ETC VXS400-3

Compact Single and Three Phase Torque
Vector Systems for Small Three Phase Motors
JAGUAR VXS
Sensorless Vector Variable Frequency Inverters 0.4kW to 4.0kW
■ High performance Torque Vector Control
■ Over 200% torque at 1 Hz
■ Footprint filters for EMC compliance
■ User friendly auto tuning
■ Ultra compact IP40 enclosure
■ Fast torque response
■ Low motor noise profile
■ User programmable I/O
■ Integral detachable keypad
■ Single and three phase versions
■ RS485 communications port (optional)
■ Renowned IMO 5 year warranty
5
Electrical specifications
Single Phase Input
Three Phase Input
VXS20-1
VXS40-1
VXS75-1
VXS150-1
VXS220-1
VXS40-3
VXS75-3
VXS150-3
Motor rating (kW)
0.2
0.37
0.55
0.75
1.5
2.2
0.37
0.55
0.75
1.5
2.2
4.0
Maximum rated
O/P current (A)
1.5
3.0
5.0
8.0
11.0
1.6
2.5
3.7
5.5
9.0
100% Rated I/P current ARMS
2.95
4.1
7.2
14.0
20.0
1.3
2.2
4.3
6.0
9.8
Jaguar VXS order codes
200 - 240 AC, ±10%, 1 phase
Input voltage
VXS220-3 VXS400-3
380 - 480 AC, +10 to -15%, 3 phase
Input frequency
50 - 60 Hz, ±5%
Output voltage
AC, 0 - VINPUT PWM
Output frequency
0.2 - 400 Hz
PRICE
INFORMATION
AND ORDERING
General specifications
Heat loss at minimum
carrier frequency (W)
23
45
56
81
129
42
51
67
97
120
Weight (Kg)
1.1
1.6
1.7
2.7
2.8
1.8
1.8
2.7
2.7
3.2
Enclosure rating
Cooling method
Ambient temperature
Relative humidity
Vibration
Altitude
IP40
Natural
Convection
Fan
Assisted
Natural
Convection
-10 to +50˚C (remove covers >+40˚C)
20 to 95% non condensing
5.9 m/s2 (0.6G) max
1000 metres max
Fan Assisted
Jaguar VXS
Connection diagram
WARNING! This equipment must be earthed
C
F
240V
1Ø
or
415V
3Ø
50/60 Hz
CAUTION: Do not short circuit. Terminal
P24 to terminal 11, CM or CME
L1
U
PANEL
CONTROL
F
L2
(L)
F
L3
(N)
PRG MODE
Hz
A
r/min m/min
PRICE
INFORMATION
AND ORDERING
RUN
V
V
PRG
RESET
RUN
FUNC
DATA
STOP
M
W
NOTE: Figures in brackets are for
single phase models
Frequency reference
current input
(4~20 mA DC)
(+)
(–)
C1
GND(PE)
GND(P
E)
DC REACTOR (OPTIONAL)
P1
LINK
13
Manual frequency
setting potentiometer
(10KΩ/1W)
12
(+)
EXTERNAL
BRAKE RESISTOR (OPTIONAL)
11
DB
P24
+24V
Forward operation
and stop command
FWD
Reverse operation
and stop command
REV
Coast - to - stop
command
30A
30B
BX
30C
Alarm reset
RST
X1
Multistep
frequency select
FMP
X2
X3
Function
extension input
From P24*
terminal
From THR
terminal
Alarm output (any fault)
(Relay shown in power ON or OFF and healthy state)
PULSE
To CM terminal
FMA
X4
To terminal 11
CM
External alarm
input
THR
Digital
frequency
meter
YIE
CMC
Analog
frequency
meter
(10 V/1 mA DC)
Programmable output
Common for YIE
*
NOTE: Under no circumstances should the above guide be considered sufficient for the attainment of relevant EMC emission
limits. Please consult the product manual for full information regarding compliance.
Power Terminals
Symbol
Terminal Name
Description
L1, L2, L3
Main input
power terminals
For connecting 3 phase power supply (VXS - 3 only)
L, N
Main input
power terminals
For connecting single phase power supply (VXS - 1 only)
U, V, W
Power output
terminals
For 3 phase AC induction motor
P1, (+)
DC reactor
terminals
(+), DB
External brake
resistor terminals
Connection for brake resistor to increase braking torque
GND (PE)
Earth terminal
Safety electrical earth
Optional DC reactor terminals for improving
power factor (fitted with shorting link)
Jaguar VXS
Control circuit terminals
Purpose
Analog
Frequency
Setting
Terminal
Terminal Name
Description
11
Speed reference
0V common
For use with terminals 12, 13, C1 and FMA
12
Reference input
0 - 10V DC input, impedance = 22 KΩ
13
Potentiometer supply
+10V DC power supply for 1 KΩ speed control potentiometer.
Output 10mA max.
C1
Current loop input
4 - 20mA input, impedance = 250Ω
FWD
Forward and stop
command
FWD - P24 Closed – Motor runs forward
Open – Motor stops
REV
Reverse and stop
command
REV - P24 Closed – Motor runs in reverse
Open – Motor stops
Coast - to - Stop
command
BX - P24 Closed – Output inhibited instantaneously
Open – Normal
External trip
• THR - P24 Closed – Normal
Open – Trips output instantaneously
or
• THR - P24 Closed – Normal
Open – Data protected
BX
THR
or
Enable/disable
data edit mode
Control
Inputs
RST
X1, X2, X3
Trip/Alarm reset
If RST - P24 is closed for ≥100mS following a trip condition,
the inverter will reset
Preset speeds
Combinations of X1, X2, X3 - P24 will call for preset
frequencies to be output
X4
Function
extension
Depending upon the setting of function No. 43
terminal acts as – Acc 2 / Dec 2 pattern select
– Extension to 15 preset speeds
– 2nd motor V/F profile
– FWD/REV latch for 3-wire I/P
P24
+24V DC supply
Internal 24V DC supply for control inputs
CM
Common terminal
Common terminal for FMP and digital inputs
FMA
Analogue output
Output frequency, current, torque or load factor can be selected,
0 - 10V DC, 1mA maximum
Up to 2 metres of cable is recommended for connection
to this terminal
FMP
Digital output
YIE
Programmable
output
Selectable for:1) Inverter running 2) Frequency level detected
3) Frequency hysteresis band reached
4) Undervoltage trip 5) Torque limiting 6) Auto Restart
Maximum 27V DC, 50 mA
Common terminal
Used for YIE output only
Fault relay
Normally 30B - 30C closed with power OFF or ON, with drive
output healthy
30A - 30C closes on fault. Rated 250V, 0.3A
Meter
Outputs
Control
Outputs
If both FWD
and REV are
opened or closed,
then the inverter
output stops
CMC
30A
30B
30C
Output proportional to frequency of motor
6 kHz maximum, fully scalable
Jaguar VXS
Dimensions (mm)
VXS40-1 and VXS75-1 (Single Phase)
VXS40-3 and VXS75-3 (Three Phase)
Remote mountable keypad
with optional cable
2 holes, 5mm
65
6
PANEL
CONTROL
6
5
*
30
PRG MODE
Hz
A
r/min m/min
RUN
RUN
FUNC
DATA
STOP
*
30
Removable
side-cover
V
PRG
RESET
*
PANEL
CONTROL
138
150
PRG MODE
Hz
A
r/min m/min
PRG
RESET
RUN
FUNC
DATA
STOP
5
45
*
128
75
140
109
*Centrelines of 3 cable entry holes, 22mm dia.
VXS150-1 and VXS220-1 (Single Phase)
VXS150-3 and VXS220-3 (Three Phase)
2 holes, 5mm
6
PANEL
CONTROL
6
5
*
PRG MODE
Hz
A
r/min m/min
RUN
RUN
FUNC
DATA
STOP
*
30
138
150
6
5
*
30
Removable
side-cover
V
PRG
RESET
188
200
5
*
71
100
134
*Centrelines of 3 cable entry holes, 22mm dia.
VXS400-3 (Three Phase)
2 holes, 5mm
6
PANEL
CONTROL
6
5
*
188
200
30
67.5
RUN
V
85
6
5
12.3 7.9
PRG MODE
Hz
A
r/min m/min
RUN
PRG
RESET
RUN
FUNC
DATA
STOP
*
30
Removable
side-cover
V
*
138
150
5
6
5
*
86
115
149
*Centrelines of 3 cable entry holes, 22mm dia.
PRICE
INFORMATION