FC SERIES MANUAL LOADER (STEP OUTPUT TYPE) DATA SHEET PND1 The FC series manual loader is available in two types, a manual control type and a remote control type used in combination with a compact controller. This instrument is equipped with a solid state indicator and pushbutton operation circuit to provide easy readouts and handling for process operation by man-machine communication. It can be directly connected to a thermocouple, resistance bulb or 4 to 20mA input optionally. FEATURES 1. High reliability The manual loader is a solid state instrument having few mechanical parts. The indicator and other units which formerly consisted of mechanical parts are also designed with solid state circuits to provide high reliability. 2. Application of international standards The instrument is compact, and the external dimensions comply with international IEC. The power supply and signal also comply with IEC standards (24V, 1 to 5V DC). Operation on 100V or 200V AC power supply is possible. 3. Front panel operation Process values, valve position input, etc. can be read accurately from the digital display on the panel front. Parameter setting and manual operation are also possible from the front of the panel. FUNCTIONAL DIAGRAM PV Linearize Square-root extraction MV Manual mode output (M) Filter Compensated process value signal (KPV) Process value input (PV) M Limiter Valve position input (W) Manipulated output (pulse width) (PO) A External MV input (PI) W/V H MV L High alarm output (H) Manual mode command (SMV) KPV ALM Low alarm output (L) EDS11-104e Date Jan. 27, 1999 PND1 SPECIFICATIONS 1. Input signal (1) Process value input signal: One point of signal select from the following inputs Voltage input signal 1 to 5V DC Input resistance, more than 1MΩ Allow. error ± 0.2%/FS* Current input signal 4 to 20mA DC 24V DC power supplied to transmitter during AC operation Allow. error ± 0.2%/FS* 10mV DC span or more Basic contact compensating function Allow. error ± 0.5%/FS* 50°C span or more Allow. error ± 0.5%/FS* Thermocouple input I+ I0 Type I – J:0 to 600°C K:0 to 1200°C E:0 to 800°C R:0 to 1600°C Resistance bulb input JPt100/Pt100 –50 to 500°C Note: * FS: Full scale (2) Valve position input signal: 1 point Voltage input signal W0 1 to 5V DC Resistance input signal W+ 50 to 1000Ω 3-wire system potentiomenter Allow. error ± 0.5/FS* W0 span** W– Input resistance, 1MΩ or more Allow. error ± 0.5%/FS* Note: ** : Basic design: 10 to 100 to 10Ω, others should be specified. (3) Pulse width input signal: 1 set PI+ PI– Pulse width input signal Contact input (photo-coupler insulation) ON 0V, OFF 24V (input current, approx. 11mA/24V DC) (4) Digital input signal: 1 point Manual mode command SMV Contact input (photo-coupler insulation) ON 0V, OFF 24V (input current, approx. 11mA/24V DC) 2. Output signal (1) Control output signal: 1 set Pulse width output signal P0+ P0– Open-collector output (phone-coupler insulation) Output rating, 30V x 0.1A DC, max. (2) Operation mode indication Indicating method: LED (red and green) Red: M Green: A (3) Numerical indication, setting Indication method: LED (red), name in 3 digits + number in 5 digits (negative sign included) Indication contens: Process variable (engineering unit), high/ low alarm, limiter value etc. Indication contents are select with F/S, , , keys on front panel. Setting method: By using F/S , , , , ST, keys on front panel (4) Operating functions Manual operating method: By use of , , buttons on front panel Auto operating method: By pulse width input signal (5) Operation mode selection By using front panel A/M pushbutton A← Balanceless bumpless → M selection (6) Alarm function High/low limit alarm can be set in engineering units for process value input signal. 4. Power failure processing function Power failure detection: Control output OFF at power failure detection. During power failure: Data backed up by capacitor when power failure occurs within 5 minutes. Initial value of data stored in non-volatile memory (last for more than 10 years at ambient temperature of 50°C or less). Power failure recovery time: Initial or continuous start set for power failure within 5 minutes. Recovery from power failure lasting longer than 5 minutes is done by initial. (2) Analog output signal: 1 point Note: Control mode at initialization set. M: Manual mode or A: Auto mode Compensated KPV 1 to 5V DC Output resitance, 1Ω or less process value Allow. error ± 0.2%/FS signal (3) Digital output signal: 4 points Fault output FLT Manual mode output M High alarm output H Low alarm output L Open-collector output (photo-coupler insulation) Output rating, 30V x 0.1A DC, max. 5. Self-diagnosis functions Process value input signal abnormality: FLT indicator lights and FLT contact output turns ON. Fault contents indication: Cause of fault is indicated numerically on numerical indicator on the front panel. 6. Other functions 3. Indication, setting, operating functions (1) Bar graph indication Data protective function by use of pass code 7. Operating conditions Power supply: Indication method PV indicator MV indicator LED (red) LED (red) No. of indicating segments 101 + 2 51 + 2 Indication range 0 to 100%, linear 0 to 100%, linear Indication resolution 1 %/FS 2%/FS Scale length 100mm 50mm Indicating mode 0 to 100% bar graph indication, 0 to 100% reverse bar graph indication, 0 to 100% dot indication Selected from the following 3 types 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (87 to 264V/47 to 63Hz AC) Power consumption: Approx. 11W (DC) Approx. 20VA (AC) Dielectric strength: 1500V AC, 1 min. Insulation resistance: 100MΩ or more at 500V DC Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Nameplate: 100 (H) x 72 (W) mm, white acryl Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC (DIN) standards Mass {weight}: Approx. 2.9kg Mounting method: Flush with indoor panel; vertical mounting is standard. Mounting on tilted surface possible (angle "α") CODE SYMBOLS 1 2 3 4 5 6 7 8 9 5 - PND1 A B C D E F G W Operating method M type A-M type A B Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) 1 2 3 Valve position input signal Voltage input signal (1 to 5V DC) Resistance input signal (50 to 1000Ω span) (Note 1) 1 2 α=0° to 90° Notes: (1) Basic: 10 to 100 to 10Ω, others should be specified. (2) Symbols of resistance bulbs are as follows. JPt100 ... JIS C 1604-1981 Pt100 ... IEC Pub751-1983 (JPt/Pt changeover is possible with front key.) Finish color: Munsell N1.5 for front panel and case Range of delivery:Manual loader and mounting bracket OUTLINE DIAGRAM Description Process value input signal 1 to 5V DC 4 to 20mA DC J thermocouple 10mV DC span or K thermocouple more, with reference contact compensating E thermocouple function R thermocouple Resistance bulb, JPt100, 3-wire, 50°C span or more Resistance bulb, Pt100, 3-wire, 50°C span or more (Unit:mm) Terminal Panel thickness 8mm or less 16 144 Terminal cover 140 36 Support bracket 355 Mounting bracket 200min. 72 Panel cutout 138 +1 0 250min. When mounting "n" units 138 +1 0 200min. When mounting one unit 68 +0.7 0 (72.2n – 4) +1 0 No. of units n≥ –2 PND1 CONNECTION DIAGRAM Block terminal (M4 screws) Process value input I+ (PV) I– (SC) DO (Manual mode) M AO (Compensated PV signal) 11 12 13 14 DI (Manual mode command) SMV 15 AC 16 31 Io 32 PI+ 33 PI– 34 FLT 35 AC Pulse width input DO (FLT output) KPV W0 (Valve position input) AI, AO Common bus PO (Control output) DO (High alarm) DO (Low alarm) Instrument power – (24V DC, AC power) Instrument power (AC) – DI, DO 24V power Earth 51 71 52 72 53 73 W0 54 74 W+ SC 55 75 W– PO+ 56 76 SC PO– 57 77 H 58 78 L 59 79 PC* 60 80 PCD 61 81 VP* G 62 82 VPD W– (Valve position input) W+ (Valve position input) AI, AO Common bus + Instrument power (24V DC, AC power) + DI, DO 24V power Note: * Symbols for AC instrument power are VPO, PCO. Output : Approx. 24V DC (0.1A max.) Process value input terminal connections 1 to 5V DC The 5th digit of code symbols: "A" 4 to 20mA DC The 5th digit of code symbols: "B" + Thermocouple The 5th digit of code symbols: C,D,E,F 11 31 + – 12 + 11 Resistance bulb The 5th digit of code symbols: G,W 31 – – 12 + 11 – 12 + + 11 – – 12 + 11 – 12 31 31 + 4 to 20mA DC power The 5th digit of code symbols: "B" – 31 PC 60 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan