FCX –A SERIES REMOTE SEAL TYPE PRESSURE TRANSMITTER FKB...4 DATA SHEET The FCX – A2 pressure transmitter accurately measures gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. High accuracy 0.2% accuracy for all calibrated spans is a standard feature for all GP models covering 1.3kPa {0.013bar} range to 50000kPa {500bar} high pressure range. 0.1% accuracy is available as option. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART ® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART ®. Any HART® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX – A2 suitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum seals 5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 6. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Span, range, and overrange limit: Span limit [kPa]{bar} Type F KB 1 F KB 2 F KB 3 F KB 4 F KB 5 Min. Max. 1.3 {0.013} 5 {0.05} 30 {0.3} 100 {1} 500 {5} 130 {1.3} 500 {5} 3000 {30} 10000 {100} 50000 {500} Range limit [kPa]{bar} –100 to +130 {–1 to +1.3} –100 to +500 {–1 to +5} –100 to +3000 {–1 to +30} –100 to +10000 {–1 to +100} –100 to +50000 {–1 to +500} Overrange limit [MPa] {bar} 1 {10} 1.5 {15} 9 {90} 15 {150} 75 {750} Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower range limit (vacuum limit) ; Silicone fill sensor: See Fig. 1, Fig. 2 Fluorinated fill sensor: Atmospheric pressure – Conversion factors to different units; 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal. Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX5-83j Date May. 30, 2007 FKB...4 Load limitations: see figure below Authorities ATEX [Ω] Load resistance 2000 1533Ω Ex II 1 GD EEx ia IIC T5 Tamb = –40°C to +40°C EEx ia IIC T4 Tamb = –40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH 1500 1000 600Ω 24V 250 0 Factory Mutual Operating area 500 10 16.1 10.5V Power voltage 45V 50 [V] required. 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D Flameproof CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH ATEX Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = –40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = –40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C TIIS Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH IECEx Scheme /SAA Ex ia IIC T4 IP66/67 Tamb = –40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH CSA Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH Hazardous locations: Authorities Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – Note: For communication with HHC(1) (Model: FXW), min. of 250Ω is Note) “Seal Not Required” enclosure is allowed. 2 Intrinsic safety TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C IECEx Scheme /SAA Ex d IIC T5 IP66/67 pending Tamb = –40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = –40°C to +65°C ATEX Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1) Type n Nonincendive Authorities Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +40°C EEx nL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH EEx nAL IIC T5 Tamb = –40°C to +40°C EEx nAL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D 20 20.8 Normal operating range Under scale Probable under range Burnout Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C CSA Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS – 21.6 [mA] Probable over range Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60°C for fluorinated oil fill transmitter) (–10 to +85°C for silicone oil “H”, “S”, “K”) (+20 to +85°C for silicone oil “J”, “T”) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: Fill fluid Code in the 13th digit of “Code symbols” Process temperature Fluorinated oil W, A and D –20 to 120°C Silicone oil H –15 to 250°C J 85 to 300°C – Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (Span adjustment is not available with 9th digit code “L, P, Q, S”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1). Indication: Analog indicator or 5-digit LCD meter, as specified. (Note) 3.8 4 Over scale Burnout Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – IECEx Scheme /SAA 3.2 Y and G – 40 to 120°C S –15 to 250°C T 85 to 300°C K –15 to 200°C Lower limit of static press. Atmospheric pressure 2.7kPa abs {20mmHg abs} 0.13kPa abs {1mmHg abs} or more Storage: – 40 to +90°C (1) HHC: Hand Held Communicator 3 FKB...4 Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2. Items Display Set Tag No. v v Model No. v v Serial No. v — Engineering unit v v Range limit v — Measuring range v v Damping v v Output mode v — Burnout direction v v Calibration v v Output adjust — v Data v — Self diagnoses v — Printer — — External switch lock v v Transmitter display v v Linearize v v Rerange v v EMC Conformity:EN61326 Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ± 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (Code; 21th digit H,K) Not available for Max span 50000kPa model. For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span ( ( ) ) ± 0.1% of upper range limit (URL) for 3 years. Temperature effect: Effect per 28°C change between the limits of – 40°C and +85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code; 21th digit J,K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL Overrange effect: Zero shift; 0.2% of URL for any overrange to maximum limit Supply voltage effect: Less than 0.005% of calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: Time constant: 0.2s*) Dead time: 0.2s*) (without electrical damping) Stability: *) Faster response is available as option (maximum update rate: 25 times per second). Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ/500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less 4 Physical specifications Electrical connections: G1/2, 1/2 -14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. 1-port (standard) or 2-port with each conduit, as specified. Process connections: JIS, ANSI, or DIN raised face flanges or screw connection JIS/ISO G1 external thread. Refer to “Code symbols.” Process-wetted parts material: Diaphragm: 316L stainless steel, Hastelloy-C Monel, Tantalum, Titanium or Zirconium Flange face:316 stainless steel, Hastelloy-C Monel, Tantalum, Titanium or Zirconium Extension: 316 stainless steel, Hastelloy-C (Refer to “Code symbols”) Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14 per JIS G5121), as specified. Capillary: In case of 11th code “D, E, L, F, M, N, P”, PVC armored stainless steel. In case of 11th code “Q, R, S, T, V, W, X”, stainless steel armored stainless steel. Mounting flange: 304 stainless steel or carbon steel, as specified Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 10kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm Optional features Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum and high temperature service: Special silicone oil and filling procedure are applied. See Fig.1 and Fig.2. Optional tag plate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. 5 FKB...4 [kPa abs] {mbar abs} Silicone (Code Y,G) [kPa abs] {mbar abs} Silicone (Code S) Silicone (Code T) Sealing liquid:Silicone (Code K) 101 {1010} 53.3 {533} Operating pressure Operating pressure 101 {1010} Operating area 13.3 {133} Non-operating area 0.27 {2.7} 0.13 {1.3} 2.7 {27} –40 –15 60 85 120 Process temperature[°C ] 200 230 250 Fig. 1 Relation between process temperature and operating pressure ACCESSORIES Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 amplifier unit, external adjustment screw will be available for zero and span adjustment. 6 Operating area 300 –15 100 Process temperature[°C ] 200 Fig. 2 Relation between process temperature and operating pressure CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 5 6 7 Description <Conduit connection> G1/2 (×1) Combination with 12th digit code “C, E, P, Q” are not 1/2-14NPT (×1) available. Pg13.5 (×1) M20 × 1.5 (×1) G1/2 (×2) 1/2-14NPT (×2) Pg13.5 (×2) M20 × 1.5 (×2) <Flanges> Mounting flange Flange size and rating Ranges 1 2 3 4 5 304 stainless JIS 10K 80A * * * steel JIS 10K 100A * * * ANSI/JPI 150LB "3" * * * ANSI/JPI 150LB "4" * * * DIN PN16/40 DN80 * * * DIN PN16 DN100 * * * JIS 20K 80A * * * JIS 30K 80A * * * ANSI/JPI 300LB 3B * * * ANSI/JPI 600LB 3B * * * Carbon steel JIS 10K 80A * * * JIS 10K 100A * * * ANSI/JPI 150LB "3" * * * ANSI/JPI 150LB "4" * * * DIN PN16/40 DN80 * * * DIN PN16 DN100 * * * Screw type, JIS/ISO G1 * * 316 stainless ANSI/JPI 150LB 3B * * * steel ANSI/JPI 150LB 4B * * * ANSI/JPI 300LB 3B * * * ANSI/JPI 300LB 4B * * * ANSI/JPI 600LB 3B * * * None 3 inch wafer * * * (wafer type) 4 inch wafer * * * <Span limit (*2) [kPa]{bar}> 1.3…130 {0.013…1.3} 5…500 {0.05…5} 30…3000 {0.3…30} 100…10000 {1…100} Available only with material code “V” 500…50000 {5…500} <Material/diaphragm extension> Diaphragm Flange face Diaph. extension [mm] 316L stainless 316 stainless 0 steel steel 50 100 (*3) 150 200 Hastelloy-C 0 Hastelloy-C 50 100 150 200 316L stainless 316 stainless steel 0 +Au coating Monel 0 Monel Tantalum 0 Tantalum Titanium 0 Titanium (*4) Zirconium 0 Zirconium Note1: (*1) Note2: (*2) Note3: (*3) Note4: (*4) Note F KB 9 10 11 12 13 14 15 21 4 Digit No. of code A B C D S T V W 0 1 3 4 6 7 9 M S T A B D E G H K V W X Y U P Q Note 2 1 2 3 4 5 Note 1 Note 3 Note 4 V (*1) A B C D H F G K L J M T P R If range 4 or 5 is selected, specify material “V” in any cases. 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. Available for 13th digit code “S”, “T”, “K” and 5th digit code “1”,“4”,“7”,“B”,“E”,“H”,“Q”, “W”, “Y”. Available for 6th digit code “2”, “3” and 5th digit “0”, “3”, “6”, “9”, “A”, “D”, “G”, “P”, “M”, “S”, “T”, “U”, “V”, “X”. 7 FKB...4 1 2 3 4 5 6 7 8 Digit 9 10 11 12 Description <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Z/S board Analog, custom scale None attached. None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% None Digital, custom scale None Digital, 0 to 100% Yes Digital, custom scale Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes Approvals for hazardous locations None (for ordinary locations) TIIS, Flameproof (Conduit seal) (Available for 4th digit code “A”, “S”) TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A”, “S”) FM, Flameproof (or explosionproof) (Available for 4th digit code “B”, “T”) CSA, Flameproof (or explosionproof) (Available for 4th digit code “B”, “T”) ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and nonincendive CSA, Intrinsic safety and nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety <Capillary and mounting bracket> Capillary Mounting bracket Armor of capillary 1.5 m 304 Stainless steel PVC (*5) 3 304 Stainless steel PVC (*5) 5 304 Stainless steel PVC (*5) 6 304 Stainless steel PVC (*5) 7 304 Stainless steel PVC (*5) 8 304 Stainless steel PVC (*5) 10 304 Stainless steel PVC (*5) 1.5 304 Stainless steel Stainless steel (*6) 3 304 Stainless steel Stainless steel (*6) 5 304 Stainless steel Stainless steel (*6) 6 304 Stainless steel Stainless steel (*6) 7 304 Stainless steel Stainless steel (*5) 8 304 Stainless steel Stainless steel (*5) 10 304 Stainless steel Stainless steel (*5) <Options> Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None (*7) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Note F KB A B D E F H L P Q S 1 2 4 5 A B C D E X R G H J K P T V Note 5 Note 5 Note 5 Note 5 Note 5 Note 5 Note 5 Note 6 Note 6 Note 6 Note 6 Note 5 Note 5 Note 5 Note 7 Note5: (*5) Available for 13th digit code “Y, W, G, A, D”. Inquire about in case of 13th other code. Note6: (*6) Available for all 13th digit code. Note7: (*7) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. 8 9 10 11 12 13 4 D E L F M N P Q R S T V W X Y B C E M N P Q 14 15 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 13 14 15 21 Description <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V", "A", "B", "C" and "D") Chlorine service Fluorinated oil (7th digit code "H", "F", "G", "K", "L" and "T") High temp. 250°C Silicone oil Available for 7th digit code "V", "A", High temp. 300°C Silicone oil "B", "C", "D", "H", "F", "G", "K" and "L". (* 8) High temp. and vacuum (250°C) Silicone oil Available for 6th digit code "1", "2" or "3". High temp. and vacuum (300°C) Silicone oil In case of 13th digit code "S", "T", "K", available High temp. and high vacuum Silicone oil for 6th digit code "2", "3" only. <Teflon membrane> None Yes (Available for the 5th digit code "0", "3", "6", "A", "D", "G", "P" and 7th digit code "V", "H", "M", "T", "P", "R". Not available for the 13th digit code "H", "J", "S", "T", "K".) <Bolt/nut> (*9) None (6th digit code "1", "2", "3") Cr-Mo alloy hexagon socket head cap screw/carbon steel nut (6th digit code "4", "5") Cr-Mo alloy hexagon bolt/carbon steel unit 304 stainless steel/304 stainless steel (6th digit code "4") 630 stainless steel/304 stainless steel (6th digit code "5") <Other options> (*10) High accuracy type Instruction manual attached Low temperature effect type Instruction manual attached H+J Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached Low temperature effect type Instruction manual unattached T+U Instruction manual unattached Note Note 8 F KB 9 10 11 12 13 14 15 21 4 Digit No. of code Y W G A D H J S T K Y C Note 9 Y A B E F Note 10 H J K L T U V Note8: (*8) Treatment; Standard Note9: (*9) In case of tropical use, select stainless bolts and nuts. Note10: (*10) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. 9 FKB...4 OUTLINE DIAGRAM (Unit:mm) Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. In case of 4th digit code “S.V.W.X” MTG. pipe JIS 50A (2B) In case of 4th digit code “A.B.C.D.E” In case of 4th digit code “T” Fastener (Flameproof only) U - bolt M8 10 94.5 8 Zero ADJ. screw ø80 104 105 70 ø80 52.5 105 UP 38 88 DOWN 30 58 4 holes 9 dia. 210 Cable gland (option) (27) “B” Conduit conn. With field ind. “A” Conduit conn. N holes h dia. Inner of gasket Detail “B” 17 øE P ø13 K M øG øH Detail “A” (Conduit conn.) ø15 øD øF Note) J G1/2 20 L See Table 1 t No flange is attached in case of 5th digit code “P,Q”. 191 43 60 Earth terminal L Mass approx.(kg) 11th digit code S (m) 9.5 D Q 1.5 E R 3 L S 5 10.5 F T 6 100 11.5 M V 7 C K 150 12 N W 8 D L 200 12.5 P X 10 V J H M T P R 0 A F 50 B G 5th digit of the code symbols S øH t P N-øh Flange 0, A 185 150 126 100 73 38 116 8-19 JIS 10K 80A 9 200 160 126 100 73 42 116 8-23 JIS 20K 80A M 210 170 126 100 73 48 116 8-23 JIS 30K 80A 1, B 210 175 151 103 96 38 141 8-19 JIS 10K 100A ANSI 150LB 3B øD øE øF øG 191 152.5 126 100 73 44 116 4-20 S, X 210 168 126 100 73 49 116 8-23 ANSI 300LB 3B T, U 210 168 126 100 73 52 116 8-23 3, D, V Electronics unit 231 7th digit code 2-M8×12 50 70 120 CONNECTION DIAGRAM + 4th digit of the code symbols 229 190.5 151 103 96 44 141 8-20 A, S G1/2 17 8 Y 254 200 151 103 96 52 141 8-23 ANSI 300LB 4B B, T 1/2-14NPT 16 5 6, G 200 160 126 100 73 44 116 8-18 DIN PN40 DN80 C, V Pg13.5 8 4.5 7, H 220 180 151 103 96 40 141 8-18 DIN PN16 DN100 D, W M20×1.5 16 5 4, E, W K Table 1 10 CK+ CK– + – Conduit conn. ANSI 600LB 3B ANSI 150LB 4B J – M Sensor unit In case of 4th digit code “A.B.C.D.E” In case of 4th digit code “S.V.W.X” MTG. pipe JIS 50A (2B) In case of 4th digit code “T” Fastener (Flameproof only) 10 8 Zero ADJ. screw 38 S Cable gland (option) Note) 30 4 holes 9 dia. ø80 104 105 Down 88 70 ø80 Up 52.5 105 94.5 U - bolt M8 58 (27) 210 “B” Conduit conn. 20 “A” Conduit conn. 47 G1 191 43 Packing 60 Earth terminal 2 53 14 100 With field ind. -0.1 ø23.6 -0.2 Electronics unit ø30 -0.1 -0.2 Detail “B” 231 Detail “A” (Conduit conn.) ø15 17 D E ø13 C Sensor unit 2-M8×12 G1/2 See Table 1 50 70 120 4th digit of the code symbols Conduit conn. C D E A, S G1/2 17 8 B, T 1/2-14NPT 16 5 C, V Pg13.5 8 4.5 D, W M20×1.5 16 5 Table 1 11th digit code S (m) D Q 1.5 E R 3 L S 5 F T 6 M V 7 N W 8 P X 10 CONNECTION DIAGRAM + – CK+ CK– + – Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 11 FKB...4 ORDERING INFOMATION When ordering this instrument, specify. 1. CODE SYMBOLS 2. Measuring range. 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA) Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 5. Tag No. (up to 26 alphanumerical characters), if required. The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission) EN61326 : 1997 Class A (standard for Industrial Location) Frequency range MHz Limits Reference standard 30 to 230 40dB (µV/m) quasi peak, measured at 10m distance CISPR16-1 and CISPR16-2 230 to 1000 47dB (µV/m) quasi peak, measured at 10m distance EMI (Immunity) EN61326: 1997 Annex A (standard for Industrial Location) Phenomenon Electrostatic discharge Test value 4kV (Contact) 8kV (Air) Basic standard Performance criteria EN61000-4-2 B 80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) EN61000-4-3 A Rated power frequency magnetic field 30A/m 50Hz EN61000-4-8 A Burst 2kV 5kHz EN61000-4-4 B Surge 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) EN61000-4-5 B Conducted RF 0.15 to 80MHz 3V 80%AM (1kHz) EN61000-4-6 A Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan