LEM DCVT1000

VPN = 1000 V
Voltage Transducer DCVT 1000/SP1
For the electronic measurement of DC voltages with a galvanic
isolation between the primary circuit (high voltage) and the secondary
circuit (electronic circuit).
Preliminary
All Data are given with a R L = 10 kΩ
Electrical data
VPN
VPmax
VP
RP
RL
VOUT
Primary nominal voltage
Primary voltage measuring range
Not measurable overload
Primary input resistance
Load impedance
Output voltage 1)
IC
Vd
Ve
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz,1 min
R.m.s. voltage for partial discharge
extinction @ 10pC
1000
V DC
56 .. 1400
V DC
3000 (1s/h)
VDC
appr. 97.5
MΩ
10
kΩ
VOUT = a x VP - b V
a = 0.01 ± 0.5 %
b = 0.3 ± 0.1
appr. 1
mA/kV
5.5
kV
2.2
kV
ε
Overall Accuracy @ VPN, TA = +25°C
Overall Accuracy @ VPN, TA = -15 .. +70°C
Linearity @ TA = 25°C
Response time @ 10% of VPN
L
tr
Ambient operating temperature
Ambient storage temperature
Creepage distance
Clearance distance
Comparative tracking index (Group )
UL94 classification
Potting material
Mass
m
according to UL 94-V0
• Included primary resistor
Advantages
• Low power consumption
• Very good linearity
• Low thermal drift
• High immunity to external
• Low disturbance in common mode
±1.5
±3.5
< ±0.5
< 100
%
%
%
µs
General data
TA
TS
dCp
dCl
CTI
• Self-Powered
• Insulated plastic case recognized
interference
Accuracy-Dynamic performance data
XG
XG
Features
Applications
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
-15 .. +70
°C
-25 .. +85
°C
> 10
mm
none
600
V
V0
Polyurethane resin, UL94 V0
appr. 400
g
• DC voltage monitoring
This is customer specific model.
Utilization restricted to agreed specifications.
Notes :
1)
See graphical presentation of transfer function overleaf.
041005/0
LEM Components
www.lem.com
Dimensions DCVT 1000/SP1 (in mm. 1mm = 0.0394 inch)
Front view
100
2m
48
2m
Left view
100
28
HT+
HT-
124
40
138
63
Top view
Vout
d6.5
13.7
30
9.7
a
0.26
0
-b
Mechanical characteristics
• General tolerance
• Transducer fastening
Distance between holes
56
1000
1400
Vp
Vout=a*Vp-b --> Vp=(Vout+b)/a
a=0.01 +/-0.5%
b=0.3 +/-0.1
Remark
± 1 mm
2 holes ∅ 6.5 mm
124 mm
• IS is positive when VP is applied on terminal +HT.
• Connection
Primary
Secondary
2m halogen free 1 x 1.5 mm2 cable
2m halogen free 2 x 0.5 mm2 + EMC screen
• Recommended fastening torque
2.2 Nm or 1.62 Lb-Ft.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.