FC SERIES COMPACT CONTROLLER S (CONTINUOUS OUTPUT TYPE) DATA SHEET PNA1 Compact controller S (fixed function type) is a compact single-loop controller using a microprocessor. It accepts uniform signals, and signals from a thermocouple and resistance bulbs as input, and includes sufficient control and computation functions which permit composition of a flexible system for PID control, square-root extraction or non-linear control. FEATURES 1. PID auto tuning function Optimum PID parameter can be obtained for processing. 2. High reliability LED's (red and green) are used for the bar graph indicator and for parameter indication (red). A non-volatile memory retains the control and computation parameters even if power should be interrupted. 3. All operations are performed from the front of the panel Operations such as parameter setting, auto/manual changeover, hard manual operation, etc. are performed from the front of the panel. 4. Transmission function Incorporation of transmission function permits setting of concentrated monitoring data at the host system. FUNCTIONAL DIAGRAM Bar graph indicator To other controllers Communication terminal External set point input (CAS) A/D converter 4 to 20mA, thermocouple/ resistance bulb conversion Feed forward computation – P I D Square-root extraction Internal input terminal Process value input (PV) Filter Compensated PV signal (KPV) + + R.A MH ML M Limiter Limiter SH + Non-linear D/A converter Linearize Internal output terminal External MV input (AI2) Feed forward input (AI1) Control output (current) (MI) Control output (voltage) (MV) R SL A.M Set point transmit signal (SV) Manual mode output (M) Local mode output (DO1) Remote request (DO2) M mode L or SCC mode Pulse input (PI) Manual mode command (SMV) M mode External output terminal External input terminal Personal computer R Fault output (FLT) PV tracking (DI1) External MV command (DI2) Remote acknowledge signal (DI3) High alarm output (H) Low alarm output (L) R mode Fault FLT lamp H lamp Alarm L lamp : Option EDS11-91h Date Dec. 20, 1994 PNA1 SPECIFICATIONS (2) Analog output signal: 3 points Compensated PV value signal KPV 1. Control functions PID control: Proportional band (P); 1.0 to 3276.7% Integration time (I); 0.1 to 3276.7 sec Derivative time (D); 0.0 to 900.0 sec PID auto tuning function Additional functions: Segmented line approximation; 15 segmented lines Square-root extraction; with low input cut function Filter; filter time constant 0.0 to 900.0 sec Non-linear control Feed forward computation Output limiter; High/low limit –25.0 to 125.0% Output change rate limiter; 0.0 to 100.0% Alarm functions: PV high/low alarm PV change rate alarm DV high/low alarm Select any 1 of 3 types at left Front panel LED (H, L) ON, digital output (H, L) ON Control cycle: 0.1 sec 2. Input signal (1) PV input signal: One point select from the following inputs. Voltage input signal 1 to 5V DC Input resistance, 1 MΩ or more Allow. error, ± 0.2%/FS Current input signal 4 to 20mA DC 24V DC power is supplied to transmitter only when AC power is used. Allow. error, ± 0.2%/FS(*) Thermocouple 10 input 1– Type J:0 to 600°C K:0 to 1200°C E:0 to 800°C R:0 to 1600°C 10mV DC span or more Cold junction compensation comprised Allow. error ± 0.5%/FS Resistance bulb input JPt100/Pt100 –50 to 500°C 50°C span or more Allow. error ± 0.5%/FS 1+ (2) Analog input signal: 3 points External set point CAS Feed forward input AI1 External MV input AI2 1 to 5V DC Input resistance, 1 MΩ or more Allow. error ± 0 2%/FS (3) Digital input signal: 4 points Manual mode command SMV PV tracking command DI1 External MV command DI2 Remote ready siqnal DI3 Contact input (photo-coupler insulation) ON/OV, OFF/24V (input current, approx. 11mA/24V DC) (4) Pulse width or pulse number input signal: any 1 set Pulse width input signal Pulse number input signal PI+, PI– Contact input (photo-coupler insulation) ON/OV, OFF/24V (input current, approx. 11mA/24V DC) ON/OV, OFF/24V (approx. 11mA/24VDC), max. input frequency 500Hz 3. Output signal (1) Control output signal: 1 set Current output MI+, Ml– 4 to 20mA DC Allow. Ioad resistance; less than 600Ω Allow. error ± 0.2%/FS Note * : FS: Full scale 2 Set point transmission signal SV Control output (voltage) MV 1 to 5V DC Output resistance, less than 0.5Ω Allow. error, ± 0.2%/FS (3) Digital output signal: 6 points Fault output FLT Manual mode output M High alarm output H Low alarm output L Local mode output DO1 Remote request signal DO2 Open-collector output (photocoupler insulation) Output rating, 30V x 0.1A DC max. 4. Indication, setting and operating functions (1) Bar graph indication Indication system PV indicator SV indicator MV indicator Indication LED (red) LED (green) LED (red) 101 + 2 51 + 2 0 to 100% linear 0 to 100% linear 1%/FS 2%/FS 100mm 50mm Indication segments 101 + 2 Indication range 0 to 100% linear Indication resolution 1%/FS Scale length 100mm Indication mode 0 to 100% bar graph indication, 0 to 100% reverse bar graph indication, dot indication, –50 to +50% deviation indication (2) Operation mode indication Indication method: LED (red and green) Red: M, HM, SCC Green: A, R (3) Numerical indication, setting Indication method: LED (red), name in 3 digits + number in 5 digits (Negative sign included) Indication contents: Process variable (industrial value), set point (industrial value), alarm high/low values, PID parameters, etc. Indication contents are selected by using F/S, , , keys Setting method: By using F/S, , , , ST keys on front panel (4) SV setting function Fixed value setting method: By using, , , pushbuttons on front panel Setting speed, about 40 sec/FS Remote setting method: By external set point signal (voltage or pulse width input) (5) MV operating function Manual operating method: By using , , , , buttons on front of the panel Setting speed; approx. 40 sec/FS Simultaneous press of ; approx. 8 sec/ FS (6) Operation mode changeover Front panel R/A/M pushbutton and HM (hard manual) switch R A changeover A R changeover Balanceless bumpless Voltage signal Balance bumpless Pulse width input Balanceless bumpless A or R M changeover Balanceless bumpless A or R HM selection Balanceless bumpless 5. Power failure processing function Power failure detection: Control stoppage at power failure detection During power failure: Operating parameters backed up by capacitor when power failure occurs within 5 minutes Initial set point and manipulated output values, PID parameters, etc. are stored in nonvolatile memory (lasts for 10 years expected at ambient temperature of 50°C or less). Power failure recovery time: Initial or continuous start mode can be set for power failure within 5 minutes. Recovery from power failure lasting longer than 5 minutes is done by initial. * Operation mode at initial set can be registered M: Manual mode A: Auto mode R: Remote mode SCC: SCC mode 6. Self-diagnosis function Computation/control circuit abnormality: FLT indicator lights, FLT contact output turns, "ON", and computation and control stop. Manipulated output can be controlled manually at FLT (soft manual). Input/output signal abnormality, manipulated output break: FLT indicator lights, control stops and manipulated output is held. Computation processing and output processing other than for manipulated output continue. Fault contents indication: Cause of fault is indicated numerically on numerical indicator on front of the panel. 7. Transmission functions (1) Transmission items Supervisory items: Host PNA Process variable, set point, manipulated output, deviation, operation mode, alarm information, FAULT information, PID parameters, various limiter values, constants, etc. Setting operation items: PNA Host Set point, manipulated output operation mode, PID parameters, various limiter values, constants, etc. (2) Transmission setting inhibit: Parameter setting enable/inhibit can be designated by transmission from the host. Designation is made by using F/S, , , , ST keys on the front of the panel. (3) Transmission interface: CC data line or RS422A/RS-485 interface or T-link select (a) T-link: Private interface Transmission speed: 500 Kbps No. of units to be connected: 32 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: I/O transmission and message communication (b) RS-422A/485: Universal interface Transmission speed: 2400, 4800, 9600, 19200bps, selectable No. of units connectable: 31 max. Transmission distance: 1 km max. Transmission form: Multi-drop Control method: Polling/selecting (c) CC data line: Private interface Transmission speed: 19.2 Kbps (fixed) No. of units to be connected: 15 max. Transmission distance: 500m max. Transmission form: Multi-drop Control method: Polling/selecting 8. Other functions Data protection function by use of pass code 9. Additional functions (options) (1) Hard manual actuator (HMV) Control output: 4 to 20mA DC Allow. load resistance: Less than 600Ω (24V DC power only) (This option is available only when power supply is 24V DC) 10. Operating conditions Power supply: Select from the following 3 types 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 12W (DC) Approx. 20VA (AC) Dielectric strength: 1500VAC, 1 min. Insulation resistance: 500V DC, 100MΩ or more Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Enclosure class: Front IP65 (IEC 529) Rating plate (Name plate): 100 (H) x 70 (W), white acryl Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC (DIN) standards Mass{weight}: Approx. 2.9kg 3 PNA1 Mounting method: Flush on indoor panel, vertical mounting is standard practice. Mounting on tilted surface possible (angle α) CODE SYMBOLS 1 2 3 4 5 6 7 8 P NA 1 9 10 11 12 5 - 0 A Description Process variable input signal 1 to 5V DC 4 to 20mA DC J thermocouple 10mV DC span or K thermocouple more, with cold E thermocouple junction compensation R thermocouple Resistance bulb, JPt100, 3-wire type, 50°C span or more Resistance bulb, Pt100, 3-wire type, 50°C span or more A B C D E F G α=0° to 90° W Finish color: Munsell N1.5 for the both of front and case. Scope of delivery: Controller and mounting bracket Items prepared separately: Transmission cable (Type PNZ) Setting method A-M type R-A-M type A B Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) 1 2 3 Hard manual unit Without With only (when 24V DC power supply) 0 1 Transmission function Without T-link RS-422A RS-485 CC data line (communication controller required) Y T R S C PID auto tuning function Provided A OUTLINE DIAGRAM Notes: Symbols of resistance bulbs are as follows. JPt100 .... JIS C 1604-1981 Pt100 ..... IEC Pub 751-1983 (Jpt100/pt100 changeover is possible with front key.) (Unit:mm) Panel thickness 8mm or less 16 144 Terminal Terminal cover Mounting bracket Support bracket 140 36 200min. 72 355 Panel cutout 138 +1 0 250min. When mounting "n" units 138 +1 0 200min. When mounting one unit 68 4 +0.7 0 (72.2n – 4) +1 0 No. of units n 2 CONNECTION DIAGRAM Block terminals (M4 screws) DO (Manual mode) DO (Local mode) DI (Manual mode command) I+ (PV) I– (SC) 11 M 13 31 DO 1 14 SMV 15 AC I0 12 16 32 PI+ 33 PI– 34 FLT 35 AC PI (Pulse width input) DO (FLT output) AO (Compensated process value signal) AO (Set point transmit signal) (Unused) AO (Control output) AI, AO (Common bus) AO (Control output) Current AI (Process value input) DO (High limit alarm output) DO (Low limit alarm output) Instrument power supply (24V DC) DI, DO 24V power supply Earth Instrument power (AC) – – KPV 51 71 CAS SV 52 72 AI 1 AO 1 53 73 AI 2 AI 3 MV 54 74 SC 55 75 MI+ 56 76 MI– 57 77 DO 2 H 58 78 DI 3 L 59 79 DI 2 PC* 60 80 DI 1 AI (External set point) AI (Feed forward input) AI (External MV input) (Unused) SC PCD 61 81 VP* G 62 82 VPD + + AI, AO (Common bus) DO (Remote request) DI (Remote acknowledge) DI (External MV command) DI (PV tracking command) Instrument power supply (24V DC) DI, DO 24V power supply Note: * Symbols for AC instrument power are VPO, PCO. Output is about 24V DC (0.1A max.). Process value input terminal connections 1 to 5V DC Thermocouple + 11 31 The 5th digit of code symbols: A – 12 + 11 The 5th digit of code symbols: C,D,E,F 4 to 20mA DC 4 to 20mA DC with inner DC power supply of CC-S The 5th digit of code symbols: B + 11 – – 12 + 11 – 12 31 Resistance bulb + The 5th digit of code symbols: B + The 5th digit of code symbols: G,W 31 – – 12 + 11 – 12 31 + – 31 PC 60 5 PNA1 Transmission connector 1 SIG GND 6 7 8 RXD + 9 RXD – 1 SIG GND 6 2 SHLD(SD) 3 INH 4 TXD+(T1) 2 SHLD(SD) Black 7 White 8 RXD + 9 RXD – 5 TXD–(T2) Green 3 INH 4 TXD+(T1) 5 TXD–(T2) Yellow Brown Red 6 7 8 RXD + 9 RXD – 1 SIG GND 1 SIG GND 6 2 SHLD(SD) 7 3 INH 8 RXD + 4 TXD+(T1) 9 RXD – 5 TXD–(T2) 2 SHLD(SD) Black 3 INH White 4 TXD+(T1) 5 TXD–(T2) Terminating resistor Green Yellow Red Brown Host master controller Remark:Parenthesized symbols:For T-link connection End controller 1st controller Host Termination resistor Transmission cable PNA1 PNA1 PNA1 PNA1 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan