UL Report for Contactors 3RT104.pdf

File E31519
Project 97ME15320
Issued:
*Revised:
June 18, 1997
November 19, 1999
Report on
MAGNETIC MOTOR CONTROLLERS
Siemens AG
92220 Amberg, Fed. Rep. Germany
Copyright © 1997, 1999 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File E31519
Vol. 8
Sec. 2
Vol. 5
Sec. 5
and Report
Page 1
Issued: 1997-06-18
Revised: 2005-11-11
DESCRIPTION
PRODUCT COVERED:
USL, CNL – Type No. 3RT10, 3RT13, 3RT14 or 3RT16 followed by 44, 45, 46
or 47, followed by –1, -2, –3 or -6 followed by A, B, C, D, E, F, G, H, J, K,
M, P, Q, R, S or X followed by a character and a number followed by 0, 1, 2,
3, 4, 5, 6, 8 or 9 may be followed by -0LA2, -0GA0 or any Suffix Letters
and/or numbers.
USL, CNL - Accessory - Terminal Kit Type 3RT1946-4G
Auxiliary Terminal Kit Type 3RT1946-4F
Terminal housing, Types 3RT1946-4EA followed by 1 or 2
GENERAL:
These devices are open types 3 or 4 pole contactors for use in
industrial applications.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL – Indicates Investigated to Canadian National Standard C22.2 No.
14-M95.
Note: CNL = Canadian National Standards – Listed.
USL = United States Standards – Listed.
RATINGS:
Horsepower 3RT1044
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
5 hp
10 hp
15 hp
-
-20 hp
25 hp
50 hp
60 hp
56 A
62.1 A
68 A
65 A
62 A
-516 A
562 A
515 A
494 A
1-ph
3-ph
FLA
LRA
7 1/2 hp
15 hp
15 hp
-
-25 hp
30 hp
60 hp
75 hp
80 A
78.2 A
80 A
77 A
77 A
-646 A
674 A
618 A
618 A
Horsepower 3RT1045
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
File E31519
Vol. 8
Vol. 5
and Report
Sec. 2
Sec. 5
Page 2
Issued: 1997-06-18
Revised: 2005-06-02
Horsepower 3RT1046
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
10 hp
15 hp
20 hp
-
30 hp
30 hp
75 hp
100 hp
100 A
92 A
80 A
96 A
99 A
-776 A
674 A
773 A
749 A
Horsepower 3RT1044 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1 ph, 1 pole
3 hp
7 1/2 hp
-
1 ph, 3 pole
3 hp
7 1/2 hp
-
3-ph
15 hp
30 hp
40 hp
FLA
54 A
42 A
40 A
41 A
LRA
449
337
337
330
A
A
A
A
Horsepower 3RT1045 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1 ph, 1 pole
3 hp
10 hp
-
1 ph, 2 pole
3 hp
10 hp
-
3-ph
20 hp
40 hp
50 hp
FLA
54 A
54 A
52 A
52 A
LRA
449
449
412
412
A
A
A
A
3-ph
25 hp
50 hp
60 hp
FLA
68 A
68 A
65 A
62 A
LRA
562
562
515
494
A
A
A
A
Horsepower 3RT1046 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1 ph, 1 pole
5 hp
10 hp
-
1 ph, 2 pole
5 hp
15 hp
-
Horsepower 3RT1446 (3 NO main contacts)
Voltage
3-ph
FLA
LRA
230/240 V
460/480 V
575/600 V
15 hp
30 hp
40 hp
42 A
40 A
41 A
337 A
337 A
330 A
1-ph
3-ph
Current
15
17
35
43
26
30
60
75
72
72
72
72
Capacitive Switching 3RT1647
Voltage
200/208
230/240
460/480
575/600
V
V
V
V
kVar
kVar
kVar
kVar
kVar
kVar
kVar
kVar
A
A
A
A
File E31519
Vol. 8
Sec. 2
Vol. 5
Sec. 5
and Report
Main Contacts:
Page 2A
Issued: 1997-06-18
Revised: 2005-06-02
General Purpose Rating
-type 3RT1044: 600 V ac, 90 A
-type 3RT1045 or 3RT1046: 600 V ac, 105 A
Auxiliary Contacts:
1-, 2-, or 4-pole auxiliary contact blocks type
3RH1921 are top or side mounted, for ratings
refer to File E44653 Vol. 11, Sec. 2 or Vol. 12
Sec. 3. The auxiliary blocks are available as
factory assembled (removable or not removable
design) or available as separate devices for
individual arrangements.
Coil Ratings:
24 through 600 V ac
24 through 250 V dc
Definite Purpose:
Electric Heating, 600 V ac, 250,000 c.
3RT1044:
90 A
3RT1045, 3RT1046: 105 A
For
For
For
For
Type
Type
Type
Type
3RT1344:
3RT1346:
3RT1446:
3RT1446,
AC
AC
AC
DC
Resistance 600
Resistance 600
controlled: AC
controlled: AC
V, 100 A
V, 110 A
Resistance 600 V, 140 A
Resistance 600 V, 131 A
Short Circuit Ratings:
Type No.
Fuse
3RT1044
3RT1045
3RT1046/3RT1446
3RT1647
1
2
Note:
Note:
max
max
max
max
250
300
350
250
A
A
A
A
Bkr
max
max
max
-
Circuit
TM1
250 A
300 A
400 A
Breaker
Bkr I2
max 50 A
max 100 A
max 150 A
-
Note:
600
600
600
600
V
V
V
V
3RV104/Size
Size
Volt.
[A]
[V]
63
480
63
600
75
480
75
600
100
480
75
600
S33
Short
[kA]
65
25
65
25
65
25
For Siemens UL Listed Combination Motor Controller Type 3RV104 (Size
S3) covered in File E156943.
NEMA Ratings:
*
Voltage
UL Listed inverse time circuit breakers
UL Recognized instantaneous trip circuit breakers manufactured by
Siemens, Type ED63A...
High Capacity Short Circuit Ratings:
Type No.
Fuse Rating
CB Rating (Bkr TM)
Size
Volt.
Short
Size
Volt.
Short
[A]
[V]
[kA]
[A]
[V]
[kA]
3RT1044
125
480
65
175
480
65
600
175
600
25
3RT1045
150
480
65
200
480
65
600
200
600
25
3RT1046
200
480
65
250
480
65
600
250
600
25
3
Short
Circuit
5 kA
10 kA
10 kA
10 kA
3RT1046 meets ratings for NEMA Size 3
File E31519
Vol. 8
Sec. 2
Vol. 5
Sec. 5
and Report
Page 2B
Issued: 1997-06-18
Revised: 2005-06-02
Short Circuit Rating for Contactor, Fuse, Overload Relay combination according
To UL 60947-4-1, for type “2” co-ordination.
Contactor
Overload
Relay
Fuse
Class
LPJ
[A]
Voltage
for High
Fault
Current
High Fault
Current [kA]
according to
UL60947-4-1
Standard Fault
Current [kA]
according to
UL60947-4-1 at
600V
3RT1044
3RT1044
3RT1045
3RT1046
3RU1146-4J
3RU1146-4K
3RU1146-4L
3RU1146-4M
90
125
175
200
600
600
600
600
100
100
100
100
5
5
10
10