DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER FKC...4 DATA SHEET The FCX–A2 differential pressure (flow) transmitter accurately measures differential pressure, liquid level, gauge pressure or flow rate and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FEATURES 1. High accuracy ±0.07% 0.07% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART ® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX–A2 suitable for almost any process applications include. – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials 5. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) 6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type F KC 11 F KC 22 F KC 23 F KC 25 F KC 26 F KC 33 F KC 35 F KC 36 F KC 38 F KC 43 F KC 45 F KC 46 F KC 48 Span limit [kPa] {m bar} Static pressure [MPa] {bar} –0.1 to + 3.2 {–1 to + 32} –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 30 {–1 to + 300 } Max. Min. 0.1 1} 0.1 { 1} 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 30 { 300 } 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 30 { 300 } { { { { { { { { { { { { { { 1 10 } 6 60 } 32 320 } 130 1300 } 500 5000 } 32 320 } 130 1300 } 500 5000 } 3000 30000 } 32 320 } 130 1300 } 500 5000 } 3000 30000 } Range limit [kPa] {m bar} +/– 1 { +/– 10 } +/– 6 { +/– 60 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 } Remark : To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60°C – The maximum span of each sensor can be converted to different units using factors as below. 1MPa =10 3KPa=10bar=10.19716kgf/cm2 =145.0377psi 1kpa=10mbar=101.9716mmH2O=4.01463inH2O EDSX6-114j Date Mar. 7, 2007 FKC...4 Over range limit: To maximum static pressure limit Output signal: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below [Ω] Load resistance 2000 Authorities ATEX Factory Mutual 1000 600Ω Operating area 24V 0 10 16.1 10.5V Power voltage 50 [V] Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = –40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = –40°C to +85°C Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH IECEx Scheme /SAA Ex ia IIC T4 IP66/67 Tamb = –40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH Authorities Flameproof CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C IECEx Scheme /SAA Ex d IIC T5 IP66/67 pending Tamb = –40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = –40°C to +65°C Note) “Seal Not Required” enclosure is allowed. 2 Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C CSA Hazardous locations: Factory Mutual 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A,D Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH 45V Note: For communication with HHC(1) (Model: FXW), min. of 250 Ω required. ATEX Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – 1500 250 Ex II 1 GD EEx ia IIC T5 Tamb = –40°C to +40°C EEx ia IIC T4 Tamb = –40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH 1533Ω 500 Intrinsic safety ATEX “Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1) Type n Nonincendive Authorities Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +40°C EEx nL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH 3.2 Normal operating range Under scale Probable under range Burnout Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A,D Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C CSA Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS – IECEx Scheme /SAA – 20 20.8 21.6 [mA] Over scale Burnout EEx nAL IIC T5 Tamb = –40°C to +40°C EEx nAL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual 3.8 4 Probable over range Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60°C for fluorinated oil filled transmitters) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: – 40 to +120°C for silicone fill sensor –20 to +80°C for fluorinated oil fill sensor Storage: – 40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2. Items Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (span adjustment is not available with 9th digit code “L, P, M, Q, S, N”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: –100% to +100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1) Tag No. Model No. Serial No. Engineering unit Range limit Measuring range Damping Output mode Linear Square root Burnout direction Calibration Output adjust Data Self diagnoses Printer External switch lock Transmitter display Linearize Rerange Display v v v v v v v v v v v — v v — v v v v Set v v — v — v v v v v v v — — — v v v v Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326 (Note) (1) HHC: Hand Held Communicator 3 FKC...4 Performance specifications for linear output Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) Max span above 32kPa model: For spans greater than 1/10 of URL: ± 0.07% of span For spans below 1/10 of URL: 0.1 × URL ± 0.02+0.05 % of span Span Max span 1kPa, 6kPa model: For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.1% of upper range limit (URL) for 3 years for 6th digit code 3, 5, 6, 8. Temperature effect: Effects per 28°C change between the limits of – 40°C and +85°C ( ) ( Accuracy rating: Span Output 50 to 100% 20 to 50% 10 to 20% over 0.1 × URL ± 0.07 % ± 0.175 % ± 0.35 % Zero shift “1”/1kPa {10mbar} max. span “2”/6kPa {60mbar} max. span ± 0.125+0.1 ( Total effect URL % Span ± 0.15+0.1 ) ( ( ) Accuracy 50 to 100% 20 to 50% 10 to 20% ± 0.1 % ± 0.25% ± 0.5 % Temperature effect: Effects per 55°C change between the limits of – 40°C and +85°C Range code “3” through “8” ) ) Static pressure effect: Shift at 20% output point URL ± 0.375+0.25 Span %/28°C URL ± 0.24+0.03125 Span %/28°C ( ) ( ) Low flow cut-off: Customer configurable for any point between 0 to 20% of output URL % Span ( ± (0.02+0.05 × 0.1 × URL/Span)% ± 2.5 × (0.02+0.05 × 0.1 × URL/Span)% ± 5 × (0.02+0.05 × 0.1 × URL/Span)% Output “1” and “2” Range code (6th digit in Code symbols) below 0.1 × URL Max span 1kPa, 6kPa model: ) “3”/32kPa {320mbar} max. span “5”/130kPa {1300mbar} max. URL URL span % ± 0.075+0.0125 % ± 0.095+0.0125 Span Span “6”/500kPa {5000mbar} max. span “8”/3000kPa {30000mbar} max. span Supply voltage effect: Less than 0.005% of calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: (without electrical damping) Range code (6th digit in code symbols) Time constant*) Static pressure code (5th digit in Code symbols) Zero shift (% of URL) “1” /1kPa {10m bar} sensor “2” /6kPa {60 m bar} sensor ±0.2% / 1MPa{10bar} ±0.2% / 3.2MPa{32bar} “1” 0.8 s “2” 0.5 s ±0.05%/10MPa{100bar} “3” 0.3 s “5” through “8” 0.2 s “2” “3” “4” Overrange effect: 4 Performance specifications for square root output Static pressure code (5th digit in Code symbols) Zero shift (% of URL) “1” / 1kPa{10m bar} sensor “2” / 6kPa{60m bar} sensor “2” “3” “4” ± 0.3% / 1MPa ± 0.1% / 3.2MPa ± 0.1% /10MPa ± 0.1% /16MPa ± 0.25% /42MPa {10bar } {32bar } {100bar } {160bar } {420 bar} Dead time*) 0.2 s *) Faster response is available as option (maximum update rate: 25 times per second). Mounting position effect: Zero shift, less than 0.12kPa {1.2m bar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less Physical specifications Optional features Material code (7th digit Process cover in Code symbols) V H J M T B L U 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) Hastelloy-C lining Monel lining Tantalum lining Diaphragm Wetted sensor body 316L stainless 316 stainless steel steel Hastelloy-C Hastelloy-C lining 316L stainless 316 stainless steel steel +Au coating Monel Monel lining Tantalum Tantalum lining Hastelloy-C Hastelloy-C lining Monel lining Tantalum lining Monel Tantalum Vent/drain 316/316L stainless steel 316/316L stainless steel 316/316L stainless steel 316/316L stainless steel 316/316L stainless steel Hastelloy-C Monel Hastelloy-C Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) Remarks: Sensor O-rings: Viton O-ring and teflon gasket selectable. Availability of above material design depends on ranges and static pressure. Refer to “Code symbols”. Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14A per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 stainless steel (for static pressure code “1”, “2”, and “3” only), or 630 stainless steel (for static pressure code “3” and “4” only). Static pressure rating for code “3” with 304 stainless steel bolts is degraded to 10MPa. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 4.4kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Static pressure rating for code “3” (16 MPa) is degraded to 10MPa. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/ polyurethane double coating. Specify if environment is extremely corrosive. Silicone oil (Code:Y,G,N) Silicone oil (Code:R) [kPa abs] {mbar abs} 101 {1010} Operating pressure Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. And 1 conduit or 2 conduits, as specified. Process connections: 1/4-18 NPT or Rc1/4 on 54mm centers, as specified. Meets DIN 19213. Process-wetted parts material: Operating area 20 {200} 4 {40} 2.7 {27} None-operating area –40 –15 60 85 120 Process temperature[°C ] Fig. 1 Relation between process temperature and operating pressure 5 FKC...4 ACCESSORIES ORDERING INFORMATION Oval flanges: When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA) Unless otherwise specified, output hold function is supplied. 4. Output mode (linear or square root output) Unless otherwise specified, output mode is linear. 5. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 6. Tag No. (up to 26 alphanumerical characters), if required. (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2 -14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Equalizing valves: (Model FFN, refer to Data Sheet No. EDS6-10) Available in Carbon steel or in 316 stainless steel and in pressure rating 16MPa or 42MPa. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 amplifier unit, external adjustment screw will be available for zero and span adjustment. 6 CODE SYMBOLS Digit 4 1 2 3 4 5 6 7 8 Description <Connection> Oval flange Conduit Process connection connection screw 7/16-20UNF G1/2 (×1) Rc1/4 7/16-20UNF 1/2-14NPT (×1) 1/4-18NPT Combination with 12th 1/4-18NPT M10 (or M12)(*1) Pg 13.5 (×1) digit code "C, E, P, Q" 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×1) are not available. 7/16-20UNF 1/4-18NPT Pg 13.5 (×1) 7/16-20UNF G1/2 (×2) Rc1/4 7/16-20UNF 1/2-14NPT (×2) 1/4-18NPT 1/4-18NPT M10 (or M12)(*1) Pg 13.5 (×2) 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×2) 7/16-20UNF 1/4-18NPT Pg 13.5 (×2) 5, 6, 7 <Span and materials> Static Span limit (*2) Process Diaphragm Wetted pressure cover cell body [MPa] [kPa] {bar} (m bar) –0.1 to 0.1…1 316 stainless steel 316L stainless steel 316 stainless steel +3.2 {1…10} 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+32} +Au coating 316 stainless steel Hast. C Hast. C lining –0.1 to+10 0.1…6 316 stainless steel 316L stainless steel 316 stainless steel {–1 to 100} {1…60} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining –0.1 to+16 0.32…32 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+160} {3.2…320} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 1.3…130 {13…1300} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 5…500 {50…5000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 30…3000 {300…30000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating –0.1 to+42 0.32…32 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+420} {3.2…320} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel 316L stainless steel 316 stainless steel 1.3…130 {13…1300} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel 316L stainless steel 316 stainless steel 5…500 {50…5000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining –0.1 to+30 30…3000 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+300} {300…30000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating –0.1 to+10 0.32…32 Hast. C lining Hast. C Hast. C lining {–1 to+100} {3.2…320} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining 1.3…130 Hast. C lining Hast. C Hast. C lining {13…1300} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining 5…500 Hast. C lining Hast. C Hast. C lining {50…5000} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining Note Note 1 Note 1 Note 1 Note 1 F KC 4 9 10 11 12 13 14 15 21 Digit No. of code A B C D E S T V W X Note 2 11V 11J 11H 22V 22J 22H 33V 33J 33H 33M 33T 35V 35J 35H 35M 35T 36V 36J 36H 36M 36T 38V 38J 43V 43J 43H 43M 45V 45J 45H 45M 46V 46J 46H 46M 48V 48J 23B 23L 23U 25B 25L 25U 26B 26L 26U Note 1: (*1) The thread is M12, if 42MPa {420bar} static pressure is specified. Note 2: (*2) 100: 1 turn down is possible, but should be used at the span greater than 1/40 of the maximum span for better performance. 7 FKC...4 1 2 3 4 5 6 7 8 Digit 9 10 11 12 13 14 Description Note <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Note 3 Analog, 0 to 100% sq. root scale None (*3) Z/S board Analog, custom scale None attached. Analog, double scale (Linear and sq. root) None None Yes Analog, 0 to 100% linear scale Yes Note 3 Analog, 0 to 100% sq. root scale Yes (*3) Analog, custom scale Yes Analog, double scale (Linear and sq. root) Yes Digital, 0 to 100% None Digital, custom scale None Digital 0 to 100% square root None Digital, 0 to 100% Yes Digital, custom scale Yes Digital 0 to 100% square root Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% square root (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes Digital, 0 to 100% square root (Local adjustment unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Conduit seal) (Available for 4th digit code “A“, “S“) TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A“, “S“) FM, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) CSA, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and Nonincendive CSA, Intrinsic safety and Nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety <Vent/ drain and mounting bracket> Vent/drain Mounting bracket Standard None Specify “A” or “C” for the 7th Standard Yes, stainless steel digit code “B”, “L”, or “U” Side None Side Yes, stainless steel <Options> Extra SS tag plate Stainless steel elec, housing Coating of cell Note 4 None None None Yes None None None Yes None Yes Yes None (*4) None None Yes Yes None Yes None Yes Yes Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V”, “J” only) Chlorine service Fluorinated oil (7th digit code “H”, “T”, “B”, “U”) NACE specification Silicone oil (Not available for 7th digit code “T”, “U” and 15th digit code “A”, “B”) Vacuum service Silicone oil for vacuum use <Sensor O-ring / Gasket> Viton (O-ring) Teflon (gasket) F KC 9 10 11 12 13 14 15 21 4 A B C D J E F G H K L P M Q S N 1 2 3 4 5 6 A B C D E X R G H J K P T V A C D F Y B C E M N P Q Y W G A D N R A B Note 3: (*3) In case of square root output mode, square root scale is not available. Note 4: (*4) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”. 8 Digit No. of code 1 2 3 4 5 6 7 8 Digit 15 21 Description <Bolt/nut> (*8) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) (*5) NACE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel bolt/304 stainless steel nut (*6) 630 stainless steel bolt/304 stainless steel nut (*7) <Other options> (*9) Instruction manual unattached Note Note 8 F KC Note 5 Note 6 Note 7 Note 9 9 10 11 12 13 14 15 21 4 Digit No. of code A B C D E F L Note 5: (*5) Static pressure should be –0.1 to +10MPa{–1 to +100bar}. Note 6: (*6) Available for 5th digit code “1”, “2”, “3”. In case of stainless steel bolt with 5th digit code “3”, static pressure should be –0.1 to +10MPa {–1 to + 100bar}. Note 7: (*7) Available for 5th digit code “3”, “4”. Note 8: (*8) In case of tropical use, select stainless bolts and nuts. Note 9: (*9) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. 9 FKC...4 OUTLINE DIAGRAM (Unit:mm) < 7th digit code : V, H, M, T, J > Note 2) Vent/drain plug (When the vent/drain plug attatched on the upper side of the detector) In case of 4th digit code "A.B.C.D.E" In case of 4th digit code "S.V.W.X" In case of 4th digit code "T" 105 105 52.5 70 ø80 Up ø80 94.5 8 10 Zero ADJ. screw Fastener (Flameproof only) 130 120 43.5 "A" Press. conn. MTG. pipe JIS 50A (2B) 41 Down 88 38 58 37 Note 1) 4 Holes 9 Dia. (27) 210 Cable gland (option) "B" Conduit conn. "C" Conduit conn. Vent/drain plug U-bolt M8 With field ind. 154 Detail "A" (Press. conn.) Detail "B" (Conduit conn.) ø18.5 H Detail "C" 59 43 Earth terminal ø13 2.5 ø15 F G 1/2 D See table 1 See table 1 Side vent (option) 41.3 ø7 Press.conn. (Low pressure side) 4th digit of the code symbols 3, 4, A, S Conduit conn. E F D G1/2 Press. conn. H 17 8 Rc1/4 B, T 1/2-14NPT 16 5 1/4-18NPT C, V Pg13.5 8 4.5 1/4-18NPT D, W M20 16 5 1/4-18NPT E, X Pg13.5 4.5 1/4-18NPT 1.5 8 Oval flange screw 7/16-20UNF SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 M10 SCREW DEPTH15 M10 SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 TABLE 1 Press.conn. (High pressure side) 4-M8 12 54 70 104 CONNECTION DIAGRAM CK Note 1) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. Note 2) The pressure connector is located on the down side surface of the detector, when the vent/drainplug is attatched on the upper side of the detector (when the 21th digit of the code symbols: c, e or d). 10 231 E 17 8 Electronics unit Oval flange screw See table 1 CK Sensor unit < 7th digit code : B, L, U > Oval flange screw See table 1 In case of 4th digit code "A.B.C.D.E" MTG. pipe JIS 50A (2B) In case of 4th digit code "S.V.W.X" "A"or"B" Press. conn. In case of 4th digit code "T" Fastener (Flameproof only) 41.3 94.5 8 Zero ADJ. screw 10 U-bolt M8 ø80 120 105 ø80 52.5 70 105 Up 88 41 Down 38 4 Holes 9 Dia. Note 1) Cable gland (option) 40 58 (27) 213 "D" Conduit conn. "C" Conduit conn. Vent/drain plug With field ind. Detail "A" Detail "C" (Press. conn.) (Conduit conn.) 4TH DIGIT CODE "A, S" Detail "D" ø13 Electronics unit 17 H 234 F 1 0 2 -0.1 +0.2 ø12 +0.1 186 43 Earth terminal ø15 ø16 91 G 1/2 E ø4 See table 1 Press.conn. (Low pressure side) Detail "B" (Press. conn) 4TH DIGIT CODE "B, C, D, E, T, V, W, X" ø16 10 Press.conn. (High pressure side) 4-M8 12 1/4-18NPT 4th digit of the code symbols 3, 4, A, S ø4 Sensor unit Conduit conn. E F H G1/2 17 8 B, T 1/2-14NPT 16 5 C, V Pg13.5 8 4.5 D, W M20 1.5 16 5 E, X Pg13.5 8 4.5 Oval flange screw 7/16-20UNF SCREW DEPTH10 7/16-20UNF SCREW DEPTH10 M10 SCREW DEPTH10 M10 SCREW DEPTH10 7/16-20UNF SCREW DEPTH10 54 70 104 CONNECTION DIAGRAM CK CK TABLE 1 Note 1) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. 11 FKC...4 The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission) EN61326 : 1997 Class A (standard for Industrial Location) Frequency range MHz Limits Reference standard 30 to 230 40dB (µV/m) quasi peak, measured at 10m distance CISPR16-1 and CISPR16-2 230 to 1000 47dB (µV/m) quasi peak, measured at 10m distance EMI (Immunity) EN61326: 1997 Annex A (standard for Industrial Location) Phenomenon Electrostatic discharge Test value 4kV (Contact) 8kV (Air) Basic standard Performance criteria EN61000-4-2 B 80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) EN61000-4-3 A Rated power frequency magnetic field 30A/m 50Hz EN61000-4-8 A Burst 2kV 5kHz EN61000-4-4 B Surge 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) EN61000-4-5 B Conducted RF 0.15 to 80MHz 3V 80%AM (1kHz) EN61000-4-6 A Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan