19 45-5AG62
3RT19 45-5AN62
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.171
0.130
0.123
0.123
--
400
440
--
B
3RT19 45-5AR62
1
1 unit
101
0.169
-----
-----
-----
24
42
48
60
B
C
B
B
3RT19 34-5BB42
3RT19 34-5BD42
3RT19 34-5BW42
3RT19 34-5BE42
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.625
0.557
0.652
0.633
-----
-----
-----
110
125
220
230
B
C
B
B
3RT19 34-5BF42
3RT19 34-5BG42
3RT19 34-5BM42
3RT19 34-5BP42
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.612
0.557
0.637
0.602
-----
-----
-----
24
42
48
60
B
B
B
B
3RT19 44-5BB42
3RT19 44-5BD42
3RT19 44-5BW42
3RT19 44-5BE42
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.034
0.805
1.009
1.016
-----
-----
-----
110
125
220
230
B
B
B
B
3RT19 44-5BF42
3RT19 44-5BG42
3RT19 44-5BM42
3RT19 44-5BP42
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.970
0.805
0.959
0.958
Magnetic coils ¼ DC operation
S2
S3
3RT19 44-5B0.42
3RT10 3.,
3RT13 3.,
3RT15 3.
3RT10 4.,
3RT13 4.,
3RT14 4.,
3RT15 4.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/129
3
Magnetic coils ¼ AC operation
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply
voltage
Us min ... Us max
DT
Order No.
Size
Type
PU
PS*
(UNIT,
SET, M)
Screw terminals
PG
Weight
per PU
approx.
Price
per PU
V AC/DC
kg
Withdrawable coils
Conventional operating mechanism
3RT10 5,
3RT14 5
3
S6
3RT19 55-5A
S10
S10
S12
3RT10 6,
3RT14 6
3RT12 6
Vacuum
contactor
3RT10 7,
3RT14 7,
3RT12 7
Vacuum
contactor
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
B
3RT19 55-5AB31
3RT19 55-5AD31
3RT19 55-5AF31
3RT19 55-5AM31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.620
0.576
0.591
0.568
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 55-5AP31
3RT19 55-5AU31
3RT19 55-5AV31
3RT19 55-5AR31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.580
0.579
0.569
0.613
500 ... 550
575 ... 600
B
B
3RT19 55-5AS31
3RT19 55-5AT31
1
1
1 unit
1 unit
101
101
0.610
0.605
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
C
3RT19 65-5AB31
3RT19 65-5AD31
3RT19 65-5AF31
3RT19 65-5AM31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.850
0.840
0.809
0.805
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 65-5AP31
3RT19 65-5AU31
3RT19 65-5AV31
3RT19 65-5AR31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.784
0.840
0.817
0.825
500 ... 550
575 ... 600
C
C
3RT19 65-5AS31
3RT19 65-5AT31
1
1
1 unit
1 unit
101
101
0.829
0.792
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
A
C
3RT19 66-5AB31
3RT19 66-5AD31
3RT19 66-5AF31
3RT19 66-5AM31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.060
0.995
1.003
0.650
220 ... 240
240 ... 277
380 ... 420
440 ... 480
A
C
B
C
3RT19 66-5AP31
3RT19 66-5AU31
3RT19 66-5AV31
3RT19 66-5AR31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.930
0.997
0.825
0.650
500 ... 550
575 ... 600
C
C
3RT19 66-5AS31
3RT19 66-5AT31
1
1
1 unit
1 unit
101
101
0.650
0.650
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
C
3RT19 75-5AB31
3RT19 75-5AD31
3RT19 75-5AF31
3RT19 75-5AM31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.425
1.255
1.311
1.200
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 75-5AP31
3RT19 75-5AU31
3RT19 75-5AV31
3RT19 75-5AR31
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.204
1.308
1.218
1.261
500 ... 550
575 ... 600
C
C
3RT19 75-5AS31
3RT19 75-5AT31
1
1
1 unit
1 unit
101
101
1.202
1.139
* You can order this quantity or a multiple thereof.
3/130
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply
voltage
Us min ... Us max
DT
Cage Clamp terminals
Order No.
Size
Type
V AC/DC
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
kg
Withdrawable coils
S6
S10
S12
3RT10 5,
3RT14 5
3RT10 6,
3RT14 6
3RT10 7,
3RT14 7,
3RT12 7
Vacuum
contactor
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
B
3RT19 55-5AB32
3RT19 55-5AD32
3RT19 55-5AF32
3RT19 55-5AM32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.649
0.576
0.591
0.568
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 55-5AP32
3RT19 55-5AU32
3RT19 55-5AV32
3RT19 55-5AR32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.568
0.579
0.569
0.613
500 ... 550
575 ... 600
B
B
3RT19 55-5AS32
3RT19 55-5AT32
1
1
1 unit
1 unit
101
101
0.610
0.605
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
B
3RT19 65-5AB32
3RT19 65-5AD32
3RT19 65-5AF32
3RT19 65-5AM32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.835
0.840
0.809
0.805
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 65-5AP32
3RT19 65-5AU32
3RT19 65-5AV32
3RT19 65-5AR32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.784
0.855
0.817
0.825
500 ... 550
575 ... 600
B
B
3RT19 65-5AS32
3RT19 65-5AT32
1
1
1 unit
1 unit
101
101
0.829
0.650
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
B
3RT19 75-5AB32
3RT19 75-5AD32
3RT19 75-5AF32
3RT19 75-5AM32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.425
1.255
1.311
1.100
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 75-5AP32
3RT19 75-5AU32
3RT19 75-5AV32
3RT19 75-5AR32
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
1.204
1.308
1.218
1.261
500 ... 550
575 ... 600
B
B
3RT19 75-5AS32
3RT19 75-5AT32
1
1
1 unit
1 unit
101
101
1.202
1.139
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/131
3
Conventional operating mechanism
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Rated control supply
voltage Us
DT
Order No.
Size
Type
PU
PS*
(UNIT,
SET, M)
Screw terminals
PG
Weight
per PU
approx.
Price
per PU
V AC/DC
kg
Withdrawable coils
Solid-state operating mechanism
3
For 24 V DC PLC output
S6
3RT10 5,
3RT14 5
S10
3RT19 55-5N...
S12
21 ... 27.3
96 ... 127
200 ... 277
C
B
B
3RT19 55-5NB31
3RT19 55-5NF31
3RT19 55-5NP31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.636
0.567
0.567
3RT10 6,
3RT14 6
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 65-5NB31
3RT19 65-5NF31
3RT19 65-5NP31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.808
0.926
0.813
3RT12 6
Vacuum
contactor
21 ... 27.3
96 ... 127
200 ... 277
B
C
C
3RT19 66-5NB31
3RT19 66-5NF31
3RT19 66-5NP31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.650
0.650
1.030
3RT10 7,
3RT14 7,
3RT12 7
Vacuum
contactor
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 75-5NB31
3RT19 75-5NF31
3RT19 75-5NP31
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.355
0.951
1.061
For 24 V DC PLC output/PLC relay output, with remaining lifetime indication (RLT)
(Withdrawable coil with lateral solid-state module)
S6
3RT10 5,
3RT14 5
96 ... 127
200 ... 277
B
B
3RT19 55-5PF31
3RT19 55-5PP31
1
1
1 unit
1 unit
101
101
0.570
0.955
S10
3RT10 6,
3RT14 6
96 ... 127
200 ... 277
B
B
3RT19 65-5PF31
3RT19 65-5PP31
1
1
1 unit
1 unit
101
101
1.368
1.176
S12
3RT10 7,
3RT14 7
96 ... 127
200 ... 277
B
B
3RT19 75-5PF31
3RT19 75-5PP31
1
1
1 unit
1 unit
101
101
1.100
1.424
With AS-Interface and remaining lifetime indication (RLT)
(Withdrawable coil with lateral solid-state module)
S6
3RT10 5,
3RT14 5
96 ... 127
200 ... 277
B
B
3RT19 55-5QF31
3RT19 55-5QP31
1
1
1 unit
1 unit
101
101
0.961
0.946
S10
3RT10 6,
3RT14 6
96 ... 127
200 ... 277
B
B
3RT19 65-5QF31
3RT19 65-5QP31
1
1
1 unit
1 unit
101
101
0.650
0.650
S12
3RT10 7,
3RT14 7
96 ... 127
200 ... 277
B
B
3RT19 75-5QF31
3RT19 75-5QP31
1
1
1 unit
1 unit
101
101
1.100
1.460
Rated control supply
voltage Us
DT
Cage Clamp terminals
For contactor
Order No.
Size
Type
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Price
per PU
V AC/DC
kg
Withdrawable coils
Solid-state operating mechanism
For 24 V DC PLC output
S6
3RT10 5,
3RT14 5
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 55-5NB32
3RT19 55-5NF32
3RT19 55-5NP32
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.654
0.567
0.567
S10
3RT10 6,
3RT14 6
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 65-5NB32
3RT19 65-5NF32
3RT19 65-5NP32
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.808
0.926
0.813
S12
3RT10 7,
3RT14 7,
3RT12 7
Vacuum
contactor
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 75-5NB32
3RT19 75-5NF32
3RT19 75-5NP32
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.355
0.951
1.061
* You can order this quantity or a multiple thereof.
3/132
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT,
3RH contactors and contactor relays
For contactor
Size
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
S2
3RT10 3 .
C
3RT19 36-7A
1
1 unit
101
0.112
S3
3RT10 4.,
3RT14 46
Arc chute, 3-pole
C
3RT19 46-7A
1
1 unit
101
0.299
S6
3RT10 54
3RT10 55
3RT10 56
B
B
B
3RT19 54-7A
3RT19 55-7A
3RT19 56-7A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.760
0.760
0.755
S10
3RT10 64
3RT10 65
3RT10 66
B
B
B
3RT19 64-7A
3RT19 65-7A
3RT19 66-7A
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.355
1.355
1.355
S12
3RT10 75
3RT10 76
B
B
3RT19 75-7A
3RT19 76-7A
1
1
1 unit
1 unit
101
101
1.643
1.650
S6
3RT14 56
B
3RT19 56-7B
1
1 unit
101
0.720
S10
3RT14 66
B
3RT19 66-7B
1
1 unit
101
1.350
S12
3RT14 76
B
3RT19 76-7B
1
1 unit
101
1.400
}
}
}
3RT19 34-6A
3RT19 35-6A
3RT19 36-6A
1
1
1
1 set
1 set
1 set
101
101
101
0.041
0.044
0.046
}
}
}
3RT19 44-6A
3RT19 45-6A
3RT19 46-6A
1
1
1
1 set
1 set
1 set
101
101
101
0.098
0.111
0.116
Contacts with fixing parts
For contactors with 3 main contacts
S2
3RT10 34
3RT10 35
3RT10 36
Main contacts (3 NO contacts) for
utilization category AC-3
(1 set = 3 movable and 6 fixed switching
elements with fixing parts)
S3
3RT10 44
3RT10 45
3RT10 46
S6
3RT10 54
3RT10 55
3RT10 56
}
}
}
3RT19 54-6A
3RT19 55-6A
3RT19 56-6A
1
1
1
1 set
1 set
1 set
101
101
101
0.239
0.281
0.295
S10
3RT10 64
3RT10 65
3RT10 66
}
}
}
3RT19 64-6A
3RT19 65-6A
3RT19 66-6A
1
1
1
1 set
1 set
1 set
101
101
101
0.443
0.513
0.555
S12
3RT10 75
3RT10 76
}
A
3RT19 75-6A
3RT19 76-6A
1
1
1 set
1 set
101
101
0.766
0.915
S3
3RT14 46
1
1 set
101
0.113
3RT14 56
3RT19 56-6D
1
1 set
101
0.285
S10
3RT14 66
3RT19 66-6D
1
1 set
101
0.543
S12
3RT14 76
B
Main contacts (3 NO contacts) for
utilization category AC-1
B
(1 set = 3 movable and 6 fixed switching
B
elements with fixing parts)
A
3RT19 46-6D
S6
3RT19 76-6D
1
1 set
101
0.899
3 vacuum interrupters with fixing parts
B
B
B
3RT19 64-6V
3RT19 65-6V
3RT19 66-6V
1
1
1
1 set
1 set
1 set
101
101
101
1.530
1.525
1.520
B
B
3RT19 75-6V
3RT19 76-6V
1
1
1 set
1 set
101
101
1.775
1.775
B
Main contacts (4 NO contacts) for
utilization category AC-1
C
(1 set = 4 movable and 8 fixed switching C
elements with fixing parts)
3RT19 36-6E
1
1 set
101
0.058
3RT19 44-6E
3RT19 46-6E
1
1
1 set
1 set
101
101
0.149
0.150
For 3RT12 vacuum contactors
S10
3RT12 64
3RT12 65
3RT12 66
S12
3RT12 75
3RT12 76
For contactors with 4 main contacts
S2
3RT13 26
S3
3RT13 44
3RT13 46
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/133
3
Arc chutes
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TB, 3TC, 3TF, 3TG, 3TK
contactors
■ Selection and ordering data
For contactor
Size
Version
Type
Rated control supply
voltage Us
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V AC
V DC
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
A
A
A
C
C
3TX7 402-3G
3TX7 402-3H
3TX7 402-3J
3TX7 402-3K
3TX7 402-3L
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.015
0.015
0.015
0.024
0.024
kg
Surge suppressors1) ¼ Varistors
3TC442) Varistors3)
With line spacer, for
mounting onto the
coil terminal
3
2
3TX7 402-3.
3TX7 462-3.
4 and 6 3TB50
and
3TC56
Varistors3)
For sticking onto the
contactor base or for
mounting separately
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
D
C
B
A
D
3TX7 462-3G
3TX7 462-3H
3TX7 462-3J
3TX7 462-3K
3TX7 462-3L
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.013
0.014
0.014
0.016
0.016
8 and
12
3TC52
and
3TC56
Varistors
For sticking onto the
contactor base or for
mounting separately
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
------
D
C
B
A
D
3TX7 462-3G
3TX7 462-3H
3TX7 462-3J
3TX7 462-3K
3TX7 462-3L
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.013
0.014
0.014
0.016
0.016
8 ... 12
3TB52
...
3TB56,
3TC52
and
3TC56
Varistors3)
-For separate screw
-connection or
-snapping onto 35 mm
standard mounting
rail
24 ... 70
B
70 ... 150 B
150 ... 250 B
3TX7 522-3G
3TX7 522-3H
3TX7 522-3J
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.083
0.078
0.084
14
3TF68
and
3TF69
Varistors3)
For DC economy
circuit; for snapping
onto the side of
auxiliary switches
----
24 ... 48
C
48 ... 127 C
127 ... 240 C
3TX7 572-3G
3TX7 572-3H
3TX7 572-3J
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.075
0.085
0.081
RC elements
For lateral snapping
onto auxiliary switch
or 35 mm standard
mounting rail
24 ... 48
--
-24 ... 70
C
B
3TX7 462-3R
3TX7 522-3R
1
1
1 unit
1 unit
101
101
0.084
0.080
48 ... 127
--
-70 ... 150
A
B
3TX7 462-3S
3TX7 522-3S
1
1
1 unit
1 unit
101
101
0.082
0.088
127 ... 240 -A
-150 ... 250 B
3TX7 462-3T
3TX7 522-3T
1
1
1 unit
1 unit
101
101
0.081
0.085
240 ... 400 -400 ... 600 --
A
C
3TX7 462-3U
3TX7 462-3V
1
1
1 unit
1 unit
101
101
0.084
0.086
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
------
B
B
B
B
B
3TX7 522-3R
3TX7 522-3S
3TX7 522-3T
3TX7 522-3U
3TX7 522-3V
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.080
0.088
0.085
0.085
0.086
24 ... 250
D
3TX7 462-3D
1
1 unit
101
0.014
3TX7 522-3.,
3TX7 572-3.
Surge suppressors ¼ RC elements
4
3TX7 462-3.,
3TX7 522-3.
6 ... 12
3TC48
3TB50,
3TC52
and
3TC56
RC elements
For lateral snapping
onto auxiliary switch
or 35 mm standard
mounting rail
Surge suppressors4) ¼ Diodes
6 ... 12
3TB52
...
3TB56,
3TC48
...
3TC56
-Diode assemblies
(diode and Zener
diode)
For DC solenoid
system, for sticking
onto the contactor
base or for mounting
separately
3TX7 462-3.
1) The surge suppressor is integrated as standard in the following
contactors: 3TF68 and 3TF69 (AC operation): varistor circuit.
2) The connection piece for mounting the surge suppressor must be bent
slightly.
3) Includes the peak value of the ripple voltage on the DC side.
4) Not for DC economy circuit.
* You can order this quantity or a multiple thereof.
3/134
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TB, 3TC, 3TF, 3TG, 3TK
contactors
For contactor
Size
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Solid-state compatible auxiliary switch blocks with screw terminals
3TF68
and
3TF69
3TC44 ...
3TC48
5TY7 561-1.
For mounting onto the side of
contactors.
For use in dusty atmosphere and solidstate circuits with rated operating
currents Ie/AC-14 and DC-13 from
1 mA to 300 mA at 3 V to 60 V.
With 1 changeover contact.
2nd auxiliary switch block, left or right
(replacement for 3TY6 561-1U,
3TY6 561-1V)
B
3TY7 561-1UA00
1
1 unit
101
0.053
}
3TX7 090-0D
1
1 unit
101
0.080
3
14
2 and 4
Coupling links for control by PLC
14
3TF68
and
3TF69
Operating range: 17 to 30 V DC.
Power consumption: 0.5 W at 24 V DC.
Fitted with varistor.
For technical specifications, see LV 1 T
For snapping onto the side of auxiliary
switch, with surge suppression
Terminal covers for protection against inadvertent contact with
exposed bar connections
14
3TF68
3TF69
B
3TX7 686-0A
1
1 set
101
0.410
B
3TX7 696-0A
1
1 set
101
0.402
M6
B
3TX6 506-3B
1
1 set
101
0.082
M8
B
3TX6 526-3B
1
1 set
101
0.140
M 10 B
3TX6 546-3B
1
1 set
101
0.260
C
3TX7 680-0D
1
1 unit
101
0.256
C
3TX7 680-0E
1
1 unit
101
0.080
C
3TX7 570-1E
1
1 set
101
0.675
For screwing onto free screw end on
middle connecting bar.
2 units required per contactor.
(1 set = 2 units)
3TX7
3TX6 526-3B
6
3TB50,
3TC48
8 and
SIRIUS
S6
3TB52
3RT1.5
10 and
14 and
SIRIUS
S10, S12
3TB54 ...
3TB56,
3TC52,
3TC56
3RT1.6
3RT1.7
Can be screwed on free screw end.
Covers one rail connection
(1 set = 6 units).
Links for paralleling (star jumper) ¼ 3-pole, without connection terminal1)
14
3TF68
Cover plate for link for paralleling
14
3TF68
A cover plate must be used in order to
protect against inadvertent contact
with exposed bar connections
(EN 50274).
Box terminals for laminated copper bars
Without auxiliary conductor connection (1 set = 3 units)
14
3TF68
With single covers for protection
against inadvertent contact
(EN 50274)
With auxiliary conductor connection (1 set = 3 units)
14
3TF68
With single covers for protection
against inadvertent contact
(EN 50274)
C
3TX7 570-1F
1
1 set
101
0.698
14
3TF69
Conductor cross-sections for auxiliary
conductors:
Solid 2 x (0.75 ... 2.5) mm2
Finely stranded with end sleeve
2 x (0.5 ... 2.5) mm2
Solid or stranded 2 x (18 ... 12) AWG
Tightening torque 0.8 ... 1.4 Nm
(7 ... 12 lb.in)
C
3TX7 690-1F
1
1 set
101
1.986
1) The link for paralleling can be reduced by one pole.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/135
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TB, 3TC, 3TF, 3TG, 3TK
contactors
For contactor
Remarks
Size
Rated control
DT
supply voltage Us
Type
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V DC
kg
Arc chutes
3TC44 17-0L..
With cutout for
mounting resistor
B
3TY2 442-0B
1
1 unit
101
0.164
2
3TC44
With series resistor 24
Without varistor
110
C
C
3TY6 443-0LB4
3TY6 443-0LF4
1
1
1 unit
1 unit
101
101
0.340
0.330
4
3TC48
24
110
C
C
3TY6 483-0LB4
3TY6 483-0LF4
1
1
1 unit
1 unit
101
101
1.170
1.116
6
3TB50
24
110
C
C
3TY6 503-0LB4
3TY6 503-0LF4
1
1
1 unit
1 unit
101
101
1.100
1.100
8
3TB52 and 3TC52
24
110
C
C
3TY6 523-0LB4
3TY6 523-0LF4
1
1
1 unit
1 unit
101
101
2.942
2.912
10
3TB54
24
110
C
C
3TY6 543-0LB4
3TY6 543-0LF4
1
1
1 unit
1 unit
101
101
1.100
1.100
12
3TB56 and 3TC56
24
110
C
C
3TY6 563-0LB4
3TY6 563-0LF4
1
1
1 unit
1 unit
101
101
1.100
1.100
2
3
Magnetic coils
All spare parts not mentioned above are identical to those for the standard
contactors.
Auxiliary Rated operating current
contacts Ie/AC-15/AC-14 at
Number
230/
220 V
400/
380 V
500 V
AC
A
A
A
Auxiliary contacts
Ident.
No.
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Version
N N N N
O C O C
kg
Snap-on auxiliary switch blocks for 3TF2 contactors ¼
with screw terminals
For assembling contactors with several auxiliary contacts
With 2, 4 and 5 auxiliary contacts according to DIN 50012
For 3TF2. 10 contactors (auxiliary contact 1 NO = 10E)
3TX4 4..-.A
1
4
3
2
11 E
-- 1 -- -- B
3TX4 401-1A
1
1 unit
101
0.033
3
4
3
2
22 E
1 2 -- -- B
3TX4 412-1A
1
1 unit
101
0.042
4
4
3
2
23 E
32 E
1 3 -- -- B
2 2 -- -- B
3TX4 413-1A
3TX4 422-1A
1
1
1 unit
1 unit
101
101
0.047
0.048
With 3 and 5 auxiliary contacts according to DIN 50005 for 3TF2
contactors
2
4
3
2
20
11
02
11; U
2
1
---
-1
2
--
---1
---1
B
B
B
B
3TX4 420-2A
3TX4 411-2A
3TX4 402-2A
3TX4 411-2G
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.038
0.038
0.037
0.037
4
4
3
2
40
31
22
22; 2 U
4
3
2
--
-1
2
--
---2
---2
B
B
B
B
3TX4 440-2A
3TX4 431-2A
3TX4 422-2A
3TX4 422-2G
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.047
0.047
0.047
0.047
For contactor
Rated control supply Time range
voltage Us
(minimum
times)
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
OFF-delay devices (with screw terminals) for 3TF2 contactors
For DC-operated contactors for bridging short-time
power failures up to 0.8 s
3TF2. ..-0BB4
24 V DC
0.25 s or
0.5 s
B
3TX4 490-1H
1
1 unit
101
0.083
* You can order this quantity or a multiple thereof.
3/136
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TB, 3TC, 3TF, 3TG, 3TK
contactors
For contactor
Rated control supply voltage Power
DT
Us
consumption of LED
at Us
Type
V AC
V DC
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
MW
kg
Surge suppressors for 3TF2 contactors ¼
For plugging onto contactors with and without
auxiliary switch blocks
Version without LED
3TF2. ..-0...,
3TF2. ..-1...
3TX4 490-3A
24 ... 48
48 ... 127
127 ... 240
24 ... 70
70 ... 150
150 ... 250
----
B
B
B
3TX4 490-3R
3TX4 490-3S
3TX4 490-3T
1
1
1
10 units
1 unit
1 unit
101
101
101
0.010
0.010
0.010
240 ... 400
400 ... 600
---
---
B
B
3TX4 490-3U
3TX4 490-3V
1
1
1 unit
1 unit
101
101
0.014
0.015
ˆ 48
48 ... 127
127 ... 240
24 ... 70
70 ... 150
150 ... 250
----
B
B
B
3TX4 490-3G
3TX4 490-3H
3TX4 490-3J
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.010
0.010
0.010
240 ... 400
400 ... 600
---
---
B
B
3TX4 490-3K
3TX4 490-3L
1
10 units
101
0.016
1
10 units
101
0.016
12 ... 250
--
B
3TX4 490-3A
1
1 unit
101
0.010
24 ... 250
--
B
3TX4 490-3B
1
1 unit
101
0.009
12 ... 24
24 ... 70
70 ... 150
150 ... 250
10 ... 120
20 ... 470
50 ... 700
160 ... 950
B
B
B
B
3TX4 490-4G
3TX4 490-4H
3TX4 490-4J
3TX4 490-4K
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.009
0.009
0.010
0.009
24 ... 70
70 ... 150
150 ... 250
20 ... 470 B
50 ... 700 B
160 ... 950 B
3TX4 490-4A
3TX4 490-4B
3TX4 490-4C
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.009
0.009
0.009
3TX4 490-1J
1
1 unit
101
0.011
A
3TX4 491-2A
1
5 units
101
0.032
D
3TX4 491-2K
1
1 unit
101
0.010
Varistors
3TF2. ..-0...,
3TF2. ..-1...
Noise suppression diodes
3TF2. ..-0...,
3TF2. ..-1...
--
Diode assemblies (diode and Zener diode)
For DC operation and short break times
3TF2. ..-0...,
3TF2. ..-1...
--
Version with LED
Varistors
3TF2. ..-0...,
3TF2. ..-1...
3TX4 490-4G
24 ... 48
48 ... 127
127 ... 240
--
Noise suppression diodes
3TF2. ..-0...,
3TF2. ..-1...
----
Additional load modules for 3TF2 contactors ¼
For plugging onto contactors with and without auxiliary switch blocks1)
For increasing the permissible residual current
and for limiting the residual voltage
3TF2. ..-0A..,
3TF2. ..-1A..
230/220, 50 Hz
-230, 60 Hz
230, 50/60 Hz
Operating range 0.8 ... 1.1 x Us
B
Plug-in bases with solder pin connectors for printed circuit boards ¼
width 45 mm for 3TF2 and 3TK2 contactors
For 3TF2 and 3TK2 contactors
With flat connectors 6.3 mm x 0.8 mm;
Rated insulation voltage Ui: 400 V (pollution degree 3);
Rated impulse withstand voltage Uimp: 6 kV;
Rated operating current Ie: 6 A;
s and U rated data:: max. 300 V, 6 A
3TF20 ..-3...,
3TF20 ..-7...,
3TK20 ..-3...,
3TK20 ..-7...
Release tools
3TF2. ..-7...,
3TK20..-7...
For releasing contactors from
3TX4 491-2A plug-in bases
1) Dimensions as for 3TX4 490-3 surge suppressor.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/137
3
RC elements
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TB, 3TC, 3TF, 3TG, 3TK
contactors
■ Accessories
For
contactor
Max. rated operating currents Ie/AC-1 Max. conductor DT
(at 55 °C) of the contactors
cross-sections
Type
A
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
mm2
Weight
per PU
approx.
kg
Links for paralleing (star jumpers)
3-pole, without connection terminal1)2)
3TG10
16 star jumpers can be reduced by
one pole
--
}
3RT19 16-4BA31
1 1 unit
101
0.003
25
}
3RT19 16-4BB31
1 1 unit
101
0.015
25
C
3RT19 16-4BB41
1 1 unit
101
0.015
3-pole, with connection terminal1)3)
3
3TG10
40
4-pole, with connection terminal1)4)
3TG10
50
1) The links for paralleling can be reduced by one pole. The rated operating
currents apply to each pole. The parallel connections are insulated.
2) Replacement for 3TX4 490-2C.
3) Replacement for 3TX4 490-2A.
4) Replacement for 3TX4 490-2B.
* You can order this quantity or a multiple thereof.
3/138
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TH contactor relays
■ Selection and ordering data
Version
Rated control supply
voltage Us
AC
DC
V
V
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
3TX7 402-3.
Noise suppression diodes
-With line spacer, for mounting
onto the coil terminal
24 ... 250
A
3TX7 402-3A
1
1 unit
101
0.147
--
24 ... 250
A
3TX7 402-3D
1
1 unit
101
0.015
24 ... 48
Varistors2)
With line spacer, for mounting 48 ... 127
onto the coil terminal
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
A
A
A
C
C
3TX7 402-3G
3TX7 402-3H
3TX7 402-3J
3TX7 402-3K
3TX7 402-3L
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.015
0.015
0.015
0.024
0.024
RC elements
24 ... 48
With line spacer, for mounting 48 ... 127
onto the coil terminal
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
A
A
A
C
C
3TX7 402-3R
3TX7 402-3S
3TX7 402-3T
3TX7 402-3U
3TX7 402-3V
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.025
0.025
0.023
0.024
0.024
--
B
3TX4 210-0P
1
1 unit
101
0.002
For mounting directly to contactor coil
without surge suppressor
A
3TX4 090-0C
1
1 unit
101
0.055
For mounting directly to contactor coil
with surge suppressor
A
3TX4 090-0D
1
1 unit
101
0.057
Diode assemblies
(diode and Zener diode) with
line spacer,
DC operation, for mounting
onto the coil terminal
Covers
For switch position indicator
--
Coupling links for control by PLC for 3TH4 contactor relays
Operating range: 17 ... 30 V DC
Power consumption: 0.5 W at 24 V DC
3TX4 090
mounted to contactor
1) The opening delay of the NO contact and the closing delay of the
NC contact are increased if the contactor coils are attentuated against
voltage peaks (noise suppression diode 6 to 10 times; diode assemblies
2 to 6 times, varistor +2 to 5 ms).
For
contactor
Type
Version
2) Includes the peak value of the ripple voltage on the DC side.
DT Order No.
Rated control
Time
supply voltage range
Us AC 50/60 Hz (minimum
times)
V
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
s
kg
ON-delay devices
3TH42/
3TH43
NTC thermistors 220 ... 230
Time tolerance
+ 100 %, -50 %
0.1
B
3TX4 180-0A
1
1 unit
101
0.013
3TX4 180-0A
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/139
3
Surge suppressors1) for 3TH4 contactor relays
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TH contactor relays
For contactor
Rated control
OFF delay
supply voltage Us
Type
AC
50/60 Hz
DC
V
V
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
s
kg
3
OFF-delay devices for bridging short-time
power failures (up to 1.2 s)
3TH42 ..-0BF4
3TH43 ..-0BF4
110
0.15 or 0.3
A
3TX4 701-0AN1
1
1 unit
101
0.169
3TH42 ..-0BM4
3TH43 ..-0BM4
220
0.6 or 1.2
A
3TX4 701-0AN1
1
1 unit
101
0.169
3TH42 ..-0BP4
3TH43 ..-0BP4
230
0.6 or 1.2
A
3TX4 701-0AN1
1
1 unit
101
0.169
0.4 or 0.8
A
3TX4 701-0BB4
1
1 unit
101
0.168
3TH42 ..-0BB4
3TH43 ..-0BB4
3TX4 701-0AN1
24
Contacts Rated operating current
Ie/AC-15/AC-14 at
Contacts
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
230/ 400/ 500 V 690/ Ident. No. Version
220 V 380 V AC
660 V acc. to
EN 50011
Number A
A
A
A
NO NC NO NC
kg
Snap-on auxiliary switch blocks for 3TH20 contactor relays ¼
with screw terminals
With 8 contacts according to EN 50011,
For snapping onto contactor relays with 4 NO,
Ident. No. 40E (3TH20 40-0...)
4
4
3
2
--
3TX4 440-0A
80 E
71 E
62 E
4
3
2
-1
2
----
----
B
B
B
3TX4 440-0A
3TX4 431-0A
3TX4 422-0A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.047
0.047
0.047
53 E
44 E
1
--
3
4
---
---
B
B
3TX4 413-0A
3TX4 404-0A
1
1
1 unit
1 unit
101
101
0.048
0.047
With 6 and 8 contacts according to EN 50005
4
4
3
2
--
40 E
31 E
22 E
22; 2U
4
3
2
--
-1
2
--
---2
---2
B
B
B
B
3TX4 440-2A
3TX4 431-2A
3TX4 422-2A
3TX4 422-2G
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.047
0.047
0.047
0.047
2
4
3
2
--
20 E
11 E
02 E
11; U
2
1
---
-1
2
--
---1
---1
B
B
B
B
3TX4 420-2A
3TX4 411-2A
3TX4 402-2A
3TX4 411-2G
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.038
0.038
0.037
0.037
For contactor
Rated control supply Time range
voltage Us
(minimum
times)
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
OFF-delay devices (with screw terminals)
For DC-operated contactors for bridging short-time power
failures up to 0.8 s
3TH2. ..-0BB4
24 V DC
0.25 s or
0.5 s
B
3TX4 490-1H
1
1 unit
101
0.083
3TX4 490-1A
1
1 unit
101
0.085
3TH2. ..-0BF4
110 V AC, 50/60 Hz
0.1 s or 0.2 s B
3TH2. ..-0BM4,
3TH2. ..-0BP4
220 V AC, 50/60 Hz
0.4 s or 0.8 s
3TX4 490-1A
* You can order this quantity or a multiple thereof.
3/140
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Accessories for 3TH contactor relays
For contactor
Rated control supply voltage Power
DT
Us
consumption of LED
at Us
Type
V AC
V DC
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
MW
kg
Surge suppressors1)
For plugging onto contactors with and without
auxiliary switch blocks
Version without LED
3TX4 490-3A
24 ... 48
48 ... 127
127 ... 240
24 ... 70
70 ... 150
150 ... 250
----
B
B
B
3TX4 490-3R
3TX4 490-3S
3TX4 490-3T
1
1
1
10 units
1 unit
1 unit
101
101
101
0.010
0.010
0.010
240 ... 400
400 ... 600
---
---
B
B
3TX4 490-3U
3TX4 490-3V
1
1
1 unit
1 unit
101
101
0.014
0.015
ˆ 48
48 ... 127
127 ... 240
24 ... 70
70 ... 150
150 ... 250
----
B
B
B
3TX4 490-3G
3TX4 490-3H
3TX4 490-3J
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.010
0.010
0.010
240 ... 400
400 ... 600
---
---
B
B
3TX4 490-3K
3TX4 490-3L
1
1
10 units
10 units
101
101
0.016
0.016
12 ... 250
--
B
3TX4 490-3A
1
1 unit
101
0.010
24 ... 250
--
B
3TX4 490-3B
1
1 unit
101
0.009
12 ... 24
24 ... 70
70 ... 150
150 ... 250
10 ... 12
20 ... 470
50 ... 700
160 ... 950
B
B
B
B
3TX4 490-4G
3TX4 490-4H
3TX4 490-4J
3TX4 490-4K
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.009
0.009
0.010
0.009
24 ... 70
70 ... 150
150 ... 250
20 ... 470 B
50 ... 700 B
160 ... 950 B
3TX4 490-4A
3TX4 490-4B
3TX4 490-4C
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.009
0.009
0.009
3TX4 490-1J
1
1 unit
101
0.011
3TX4 491-2A
1
5 units
101
0.032
Varistors
3TH2. ..-0...
Noise suppression diodes
3TH2. ..–0...
--
Diode assemblies (diode and Zener diode)
For DC operation and short break times
3TH2. ..–0...
--
Version with LED
Varistors
3TH2. ..-0...
24 ... 48
48 ... 27
127 ... 240
--
3TX4 490-4G
Noise suppression diodes
3TH2. ..-0...
----
Additional load modules (residual current)
For plugging onto contactors with and without auxiliary switch blocks
For increasing the permissible residual current
and for limiting the residual voltage of SIMATIC
semiconductor outputs
3TH2. ..-0A
230/220, 50 Hz
-230, 60 Hz
-230, 50/60 Hz
-Operating range 0.8 ... 1.1 x Us
B
Plug-in bases with solder pin connectors for printed circuit boards,
width 45 mm
For 3TH2 contactor relays;
With flat connectors 1 x 6.3 mm ... 0.8 mm;
Rated insulation voltage Ui: 400 V (pollution degree 3);
Rated impulse withstand voltage Uimp: 6 kV;
Rated operating current Ie: 6 A;
s and U rated data: max. 300 V, 6 A
3TH20 ..-3,
3TH20 ..-7
A
1) The opening delay of the NO contact and the closing delay of the NC
contact are increased if the contactor coils are attenuated against voltage
peaks (noise suppression diode 6 to 10 times; diode assemblies 2 to
6 times, varistor +2 to 5 ms).
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/141
3
RC elements
3TH2. ..-0...
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Spare parts for 3TB, 3TC, 3TF, 3TK contactors
■ Selection and ordering data
For contactor
Contacts
Version
Version
Size
Type
NO NC NC
3TB50
1
1
--
1
--
1
1
1
--
1
1
--
1
--
1
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Auxiliary switch blocks
3
6
8 ... 12
3TB52
...
3TB56
3TY6 561-1A
B
3TY6 501-1AA00
1
1 unit
101
0.053
C
3TY6 501-1E
1
1 unit
101
0.054
B
3TY6 561-1A
1
1 unit
101
0.074
B
3TY6 561-1B
1
1 unit
101
0.075
C
3TY6 561-1E
1
1 unit
101
0.076
C
C
C
C
3TY6 503-0B..
3TY6 523-0B..
3TY6 543-0B..
3TY6 563-0B..
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.230
0.400
0.400
0.560
B
C
C
C
3TY6 502-0A
3TY6 522-0A
3TY6 542-0A
3TY6 562-0A
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.751
1.177
1.456
1.580
(1 set = 3 moving and B
6 fixed contacts)
B
B
B
3TY6 500-0A
3TY6 520-0A
3TY6 540-0A
3TY6 560-0A
1
1
1
1
1 set
1 unit
1 set
1 set
101
101
101
101
0.283
0.359
0.529
0.756
Auxiliary switch
block, left or right
(replacement for
3TY6 501-1A/-1B)
Auxiliary switch
block, right
Auxiliary switch
block, left
Auxiliary switch
block, right
Auxiliary switch
block, right
Magnetic coils
DC operation
6
8
10
12
3TB50
3TB52
3TB54
3TB56
6
8
10
12
3TB50
3TB52
3TB54
3TB56
3TY6 5.
Arc chutes
1 arc chute, 3-pole
3TY6 502-0A
Contacts with fixing parts
In order to ensure reliable operation of the contactors,
only original replacement contacts from Siemens
should be used.
6
8
10
12
3TB50
3TB52
3TB54
3TB56
3TY6 520-0A
For rated control supply voltages for coils, see page 3/146.
* You can order this quantity or a multiple thereof.
3/142
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Spare parts for 3TB, 3TC, 3TF, 3TK contactors
For
contactor
Size
Auxiliary
contacts
Version
Type
NO
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
NC
kg
2 and 4
3TB44, 1
3TC48
1
Auxiliary switch block, left B
or right (replacement for
3TY6 501-1A/-1B)
3TY6 501-1AA00
1
1 unit
101
0.053
4
3TC48
1
2nd auxiliary switch block, C
left1)
2nd auxiliary switch block, C
right1)
3TY6 501-1K
1
1 unit
101
0.055
3TY6 501-1L
1
1 unit
101
0.047
Auxiliary switch block, left
Auxiliary switch block,
right
2nd auxiliary switch block,
left1)
2nd auxiliary switch block,
right1)
B
B
3TY6 561-1A
3TY6 561-1B
1
1
1 unit
1 unit
101
101
0.074
0.075
C
3TY6 561-1K
1
1 unit
101
0.077
C
3TY6 561-1L
1
1 unit
101
0.078
B
B
B
B
3TY2 440-0A
3TY2 480-0A
3TY2 520-0A
3TY2 560-0A
1
1
1
1
1 set
1 set
1 set
1 set
101
101
101
101
0.065
0.100
0.237
0.424
C
C
C
C
3TY2 442-0A
3TY2 482-0A
3TY2 522-0A
3TY2 562-0A
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.166
0.503
1.205
2.129
C
C
C
C
3TY6 443-0B..
3TY6 483-0B..
3TY6 523-0B..
3TY6 563-0B..
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.300
1.000
2.300
4.800
C
C
C
C
3TY7 403-0A..
3TY6 483-0A..
3TY6 523-0A..
3TY6 566-0A..
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.100
0.200
0.350
0.650
1
8 and 12 3TC52, 1
3TC56
1
3TY6 561-1A
Contacts with fixing parts
In order to ensure reliable operation of the contactors, only
original replacement contacts from Siemens should be
used.
2
4
8
12
3TC44
3TC48
3TC52
3TC56
2
4
8
12
3TC44
3TC48
3TC52
3TC56
(1 set = 2 moving and 2 fixed switching
elements)
3TY2 520-0A
Rated control supply voltages for coils, see page 3/146.
Arc chutes
1 arc chute,
2-pole
3TC2 48
Magnetic coils
DC operation
2
4
8
12
3TC44
3TC48
3TC52
3TC56
AC operation
2
4
8
12
3TC44
3TC48
3TC52
3TC56
1) Can only be mounted on AC-operated contactors.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/143
3
Auxiliary switch blocks
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Spare parts for 3TB, 3TC, 3TF, 3TK contactors
For
contactor
Version
Rated control DT
supply
voltage Us
Type
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V AC/DC
kg
Varistors
3TC7
For sticking onto the
contactor base
24
110
C
C
3TX2 746-2F
3TX2 746-2G
1
1
1 unit
1 unit
101
101
0.011
0.011
Main contacts (1 set)
For 3TC78: 2 units required
per contactor
B
3TY2 740-0E
1
1 set
101
0.356
3TC74
4 NO +4 NC
B
3TY2 741-2J
1
1 unit
101
0.265
3TC78
Auxiliary contact, left, with
2 NO +2 NC
Auxiliary contact, right, with
2 NO +2 NC
C
3TY2 781-2C
1
1 unit
101
0.186
C
3TY2 781-2D
1
1 unit
101
0.184
For 3TC78: 2 units required
per contactor
C
3TY2 742-0C
1
1 unit
101
3.916
DT
Order No.
Contacts with fixing parts
3
3TC7
Auxiliary switch blocks
Arc chutes
3TC7
For contactor
Contacts
Version
Size
NO NC
Type
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
NC
kg
Auxiliary switch blocks
With screw terminals
14
3TF68
and
3TF69
3TY7 561-1.
1
1
--
1st auxiliary switch
block, left or right
Replacement for:
3TY7 561-1A/-1B.
B
3TY7 561-1AA00
1
1 unit
101
0.048
1
--
1
Auxiliary switch block,
left or right
B
3TY7 561-1EA00
1
1 unit
101
0.048
1
1
--
2nd auxiliary switch
block, left or right
Replacement for:
3TY7 561-1K/-1L.
B
3TY7 561-1KA00
1
1 unit
101
0.050
3TY7 681-1G
1
1 unit
101
0.050
For coil reconnection with DC economy circuit,
with screw terminals
14
3TF68
and
3TF69
For contactor
Size
--
--
1
Auxiliary contact block C
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Magnetic coils
AC operation
14
3TF68
3TF69
The coils are fitted as standard with
C
varistors against overvoltage. The coil is C
supplied with switch-on electronics.
3TY7 683-0C..
3TY7 693-0C..
1
1
1 unit
1 unit
101
101
0.650
0.650
3TY7 683-0D..
3TY7 693-0D..
1
1
1 unit
1 unit
101
101
0.560
0.560
3TY7 680-0B
3TY7 690-0B
1
1
1 set
1 set
101
101
3.490
3.638
DC operation · DC economy circuit
14
3TF68
3TF69
3TY7.
C
Reversing contactors are required for
size 14 contactors:
C
Contactor type 3TF68 and 3TF69
Reversing contactor 3TC44
(70 mm wide, 85 mm high)
The coils are supplied without reversing
contactor.
Vacuum interrupters
In order to ensure reliable operation of the contactors, only
original replacement interrupters from Siemens should be
used.
14
3TF68
3TF69
3 vacuum interrupters with mounting
parts
For rated control supply voltages for coils, see page 3/146.
B
B
For solid-state compatible auxiliary switch blocks,
see page 3/135.
* You can order this quantity or a multiple thereof.
3/144
Siemens LV 1 · 2006
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Spare parts for 3TB, 3TC, 3TF, 3TK contactors
Version
Rated control
supply voltage
Us
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V AC
kg
Reversing contactors (3TC44)
Complete with resistor and 1 m connecting 110 ... 120
lead and connector for 3TF68 ..-.Q,
220 ... 240
3TF69 ..-.Q
380 ... 420
C
C
C
3TY7 684-0QG7
3TY7 684-0QL7
3TY7 684-0QV7
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.000
1.000
1.000
For 3TF68 ..-.Q
110 ... 120
220 ... 240
380 ... 420
C
C
C
3TY7 683-0QG7
3TY7 683-0QL7
3TY7 683-0QV7
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.700
1.509
1.460
For 3TF69 ..-.Q
110 ... 120
220 ... 240
380 ... 420
C
C
C
3TY7 693-0QG7
3TY7 693-0QL7
3TY7 693-0QV7
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.650
1.455
1.431
For rated control supply voltages for coils, see page 3/146.
For contactor
Version
Type
Rated control supply
voltage Us
For solid-state compatible auxiliary switch blocks,
see page 3/135.
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
V AC
kg
Surge suppressors ¼ RC elements
3TK10 to 3TK13
24 ... 48
110 ... 415
D
B
3TK19 30-0A
3TK19 30-0B
1
1
1 unit
1 unit
101
101
0.033
0.039
3TK14 to 3TK17
48 ... 110
220 ... 600
C
B
3TK19 34-0C
3TK19 34-0D
1
1
1 unit
1 unit
101
101
0.042
0.044
B
B
B
B
3TK19 40-0A
3TK19 42-0A
3TK19 44-0A
3TK19 46-0A
1
1
1
1
2 units
2 units
2 units
2 units
101
101
101
101
0.141
0.113
0.190
0.203
B
3TK19 10-3A
1
1 unit
101
0.055
B
3TK19 10-3B
1
1 unit
101
0.055
Terminal covers
3TK10, 3TK11
3TK12, 3TK13
3TK14, 3TK15
3TK17
For mounting onto contactors
Auxiliary switch blocks
3TK1
1st auxiliary switch block, left or 1 NO + 1 NC
right
2nd auxiliary switch block, left or 1 NO + 1 NC
right
Locking devices
3TK10, 3TK11
3TK12, 3TK13
For mechanical interlocking of
2 identical contactors, auxiliary
contacts 2 NC
B
B
3TK19 20-0A
3TK19 22-0A
1
1
1 unit
1 unit
101
101
0.144
0.143
3TK14, 3TK15,
3TK17
Mechanical interlock, including
mounting plate
B
3TK19 24-0A
1
1 unit
101
6.750
1 arc chute, 4-pole
D
D
D
D
3TK19 50-0A
3TK19 51-0A
3TK19 52-0A
3TK19 53-0A
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.055
0.065
1.250
1.384
D
D
D
3TK19 54-0A
3TK19 55-0A
3TK19 57-0A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.001
3.681
3.785
D
D
D
3TK19 70-0A..
3TK19 72-0A..
3TK19 74-0A..
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.350
0.450
0.950
D
D
D
D
3TK19 60-0A
3TK19 61-0A
3TK19 62-0A
3TK19 63-0A
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.254
0.275
0.573
0.582
D
D
D
3TK19 64-0A
3TK19 65-0A
3TK19 67-0A
1
1
1
1 unit
1 unit
1 unit
101
101
101
2.354
2.356
2.311
Arc chutes
3TK10
3TK11
3TK12
3TK13
3TK14
3TK15
3TK17
Magnetic coils
3TK10, 3TK11
3TK12, 3TK13
3TK14, 3TK15,
3TK17
Contacts with fixing parts
3TK10
3TK11
3TK12
3TK13
4 moving and 8 fixed contacts
3TK14
3TK15
3TK17
For rated control supply voltages for coils, see page 3/146.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2006
3/145
3
Magnetic coils for main contactor, with rectifier bridge
Accessories and Spare Parts
For 3T Contactors and Contactor Relays
Spare parts for 3TB, 3TC, 3TF, 3TK contactors
For contactor type
3TC44
3TC48
3TC5
3TF68/69
3TK10/11/12/13
3TK14/15/17
Coil type
3TY7 403-0A..
3TY6 483-0A..
3TY6 523-0A..
3TY6 566-0A..
3TY7 683-0C..
3TY7 693-0C..
3TK19 70-0A..
3TK19 72-0A..
3TK19 74-0A..
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
AC operation · Coils for 50 Hz
24 V AC
110 V AC
230/220 V AC
240 V AC
B0
F0
P01)
U0
B0
F0
P01)
U0
-F0
P01)
--
-----
B03)
F03)
P03)
U03)
-F03)
P03)
U03)
3
AC operation · Coils for 50/60 Hz
24 V AC
110 V AC
120 V AC
220 V AC
230 V AC
C2
G2
K2
N2
L2
------
------
------
------
------
110 V ... 132 V AC
200 V ... 240 V AC
230 V ... 277 V AC
380 V ... 460 V AC
500 V ... 600 V AC
------
------
------
F7
M7
P72)
Q7
S7
------
------
For contactor type
3TC4
3TB5, 3TC5
3TF68/69
Coil type
3TY6 443-0B..
3TY6 483-0B..
3TY6 503-0B..
3TY6 523-0B..
3TY6 543-0B..
3TY6 563-0B..
3TY7 683-0D..
3TY7 693-0D..
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
DC operation
24 V DC
48 V DC
60 V DC
110 V DC
125 V DC
220 V DC
230 V DC
B4
W4
E4
F4
G4
M4
P4
B4
--F4
-M4
--
B4
--F4
G4
M4
P4
1) Operating range at 220 V or 380 V:
0.85 to 1.15 x Us;
lower operating range limit according to IEC 60947.
2) Lower operating range limit at 220 V:
0.85 x Us according to IEC 60947.
3) Rated control supply voltages Us:
50 Hz
60 Hz
B0:
24 V
-F0:
110 V
120 V
P0:
220 V to 230 V
240 V (only 3TK19 74)
U0:
230 V to 240 V
--
7
3/146
Siemens LV 1 · 2006