Timers Delay on Operate Type DAA01, PAA01 • • • • • • • Time range 0.1 s to 100 h Knob selection of time range Knob adjustable time setting Automatic start Repeatability: ≤ 0.2% Output: 8 A SPDT or 2 x 8 A SPDT relays For mounting on DIN-rail in accordance with DIN/EN 50 022 or Plug-in • 22.5 Euronorm or 36 mm plug-in module housing • Combined AC and DC power supply • LED indication for relay status and power supply ON DAA01 PAA01 Product Description Ordering Key Multi-voltage delay on operate timer with 7 selectable time ranges within 0.1 s and Housing Function Type Item number Output Power supply 100 h. For mounting on DINrail (DAA01) or plug-in (PAA01). DAA 01 C M24 Type Selection Mounting Output Housing Supply: 24 VDC and 24 to 240 VAC DIN-rail 1 x SPDT 2 x SPDT 1 x SPDT 2 x SPDT D-Housing DAA01CM24 P-Housing PAA01CM24 Plug-in DAA01DM24 PAA01DM24 Time Specifications Time ranges Knob selectable Setting accuracy Repeatability Time variation Within rated power supply Within ambient temperature Reset Power supply interruption Supply: 24 to 240 VAC/DC Output Specifications 0.1 to 1 s 1 to 10 s 6 to 60 s 60 to 600 s 0.1 to 1 h 1 to 10 h 10 to 100 h ≤ 5% ≤ 0.2% ≤ 0.05%/V ≤ 0.2%/°C ≥ 200 ms Output Rated insulation voltage Contact Ratings (AgSnO2) Resistive loads AC 1 DC 12 Small inductive loads AC 15 DC 13 Mechanical life Electrical life Operating frequency Dielectric strength Dielectric voltage Rated impulse withstand voltage 1 or 2 x SPDT relays 250 VAC (rms) µ 8 A @ 250 VAC 5 A @ 24 VDC 2.5 A @ 250 VAC 2.5 A @ 24 VDC ≥ 30 x 106 operations ≥ 105 operations (at 8 A, 250 V, cos ϕ = 1) < 7200 operations/h 2 kVAC (rms) 4 kV (1.2/50 µs) Supply Specifications Power supply Rated operational voltage through terminals: (DAA01C) A1, A2 or (PAA01C) 2, 10 (DAA01D) (PAA01D) A1, A2 or 2, 10 Overvoltage cat. III (IEC 60664, IEC 60038) 24 VDC ± 15% and 24 to 240 VAC + 10% -15%, 45 to 65 Hz 24 to 240 VAC/DC + 10% - 15%, 45 to 65 Hz Specifications are subject to change without notice (24.10.05) Voltage interruption Rated operational power AC supply DC supply ≤ 10 ms 4 VA 1.5 W 1 DAA01, PAA01 General Specifications Time Setting ≤ 100 ms Power ON delay Reaction time Instantaneous contact Indication for Power supply ON Output relays ON < 20 ms from power ON Centre knob: Time setting on relative scale: 1 to 10 with respect to the chosen range Lower knob: Setting of time range LED, green LED, yellow (flashing when timing) (EN 60529) IP 20 3 (DAA01), 2 (PAA01) (IEC 60664) -20° to +60°C, R.H. < 95% -30° to +80°C, R.H. < 95% Environment Degree of protection Pollution degree Operating temperature Storage temperature Housing dimensions DIN-rail version Plug-in version Weight Screw terminals (DAA01) Tightening torque Mode of Operation 22.5 x 80 x 99.5 mm 36 x 80 x 94 mm Approx. 130 g The yellow LED, flashing when timing, is ON as soon as the relay turns ON. Max. 0.5 Nm according to IEC EN 60947 UL, CSA RINA (DAA01 only) Yes Electromagnetic Compatibillity According to EN 61000-6-2 According to EN 61000-6-3 According to EN 61812-1 Approvals CE marking EMC Immunity Emission Timer Specifications The second relay can operate as instantaneous or delayed changeover contact. The selection is made by a DIPswitch placed under the plastic door on the device’s front. is connected. At the end of the set delay the relay operates and does not release until the power supply is interrupted for at least 200 ms. If the power supply is interrupted for at least 200 ms before the relay operates the time is set to zero and the circuit is ready for a new time period. The set delay period begins as soon as the power supply Wiring Diagrams DAA01 PAA01 L(+) A1 A2 N(-) m 18 26 16 15 L(+) m 28 25 DAA01C... DAA01D... DAA01C... DAA01D... DAA01D... DAA01D... 2 10 N(-) m 4 m 3 1 8 9 11 PAA01C... PAA01D... PAA01D... PAA01C... PAA01D... PAA01D... Operating Diagram Power supply Relay 1 ON T OFF Relay 2 (Delayed) ON T OFF Relay 2 ON (Istantaneous) OFF LED 2 Specifications are subject to change without notice (24.10.05) DAA01, PAA01 Dimensions DIN-rail Plug-in 94 90 63 28.5 Specifications are subject to change without notice (24.10.05) 80 36 63 99.5 83.5 80 22.5 28.5 3