FUJI EDSX5-91H

ABSOLUTE PRESSURE TRANSMITTER
FKA...5
DATA SHEET
The FCX -AIII absolute pressure transmitter accurately
measures absolute pressure and transmits a proportional
4 to 20mA signal.
The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and functionality.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard
feature for all AP models covering 1.6kPa {0.016bar}
range to 3000kPa {30bar} high pressure range. 0.1%
accuracy is available as option. Fuji’s micro-capacitance
silicon sensor assures this accuracy for all suppressed
calibration ranges without additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects
the pressure sensor against changes in tempera ture,
and overpressure substantially reduces total measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX -AIII.
4. Application flexibility
Various options that render the FCX -AIII suitable for
almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with
NAMUR NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
[ L-Type ]
[ T-Type ]
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range, and overrange limit:
Span limit
[kPa abs] {bar abs}
Type
Min.
FKA
01
FKA
02
FKA
03
FKA
04
1.6
{0.016}
1.6
{0.016}
5
{0.05}
30
{0.3}
Overrange
limit
[MPa]
{bar}
Range limit
[kPa abs]
{bar abs}
Max.
16
{0.16}
130
{1.3}
500
{5}
3000
{30}
0 to +16
{0 to +0.16}
0 to +130
{0 to +1.3}
0 to +500
{0 to +5}
0 to +3000
{0 to +30}
0.5
{5}
0.5
{5}
1.5
{15}
9
{90}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– The maximum span of each sensor can be converted
to different units using factors as below.
1MPa abs=103kPa abs=10bar abs=10.19716kgf/cm2 abs
=145.0377psi abs
1kPa abs =10mbar abs=101.9716mmH2O abs
=4.01463inH2O abs=7.50062mmHg abs
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V
DC at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX5-91h
Date
Aug. 10, 2011
FKA...5
Load limitations: see figure below
[Ω]
Load resistance
2000
1474Ω
1500
R=
E-10.5
(Imax+0.9)x10-3
1000
577Ω
Operating
area
500
24V
250
0
10
45V
16.35
10.5V
Power voltage (DC)
50
E[ V ]
Note: For communication with HHC(1) (Model: FXW), min. of 250 is
required.
Hazardous locations: SEE TABLE2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
Zero can be elevated within the specified
range limit of each sensor model.
Normal/reverse action:
Selectable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction:Selectable from HHC(1)
If self-diagnostic detect transmitter failure,
the analog signal will be driven to either
“Output Hold”, “Output Overscale” or
“Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC(1)
3.2
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Probable over range
Temperature limit:
Ambient: −40 to +85°C
(−20 to +80°C for LCD indicator)
(−40 to +60°C for arrester option)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified by
each standard.
Process: −40 to +85°C for silicone fill
sensor
Storage: −40 to +90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than
7.0 (or FXW
1– 4), for FCX AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Output mode
v
—
v
—
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
EMC Conformity: EN61326-1: 2006
Output Limits comforming the NAMUR NE43 by order.
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA
by HHC(1).
(Note)
2
(1) HHC: Hand Held Communicator
Process-wetted parts material:
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability).
(Standard)
For spans greater than 1/10 of URL: ±0.2% of span
For spans below 1/10 of URL:
± 0.1 + 0.1 0.1 x URL % of span
Span
(
)
(Option) (code: 21th digit H)
(Not available for Max span 16kPa abs, 130kPa abs)
For spans greater than 1/10 of URL: ±0.1% of span
For spans below 1/10 of URL:
± 0.05 + 0.05 0.1 x URL % of span
Span
(
)
Stability:
±0.2% of upper range limit (URL) for 10
years.
Temperature effect:
Effect per 28°C change between the
limits of - 40°C and +85°C
URL
Zero shift: ± 0.125+0.1
%
Span
Total effect: ± 0.15+0.1 URL %
Span
(
(
)
)
Overrange effect: Zero shift; ±0.2% of URL for any overrange
to maximum limit
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
Update rate:
60 msec
Step response: Time constant: 0.08 s (at 23°C)
Dead time: 0.12 s
(without electrical damping)
Mounting position effect:
Zero shift, less than 0.1kPa{1mbar} for a
10° tilt in any plane.
No effect on span. This error can be corrected by adjusting zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
Physical specifications
Electrical connections:
G 1/2, 1/2-14NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
l a i r e t aM
e d o c
t Process
i g i d h tcover
7(
e d oC “ n i
symbols”)
V
H
Diaphragm
Wetted
sensor body
Vent/drain
316
316 stainless
316/316L
316L
steel (*1)
stainless steel stainless steel stainless steel
Hastelloy-C
316 stainless
316/316L
Hastelloy-C
lining
steel (*1)
stainless steel
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remarks: Availability of above material design depends on ranges.
Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with polyester
coating (standard), or 316 stainless
steel (ASTM CF8M), as specified.
Bolts and nut: Cr-Mo alloy (standard),
304 or 316 stainless steel
Fill fluid: Silicone oil
Mounting bracket: 304 or 316 stainless
steel.
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting
bracket, direct wall mounting, or direct
process mounting.
Mass{weight}:
Transmitter approximately 2.9 to 3.4kg
without options.
Add; 0.5kg for mounting bracket
4.5kg for stainless steel housing
option
Optional features
Indicator:
A plug-in analog indicator (2.5%
accuracy)
An optional 5-digit LCD meter with
engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2  50µs)
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
304 stainless steel bolts and nuts, ASTM
B7M or L7M bolts and 2HM nuts (Class
II) are available.
Optional tagplate:
An extra stainless steel tag for customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/
polyurethane double coating. Specify if
environment is extremely corrosive.
3
FKA...5
CODE SYMBOLS
Digit
4
6, 7
9
10
11
1 2 3 4 5 6 7 8
Description
<Connections>
Process
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
<Span limit>
Span limit
[kPa abs]{bar abs}(*1)
1.6…16
{0.016…0.16}
1.6…130
{0.016…1.3}
5…500
{0.05…5}
30…3000
{0.3…30}
Oval flange
screw
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
Conduit
connection
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
G1/2
1/2-14NPT
Pg13.5
M20×1.5
Pg13.5
Note
0
9 10 11 12 13
5
Case type
T type
T type
T type
T type
T type
L type
L type
L type
L type
L type
Process cover
Diaphragm
Wetted cell body
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316L stainless steel
Hast. C
316L stainless steel
Hast. C
316L stainless steel
Hast. C
316L stainless steel
Hast. C
316 stainless steel
Hast. C lining
316 stainless steel
Hast. C lining
316 stainless steel
Hast. C lining
316 stainless steel
Hast. C lining
5
6
7
8
9
S
T
V
W
X
Note1
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, custom scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100% linear scale
None
Digital, custom scale
None
Digital, 0 to 100% linear scale
Yes
Digital, custom scale
Yes
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
None
Digital, custom scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Yes
Digital, custom scale
(Local configurator unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*6)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*9)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*9)
ATEX Flameproof (*8)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*8)
IECEx Scheme, Flameproof (*8)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*9)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Standard
None
Standard
Yes, stainless steel (SUS304)
Standard
Yes, stainless steel (SUS316)
Side
None
Side
Yes, stainless steel (SUS304)
Side
Yes, stainless steel (SUS316)
Note1: (*1) 100: 1 turn down is possible, but should be used at a span greater
than 1/40 of the maximum span for better performance.
4
F KA
1V
1H
2V
2H
3V
3H
4V
4H
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
Note6
Note9
Note9
Note8
Note8
Note8
Note9
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
A
C
K
D
F
L
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
12
13
14
15
21
Description
Note
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
(*2)
None
None
Yes
Yes
None
Yes
None
Yes
Yes
(*5)
Yes
Yes
Yes
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Degreasing
Silicone oil
NACE specification
Silicone oil (7th digit code "T" and 15th digit code
"A", "B" are not available)
<O-ring/Gasket and Teflon membrance>
Teflon (gasket)
<Bolt/nut> (*3)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
NECE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel bolt/304 stainless steel nut
316 stainless steel bolt/316 stainless steel nut
<Other options> (*4)
High accuracy type (*7)
Instruction manual attached
Opposite Vent/Drain Plug Position
Instruction manual attached
Instruction manual unattached
High accuracy type(*7)
Instruction manual unattached
Opposite Vent/Drain Plug Position
Instruction manual unattached
F KA
0
9 10 11 12 13
14 15
21
5
Note2
Note5
Note5
Digit No.
of code
Y
B
M
N
P
Q
Y
G
N
B
Note 3
A
B
C
D
E
U
Note 4
Note 7
Note 7
H
C
L
T
P
Note2: (*2) Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select "Yes".
Note3: (*3) In case of tropical use, select stainless bolts and nuts.
Note4: (*4) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note5: (*5) Not available for 10th digit code “C”.
Note6: (*6) Available for 4th digit code "S".
Note7: (*7) Available for 6th digit code "3", "4".
Note8: (*8) Available for 4th digit code "6", "8", "T", "W".
Note9: (*9) Available for 4th digit code "6", "T".
ACCESSORIES
ORDERING INFOMATION
Oval flanges:
When ordering this instrument, specify.
1. CODE SYMBOLS
2. Measuring range.
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
Hold / Overscale / Underscale
Unless other wise specified, output hold function is
supplied.
4. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S on 9th digit).
5. Tag No. (up to 14 alphanumerical characters), if required.
(Model FFP, refer to Data Sheet No. EDS6128)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
5
FKA...5
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: T type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE3)
MTG. PIPE JIS 50A (2B)
IN CASE OF 4TH DIGIT CODE "6"
WITH ANALOG IND.
WITH DIGITAL IND.
"A" PRESS. CONN.
ZERO ADJ. SCREW
EARTH TERMINAL
8
10
41
IN CASE OF 4TH DIGIT CODE "5,7,8,9"
(21)
(11)
38
φ81
110
70
SCS13
100
ZERO
VENT/DRAIN PLUG
"B" CONDUIT CONN.
57
37
168
4 HOLES 9 DIA.
17
127
(171)
U-BOLT M8
20
NOTE2)
DETAIL "A"
(PRESS. CONN.)
φ18.5
OVAL FLANGE SCREW
SEE TABLE1
SIDE VENT(OPTION)
E
F
41.3
8
2.5
φ15
226
H
(229) NOTE2)
DETAIL "B"
(CONDUIT CONN.)
L.P
10
D
SEE TABLE1
SEE TABLE1
Conduit conn.
Press. conn.
4th digit of the
code symbols
D
E
F
H
5
G 1/2
18
2
Rc1/4
H.P
4-M8×12
Oval frange screw
7/16-20UNF
SCREW DEPTH15
6
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
7
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
8
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
9
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
27
70
104
TABLE 1
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
6
NOTE2) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T"
NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
<AMP. case: L type>
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG ATTACHED
ON THE UPPER SIDE OF THE DETECTOR) NOTE3)
MTG. PIPE JIS 50A (2B)
IN CASE OF 4TH DIGIT CODE "T"
IN CASE OF 4TH DIGIT CODE "S,V,W,X"
"A" PRESS. CONN.
120
φ81
41
8
103
70
φ81
103
41
10
ZERO ADJ. SCREW
RO
38
57
"B" CONDUIT CONN.
37
4 HOLES 9 DIA.
172
(21)
(175)
(11)
WITH ANALOG IND.
U-BOLT M8
126
43
41
VENT/DRAIN PLUG
WITH DIGITAL IND.
NOTE2)
OVAL FLANGE SCREW
SEE TABLE1
DETAIL "B"
(CONDUIT CONN.)
φ18.5
SIDE VENT(OPTION)
φ15
F
8
41.3
2.5
H
E
L.P
10
D
SEE TABLE1
SEE TABLE1
Conduit conn.
Press. conn.
H.P
198
(201) NOTE2)
DETAIL "A"
(PRESS. CONN.)
EARTH TERMINAL
4-M8×12
4th digit of the
code symbols
D
E
F
H
S
G 1/2
18
2
Rc1/4
7/16-20UNF
SCREW DEPTH15
T
1/2-14NPT
16
4
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
V
Pg13.5
10.5
4.5
1/4-18NPT
M10
SCREW DEPTH15
W
M20×1.5
16
4
1/4-18NPT
M10
SCREW DEPTH15
X
Pg13.5
10.5
4.5
1/4-18NPT
7/16-20UNF
SCREW DEPTH15
27
Oval frange screw
70
104
TABLE 1
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
G1/2
DETAIL C
φ33.5
φ13
<SS TAG PLATE>
19
106
17
CONNECTION DIAGRAM
"C" CONDUIT CONN.
G1/2
−/CK− CK+
CABLE GLAND
75
+
20
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
NOTE2) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H"
NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
7
FKA...5
TABLE 2
Authorities
ATEX
Authorities
Intrinsic safety
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
ATEX
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Note) “Seal Not Required” enclosure is allowed.
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester), Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
NEPSI
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp. = +120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
13th digit
Y,G,N
Y,G,N
Y,G,N
Y,G,N
ATEX
Ex II 3 GD
EEx nL IIC T5 Tamb = –40°C to +50°C
EEx nL IIC T4 Tamb = –40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = –40°C to +50°C
EEx nAL IIC T4 Tamb = –40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
Type n
Nonincendive
Authorities
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
Flameproof
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan