FUJI EDSX5-83J

FCX –A SERIES
REMOTE SEAL TYPE
PRESSURE TRANSMITTER
FKB...4
DATA SHEET
The FCX – A2 pressure transmitter accurately measures
gauge pressure and transmits a proportional 4 to 20mA signal.
The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and functionality.
Totally welded construction of the seals assures excellent
reliability in high temperature and highly corrosive process
conditions.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard feature for all GP models covering 1.3kPa {0.013bar} range
to 50000kPa {500bar} high pressure range. 0.1% accuracy is available as option. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART ® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART ®.
Any HART® compatible devices can communicate with
FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available.
4. Application flexibility
Various options that render the FCX – A2 suitable for
almost any process applications include:
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum seals
5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range, and overrange limit:
Span limit [kPa]{bar}
Type
F KB
1
F KB
2
F KB
3
F KB
4
F KB
5
Min.
Max.
1.3
{0.013}
5
{0.05}
30
{0.3}
100
{1}
500
{5}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
50000
{500}
Range limit
[kPa]{bar}
–100 to +130
{–1 to +1.3}
–100 to +500
{–1 to +5}
–100 to +3000
{–1 to +30}
–100 to +10000
{–1 to +100}
–100 to +50000
{–1 to +500}
Overrange
limit
[MPa] {bar}
1
{10}
1.5
{15}
9
{90}
15
{150}
75
{750}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
–
Lower range limit (vacuum limit) ;
Silicone fill sensor: See Fig. 1, Fig. 2
Fluorinated fill sensor: Atmospheric pressure
– Conversion factors to different units;
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX5-83j
Date
May. 30, 2007
FKB...4
Load limitations: see figure below
Authorities
ATEX
[Ω]
Load resistance
2000
1533Ω
Ex II 1 GD
EEx ia IIC T5 Tamb = –40°C to +40°C
EEx ia IIC T4 Tamb = –40°C to +80°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
1500
1000
600Ω
24V
250
0
Factory
Mutual
Operating
area
500
10
16.1
10.5V
Power voltage
45V
50
[V]
required.
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Flameproof
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
ATEX
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = –40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = –40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
TIIS
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = –40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
CSA
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
Hazardous locations:
Authorities
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
Note: For communication with HHC(1) (Model: FXW), min. of 250Ω is
Note) “Seal Not Required” enclosure is allowed.
2
Intrinsic safety
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp. = +120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = –40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = –40°C to +65°C
ATEX
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = –40°C to +40°C
EEx nL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
EEx nAL IIC T5 Tamb = –40°C to +40°C
EEx nAL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
20 20.8
Normal operating range
Under scale
Probable under range
Burnout
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
CSA
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
–
21.6 [mA]
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC(1).
Temperature limit:
Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil fill transmitter)
(–10 to +85°C for silicone oil “H”, “S”, “K”)
(+20 to +85°C for silicone oil “J”, “T”)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified by each standard.
Process:
Fill fluid
Code in the
13th digit of
“Code symbols”
Process
temperature
Fluorinated oil
W, A and D
–20 to 120°C
Silicone oil
H
–15 to 250°C
J
85 to 300°C
–
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(Span adjustment is not available with 9th
digit code “L, P, Q, S”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
Zero can be elevated or suppressed within
the specified range limit of each sensor
model.
Normal/reverse action:
Selectable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
(Note)
3.8 4
Over scale
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
IECEx
Scheme
/SAA
3.2
Y and G
– 40 to 120°C
S
–15 to 250°C
T
85 to 300°C
K
–15 to 200°C
Lower limit
of
static press.
Atmospheric
pressure
2.7kPa abs
{20mmHg
abs}
0.13kPa abs
{1mmHg abs}
or more
Storage: – 40 to +90°C
(1) HHC: Hand Held Communicator
3
FKB...4
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
EMC Conformity:EN61326
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ± 0.2% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.1+0.1
% of span
Span
(Option) (Code; 21th digit H,K)
Not available for Max span 50000kPa model.
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.05+0.05
% of span
Span
(
(
)
)
± 0.1% of upper range limit (URL) for 3
years.
Temperature effect:
Effect per 28°C change between the limits of – 40°C and +85°C
(Standard)
Zero shift: ± 0.35% of URL
Total effect: ± 0.5% of URL
(Option) (Code; 21th digit J,K)
Zero shift: ± 0.3% of URL
Total effect: ± 0.4% of URL
Overrange effect: Zero shift; 0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Update period: 120 msec *)
Step response: Time constant: 0.2s*)
Dead time: 0.2s*)
(without electrical damping)
Stability:
*) Faster response is available as option (maximum
update rate: 25 times per second).
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ/500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
4
Physical specifications
Electrical connections:
G1/2, 1/2 -14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
1-port (standard) or 2-port with each conduit, as specified.
Process connections:
JIS, ANSI, or DIN raised face flanges or
screw connection JIS/ISO G1 external
thread.
Refer to “Code symbols.”
Process-wetted parts material:
Diaphragm: 316L stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Flange face:316 stainless steel, Hastelloy-C
Monel, Tantalum, Titanium or
Zirconium
Extension: 316 stainless steel, Hastelloy-C
(Refer to “Code symbols”)
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating (standard), or 316 stainless steel (SCS14 per
JIS G5121), as specified.
Capillary: In case of 11th code “D, E, L, F,
M, N, P”, PVC armored stainless steel.
In case of 11th code “Q, R, S, T, V, W,
X”, stainless steel armored stainless
steel.
Mounting flange: 304 stainless steel or
carbon steel, as specified
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting
Mass {weight}:
Transmitter approximately 10kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum and high temperature service:
Special silicone oil and filling procedure
are applied.
See Fig.1 and Fig.2.
Optional tag plate:
An extra stainless steel tag for customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
5
FKB...4
[kPa abs]
{mbar abs}
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
Silicone (Code S)
Silicone (Code T)
Sealing liquid:Silicone (Code K)
101
{1010}
53.3
{533}
Operating pressure
Operating pressure
101
{1010}
Operating area
13.3
{133}
Non-operating
area
0.27
{2.7}
0.13
{1.3}
2.7
{27}
–40 –15
60 85 120
Process temperature[°C ]
200 230 250
Fig. 1 Relation between process temperature and
operating pressure
ACCESSORIES
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
6
Operating area
300
–15
100
Process temperature[°C ]
200
Fig. 2 Relation between process temperature and
operating pressure
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Description
<Conduit connection>
G1/2
(×1)
Combination with 12th digit code “C, E, P, Q” are not
1/2-14NPT (×1)
available.
Pg13.5
(×1)
M20 × 1.5 (×1)
G1/2
(×2)
1/2-14NPT (×2)
Pg13.5
(×2)
M20 × 1.5 (×2)
<Flanges>
Mounting flange Flange size and rating
Ranges
1 2 3
4 5
304 stainless
JIS 10K 80A
* * *
steel
JIS 10K 100A
* * *
ANSI/JPI 150LB "3"
* * *
ANSI/JPI 150LB "4"
* * *
DIN PN16/40 DN80
* * *
DIN PN16 DN100
* * *
JIS 20K 80A
* * *
JIS 30K 80A
* * *
ANSI/JPI 300LB 3B
* * *
ANSI/JPI 600LB 3B
* * *
Carbon steel
JIS 10K 80A
* * *
JIS 10K 100A
* * *
ANSI/JPI 150LB "3"
* * *
ANSI/JPI 150LB "4"
* * *
DIN PN16/40 DN80
* * *
DIN PN16 DN100
* * *
Screw type, JIS/ISO G1
* *
316 stainless
ANSI/JPI 150LB 3B
* * *
steel
ANSI/JPI 150LB 4B
* * *
ANSI/JPI 300LB 3B
* * *
ANSI/JPI 300LB 4B
* * *
ANSI/JPI 600LB 3B
* * *
None
3 inch wafer
* * *
(wafer type)
4 inch wafer
* * *
<Span limit (*2) [kPa]{bar}>
1.3…130
{0.013…1.3}
5…500
{0.05…5}
30…3000
{0.3…30}
100…10000 {1…100}
Available only with material code “V”
500…50000 {5…500}
<Material/diaphragm extension>
Diaphragm
Flange face
Diaph. extension [mm]
316L stainless
316 stainless
0
steel
steel
50
100
(*3)
150
200
Hastelloy-C
0
Hastelloy-C
50
100
150
200
316L stainless
316 stainless steel 0
+Au coating
Monel
0
Monel
Tantalum
0
Tantalum
Titanium
0
Titanium
(*4)
Zirconium
0
Zirconium
Note1: (*1)
Note2: (*2)
Note3: (*3)
Note4: (*4)
Note
F KB
9 10 11 12 13
14 15
21
4
Digit No.
of code
A
B
C
D
S
T
V
W
0
1
3
4
6
7
9
M
S
T
A
B
D
E
G
H
K
V
W
X
Y
U
P
Q
Note 2
1
2
3
4
5
Note 1
Note 3
Note 4
V (*1)
A
B
C
D
H
F
G
K
L
J
M
T
P
R
If range 4 or 5 is selected, specify material “V” in any cases.
100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance.
Available for 13th digit code “S”, “T”, “K” and 5th digit code “1”,“4”,“7”,“B”,“E”,“H”,“Q”, “W”, “Y”.
Available for 6th digit code “2”, “3” and 5th digit “0”, “3”, “6”, “9”, “A”, “D”, “G”, “P”, “M”, “S”, “T”, “U”, “V”, “X”.
7
FKB...4
1 2 3 4 5 6 7 8
Digit
9
10
11
12
Description
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None Z/S board
Analog, custom scale
None attached.
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
Approvals for hazardous locations
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code “A”, “S”)
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A”, “S”)
FM, Flameproof (or explosionproof) (Available for 4th digit code “B”, “T”)
CSA, Flameproof (or explosionproof) (Available for 4th digit code “B”, “T”)
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Capillary and mounting bracket>
Capillary
Mounting bracket
Armor of capillary
1.5 m
304 Stainless steel
PVC
(*5)
3
304 Stainless steel
PVC
(*5)
5
304 Stainless steel
PVC
(*5)
6
304 Stainless steel
PVC
(*5)
7
304 Stainless steel
PVC
(*5)
8
304 Stainless steel
PVC
(*5)
10
304 Stainless steel
PVC
(*5)
1.5
304 Stainless steel
Stainless steel
(*6)
3
304 Stainless steel
Stainless steel
(*6)
5
304 Stainless steel
Stainless steel
(*6)
6
304 Stainless steel
Stainless steel
(*6)
7
304 Stainless steel
Stainless steel
(*5)
8
304 Stainless steel
Stainless steel
(*5)
10
304 Stainless steel
Stainless steel
(*5)
<Options>
Extra SS tag plate
Stainless steel elec. housing Coating of cell
None
None
None
Yes
None
None
None
Yes
None
(*7)
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Note
F KB
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
A
B
C
D
E
X
R
G
H
J
K
P
T
V
Note 5
Note 5
Note 5
Note 5
Note 5
Note 5
Note 5
Note 6
Note 6
Note 6
Note 6
Note 5
Note 5
Note 5
Note 7
Note5: (*5) Available for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code.
Note6: (*6) Available for all 13th digit code.
Note7: (*7) Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select “Yes”.
8
9 10 11 12 13
4
D
E
L
F
M
N
P
Q
R
S
T
V
W
X
Y
B
C
E
M
N
P
Q
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
13
14
15
21
Description
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "A", "B", "C" and "D")
Chlorine service
Fluorinated oil (7th digit code "H", "F", "G", "K", "L" and "T")
High temp. 250°C
Silicone oil
Available for 7th digit code "V", "A",
High temp. 300°C
Silicone oil "B", "C", "D", "H", "F", "G", "K" and "L".
(* 8)
High temp. and vacuum (250°C) Silicone oil
Available for 6th digit code "1", "2" or "3".
High temp. and vacuum (300°C) Silicone oil In case of 13th digit code "S", "T", "K", available
High temp. and high vacuum Silicone oil for 6th digit code "2", "3" only.
<Teflon membrane>
None
Yes (Available for the 5th digit code "0", "3", "6", "A", "D", "G", "P" and 7th
digit code "V", "H", "M", "T", "P", "R".
Not available for the 13th digit code "H", "J", "S", "T", "K".)
<Bolt/nut> (*9)
None
(6th digit code "1", "2", "3")
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut (6th digit code
"4", "5")
Cr-Mo alloy hexagon bolt/carbon steel unit
304 stainless steel/304 stainless steel (6th digit code "4")
630 stainless steel/304 stainless steel (6th digit code "5")
<Other options> (*10)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Note
Note 8
F KB
9 10 11 12 13
14 15
21
4
Digit No.
of code
Y
W
G
A
D
H
J
S
T
K
Y
C
Note 9
Y
A
B
E
F
Note 10
H
J
K
L
T
U
V
Note8: (*8) Treatment; Standard
Note9: (*9) In case of tropical use, select stainless bolts and nuts.
Note10: (*10) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
9
FKB...4
OUTLINE DIAGRAM (Unit:mm)
Note) Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
In case of 4th digit code “S.V.W.X”
MTG. pipe
JIS 50A (2B)
In case of 4th digit code “A.B.C.D.E”
In case of 4th digit code “T”
Fastener
(Flameproof only)
U - bolt M8
10
94.5
8
Zero ADJ. screw
ø80
104
105
70
ø80
52.5
105
UP
38
88
DOWN
30
58
4 holes 9 dia.
210
Cable gland
(option)
(27)
“B” Conduit conn.
With field ind.
“A” Conduit conn.
N holes
h dia.
Inner of gasket
Detail “B”
17
øE
P
ø13
K M
øG
øH
Detail “A”
(Conduit conn.)
ø15
øD
øF
Note)
J
G1/2
20
L
See Table 1
t
No flange is attached
in case of 5th digit
code “P,Q”.
191
43
60
Earth terminal
L
Mass approx.(kg)
11th digit code
S (m)
9.5
D
Q
1.5
E
R
3
L
S
5
10.5
F
T
6
100
11.5
M
V
7
C
K
150
12
N
W
8
D
L
200
12.5
P
X
10
V
J
H
M
T
P
R
0
A
F
50
B
G
5th digit of the
code symbols
S
øH
t
P
N-øh
Flange
0, A
185 150
126 100 73
38
116
8-19
JIS 10K 80A
9
200 160
126 100 73
42
116
8-23
JIS 20K 80A
M
210 170
126 100 73
48
116
8-23
JIS 30K 80A
1, B
210 175
151 103 96
38
141
8-19
JIS 10K 100A
ANSI 150LB 3B
øD
øE
øF
øG
191 152.5 126 100 73
44
116
4-20
S, X
210 168
126 100 73
49
116
8-23
ANSI 300LB 3B
T, U
210 168
126 100 73
52
116
8-23
3, D, V
Electronics
unit
231
7th digit code
2-M8×12
50
70
120
CONNECTION
DIAGRAM
+
4th digit of the
code symbols
229 190.5 151 103 96
44
141
8-20
A, S
G1/2
17
8
Y
254 200
151 103 96
52
141
8-23
ANSI 300LB 4B
B, T
1/2-14NPT
16
5
6, G
200 160
126 100 73
44
116
8-18
DIN PN40 DN80
C, V
Pg13.5
8
4.5
7, H
220 180
151 103 96
40
141
8-18
DIN PN16 DN100
D, W
M20×1.5
16
5
4, E, W
K
Table 1
10
CK+ CK–
+ –
Conduit conn.
ANSI 600LB 3B
ANSI 150LB 4B
J
–
M
Sensor
unit
In case of 4th digit code “A.B.C.D.E”
In case of 4th digit code “S.V.W.X”
MTG. pipe JIS 50A
(2B)
In case of 4th digit code “T”
Fastener
(Flameproof only)
10
8
Zero ADJ. screw
38
S
Cable gland
(option) Note)
30
4 holes
9 dia.
ø80
104
105
Down
88
70
ø80
Up
52.5
105
94.5
U - bolt M8
58
(27)
210
“B” Conduit conn.
20
“A” Conduit conn.
47
G1
191
43
Packing
60
Earth terminal
2
53 14
100
With field ind.
-0.1
ø23.6 -0.2
Electronics
unit
ø30 -0.1
-0.2
Detail “B”
231
Detail “A”
(Conduit conn.)
ø15
17
D E
ø13
C
Sensor
unit
2-M8×12
G1/2
See Table 1
50
70
120
4th digit of the
code symbols
Conduit conn.
C
D
E
A, S
G1/2
17
8
B, T
1/2-14NPT
16
5
C, V
Pg13.5
8
4.5
D, W
M20×1.5
16
5
Table 1
11th digit code
S (m)
D
Q
1.5
E
R
3
L
S
5
F
T
6
M
V
7
N
W
8
P
X
10
CONNECTION
DIAGRAM
+
–
CK+ CK–
+ –
Note) Cable gland is supplied in
case of flameproof packing type.
ø11 cable is suitable.
11
FKB...4
ORDERING INFOMATION
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range.
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit).
5. Tag No. (up to 26 alphanumerical characters), if required.
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan