SCHURTER DA22

DA22
Power Entry Modules with Line Filter
www.schurter.com/pg06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, for PCB Mounting
Standard- or Medical-Filter and
-Fuse drawer
C14
70° C
Description
-Panel Mount:
Screw-on mounting on PCB, from rear-side
-3 Functions:
Appliance Inlet, Fuseholder for fuse-links 5 x 20 mm, Line filter in standard and medical version
-PCB solder terminals
-Alternative: version for panel mounting KFA Characteristics
-Ultra-compact design
-All single elements are already wired
-For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
-Qualified for use in equipment according IEC/EN 60950
Other versions on request
-Fixing on PCB with self-tapping screws 3 mm or pre-inserted nuts M3
-Fuse drawer 1-pole, plus spare fuse case
-Fuse drawer 2-pole, with shorting bar
-Medical version M80, 220 nF X capacitors
-Class X1- and Y1-capacitors for enhanced withstand voltage
-Protection class II, 70°C
Approvals
-VDE License Number: 40001522
-UL License Number: E72928
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125/250 VAC;
50/60 Hz ¹⁾
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
For PCB mounting ; Additional for
ground terminal: Quick connect terminals 6.3 x 0.8 mm angled to pin axis
Screw-on mounting: max 3 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Filter
MTBF
C14 acc. to IEC/EN 60320-1
UL 498 CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.4 W (2-pole) per
pole
Admissible power acceptance at higher ambient temperature see derating
curves
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 2'000'000 h acc. to MIL-HB-217 F
1) UL appovals: 1-pole versions up to 10 A, 2-pole versions up to 8 A
EMC Products
DA22
Power Entry Modules with Line Filter
www.schurter.com/pg06
Dimensions
57.6 mm
46.8
57.6
5.8
47.6
4.2
5.
1
39
4.5
2.5
2.8
4 10.5
32.5
36.1
37.6
19.5
6
34
32.7
8.1
1.25
30.4±0.10
0.85
39 ±0.15
47.05
16.2
6.3x0.8
6.05 ±0.10
3.
4.
4
29
1.6
16.2±0.15
38 ±0.20
32.7±0.20
R
4
6.6
38
41
1.6
+0
.
0 10
1.6
+0
.
0 10
+0
.
0 10
3.6
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard Version with Bleed Resistor
2 x 10
100
2.2
1
2
Standard Version with Bleed Resistor
2x4
100
2.2
1
4
Standard Version with Bleed Resistor
2 x 1.5
100
2.2
1
6
Standard Version with Bleed Resistor
2 x 0.8
100
2.2
1
8
Standard Version with Bleed Resistor
2 x 0.6
100
2.2
1
10
Standard Version with Bleed Resistor
2 x 0.3
100
2.2
1
1
Medical Version (M5)
2 x 10
100
-
1
2
Medical Version (M5)
2x4
100
-
1
4
Medical Version (M5)
2 x 1.5
100
-
1
6
Medical Version (M5)
2 x 0.8
100
-
1
8
Medical Version (M5)
2 x 0.6
100
-
1
10
Medical Version (M5)
2 x 0.3
100
-
1
Diagrams
Standard version with bleed resistor
and Medical version M80
1-/2-pole
Medical version M5
1-/2-pole
PE’’
PE’’
1)
L
PE
N
1) Line
2) Load
L1
F1
R
F2
Cx
L2
L’
Cy
Cy
PE’
1)
2)
L
PE
N
L1
F1
R
F2
L’
PE’
Cx
L2
2)
N’
N’
1) Line
2) Load
EMC Products
3.
6
3.
4
34.4 ±0.10
R
4.
2 ±0
.0
5
4
2.2
R
R
30
DA22
Power Entry Modules with Line Filter
www.schurter.com/pg06
Derating Curves
1-pole
Admissible power acceptance in Watt
1.5
I = 1.0 In
I = 0.7 In
1.0
I = < < In
0.5
0.0
0
20
40
60
80
100
Admissible power acceptance in Watt per pole
2-pole
2.0
Ambient air temperature Ta °C
1.4
1.2
1.0
I = 1.0 In
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
Standard version
- - - - differential mode _____ common mode
1A
2A
8A
10 A
Medical version (M5)
1A
2A
8A
10 A
4A
6A
4A
6A
EMC Products
DA22
Power Entry Modules with Line Filter
www.schurter.com/pg06
Variants
Rated Current
[A]
Filter-Type
Fuseholder
Comment
Order Number
1
Standard Version with Bleed Resistor
1-pole
-
DA22.1111.11
2
Standard Version with Bleed Resistor
1-pole
-
DA22.2111.11
4
Standard Version with Bleed Resistor
1-pole
-
DA22.4111.11
6
Standard Version with Bleed Resistor
1-pole
-
DA22.6111.11
8
Standard Version with Bleed Resistor
1-pole
-
DA22.8111.11
10
Standard Version with Bleed Resistor
1-pole
1)
DA22.9111.11
1
Standard Version with Bleed Resistor
2-pole
-
DA22.1121.11
2
Standard Version with Bleed Resistor
2-pole
-
DA22.2121.11
4
Standard Version with Bleed Resistor
2-pole
-
DA22.4121.11
6
Standard Version with Bleed Resistor
2-pole
-
DA22.6121.11
8
Standard Version with Bleed Resistor
2-pole
-
DA22.8121.11
10
Standard Version with Bleed Resistor
2-pole
1)
DA22.9121.11
1
Medical Version (M5)
2-pole
-
DA22.1321.11
2
Medical Version (M5)
2-pole
-
DA22.2321.11
4
Medical Version (M5)
2-pole
-
DA22.4321.11
6
Medical Version (M5)
2-pole
-
DA22.6321.11
8
Medical Version (M5)
2-pole
-
DA22.8321.11
10
Medical Version (M5)
2-pole
1)
DA22.9321.11
1) UL approvals: versions with 1-pole fuseholder are approved up to 10 A, 2-pole versions up to 8 A.
Packaging unit 20 Pcs Required Accessory
Description
Fusedrawer 2
Fusedrawer with and without Voltage Selector Insert
Fingergrip, 2-pole
4301.1401
Extra-Safe, 2-pole
4301.1403
Fingergrip, 1-pole
4301.1405
Extra-Safe, 1-pole
4301.1407
...
Accessories
Cord retaining kits
Cord retaining strain relief
Flat head, H
4700.0008
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
5092
Appliance Outlet further types to DA22
EMC Products
DA22
Power Entry Modules with Line Filter
www.schurter.com/pg06
Connector Overview complete
IEC Connector C15, Rewireable, Straight
0101
IEC Connector C15A, Rewireable, Straight
0102
IEC Connector C15A, Rewireable, Straight
0102-G
IEC Connector C15A, Rewireable, Angled
0112
IEC Connector C13, Rewireable, Angled
4012
Connector further types to DA22
...
Power Cord Overview complete
Power Cord with IEC Connector C13, Angled
0311
Power Cord with IEC Connector C13, Angled
3011
Power Cord with IEC Connector C13, Angled
3012
Power Cord with IEC Connector C13, Angled
3013
Power Cord with IEC Connector C13
3020
Power Cord further types to DA22
...
The specifications, descriptions and illustrations indicated in this document
are based on
EMC Products
current information. All content is subject to modifications and amendments.