FUJI EDSX7-60J

LEVEL TRANSMITTER
DATA SHEET
FKE...4
The FCX–A2 level transmitter accurately measures liquid level
and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon
sensor with state-of-the-art microprocessor technology to
provide exceptional performance and functionality.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard feature for all models covering 0.32kPa {3.2mbar} range to
500kPa {5bar} high differential pressure range. 0.1% accuracy is available as option. Fuji’s micro-capacitance
silicon sensor assures this accuracy for all elevated or
suppressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX–A2.
Further, by upgrading electronics FOUNDATION™
fieldbus and Profibus™ are also available.
4. Application flexibility
Various options that render the FCX–A2 suitable for
almost any process applications include:
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum service.
5. Programmable output Linearization Function
Output signal can be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as
wet calibration.
EDSX7-60j
Date
Mar. 7, 2007
FKE...4
Hazardous locations:
SPECIFICATIONS
Authorities
Functional specifications
ATEX
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = –40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = –40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp. = +120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = –40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = –40°C to +65°C
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
F KE
3
F KE
5
F KE
6
Static
pressure
Span limit [kPa] {m bar}



0.32
{3.2}
1.3
{13}
5
{50}
Min.
Up to
flange
rating
Max.
Range limit
[kPa] {m bar}
32
{320}
130
{1300}
500
{5000}
+/–
{ +/–
+/–
{ +/–
+/–
{ +/–
32
320}
130
1300}
500
5000}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig.1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60 °C.
– The maximum span of each sensor can be converted to
different units using factors as below.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
Note) “Seal Not Required” enclosure is allowed.
Authorities
ATEX
Load resistance
2000
Factory
Mutual
1533Ω
1000
600Ω
Operating
area
24V
250
0
10
16.1
10.5V
Power voltage
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
50
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
45V
[V]
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = –40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
Note: For communication with HHC(1) (Model: FXW), min. of 250Ω required.
2
Ex II 1 GD
EEx ia IIC T5 Tamb = –40°C to +40°C
EEx ia IIC T4 Tamb = –40°C to +80°C
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
1500
500
Intrinsic safety
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
Load limitations: see figure below
[Ω]
Flameproof
ATEX
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = –40°C to +40°C
EEx nL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
3.2
Normal operating range
Under scale
Probable under range
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
CSA
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
–
IECEx
Scheme
/SAA
–
20 20.8
21.6 [mA]
Over scale
Burnout
EEx nAL IIC T5 Tamb = –40°C to +40°C
EEx nAL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
3.8 4
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(Span adjustment is not available with 9th
digit code “L, P, Q, S”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
– 100% to + 100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA
by HHC(1).
Temperature limit:
Ambient: – 40 to + 85°C
(– 20 to + 80°C for LCD indicator)
(– 40 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill transmitter)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
Code in the 13th
digit of “Code
symbols”
Lower limit
of
static press
Process
temperature
Fluorinated oil
W, A and D
–20 to 120°C
Silicone oil
H
– 15 to 250°C
Atmospheric
pressure
85 to 300°C
J
Y and G
– 40 to 120°C
S
–15 to 250°C
T
85 to 300°C
2.7kPa abs
{20.3mmHg abs}
0.13kPa abs
{0.98mmHg abs}
Low pressure side contact liquid temperature on transmitter of
Code H, J, S, T is 120°C or lower. Low pressure side contact liquid
temperature of Code K is 85°C or lower
K
–15 to 150°C
Storage: – 40 to + 90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Output mode
v
—
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
(Note) (1) HHC: Hand Held Communicator
3
FKE...4
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4-20 mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ± 0.2% of span
For spans below 1/10 of URL:
± 0.1 + 0.1 0.1 x URL % of span
Span
(
)
(Option) (Code: 21th digit H, K)
For span greater than 1/10 of URL: 0.1% of span
For span below 1/10 of URL:
0.1 x URL
± 0.05 + 0.05
% of span
Span
(
)
± 0.2% of upper range limit (URL) for 3
years.
Temperature effect:
Effects per 28°C change between the limits of – 40°C and + 85°C
(Standard) Zero shift: ± 0.35% of URL
Total effect: ± 0.5% of URL
(Option) (Code: 21th digit J, K)
Zero shift: ± 0.3% of URL
Total effect: ± 0.4% of URL
Static pressure effect:
Zero shift: ± 0.2% of URL / 1MPa
Span shift: – 0.2% of calibrated span /
1MPa
Overrange effect:Zero shift; ± 0.1% of URL for flange rating pressure
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Update period: 120 msec *)
Step response: (without electrical damping)
Stability:
Range code
*)
Time constant *)
“3”
0.55 s
“5” and “6”
0.3 s
Dead time *)
0.2 s
Faster response is available as option (maximum update rate : 25
times per second)
Mounting position effect:
Zero shift, less than 0.3kPa{3m bar} for a
10° tilt in any plane. (No extension)
No effect on span.
This error can be corrected by adjusting
zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec
Internal resistance for external field indicator:
12Ω or less
4
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
And 1-conduit or 2-conduit, as specified.
Process connections:
LP side: 1/4-18 NPT or Rc1/4.
HP side: ANSI, DIN, or JIS raised face
flange. See OUTLINE DIAGRAM for detailed dimensions.
Refer to “Code symbols”
Process-wetted parts material:
LP side
HP side
Material
code
Wetted
Diaphragm &
Process
(7th digit
Diaphragm
sensor body
flange face
cover
in “Code
symbols”)
316 stainless 316L stainless 316 stainless 316L stainless
V
(*1)
316 stainless 316L stainless 316 stainless 316L stainless
J
(*1)
steel
+Au coating
C
316 stainless 316L stainless 316 stainless Hastelloy-C
1
(* )
316 stainless 316L stainless 316 stainless Monel
D
(*1)
E
316 stainless 316L stainless 316 stainless Tantalum
(*1)
Hastelloy-C
Hastelloy-C
H
316 stainless Hastelloy-C
lining
(*1)
Monel lining Monel
316 stainless Monel
M
(*1)
Tantalum
T
316 stainless Tantalum
Tantalum
lining
(*1)
Hastelloy-C
Hastelloy-C
B
Hastelloy-C Hastelloy-C
lining
Monel lining Monel
Monel lining Monel
L
Tantalum
Tantalum
U
Hastelloy-C
Tantalum
lining
316 stainless 316L stainless 316 stainless Tantalum
P
(*1)
316 stainless 316L stainless 316 stainless Zirconium
R
(*1)
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remark: Sensor O-rings: Viton O-ring and teflon gasket selectable.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating (standard),
or 316 stainless steel (SCS14A per JIS
G5121), as specified.
Bolts and nuts: Cr-Mo alloy (standard) or
304 stainless steel
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting flange: 304 stainless steel or
Carbon steel, as specified
Environmental protection:
IEC IP67 and NEMA 6 / 6P
Flange mounting:See drawings
Mass{weight}:
Transmitter approximately 13kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.0kg per 50mm extension of
diaphragm
Optional features
Silicone (Code S)
Indicator:
Silicone (Code T)
Operating pressure
101
{1010}
53.3
{533}
Operating area
13.3
{133}
2.7
{27}
–40 –15
Fig. 1
60 85 120
Process temperature[°C ]
200 230 250
300
Relation between process temperature and
operating pressure
[kPa abs]
{mbar abs}
Sealing liquid:Silicone (Code K)
101
{1010}
Operating pressure
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for
use on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied. See Fig.1 and Fig.2
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating.
Specify if environment is extremely corrosive.
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
Operating area
Non-operating area
0.13
{1.3}
–15
150
Process temperature[°C ]
Fig. 2
Relation between process temperature and
operating pressure
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
5
FKE...4
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
6
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA).
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S on 9th digit).
5. TAG No. (up to 26 alphanumerical characters), if required.
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Description
<Connections>
Process
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
Oval flange
screw
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
7/16-20UNF
7/16-20UNF
M10
M10
7/16-20UNF
Conduit
connection
G 1/2
(×1)
1/2-14NPT (×1)
Pg13.5
(×1)
M20×1.5 (×1)
Pg13.5
(×1)
G 1/2
(×2)
1/2-14NPT (×2)
Pg13.5
(×2)
M20×1.5 (×2)
Pg13.5
(×2)
Note
316 stainless steel
316 stainless steel
316 stainless steel
Hastelloy-C lining
Monel lining
Tantalum lining
316 stainless steel
316 stainless steel
Hastelloy-C lining
Hastelloy-C
Monel lining
Monel
Tantalum lining
Tantalum
Hastelloy-C lining
Hastelloy-C
Monel lining
Monel
Tantalum lining
Tantalum
316L stainless steel 316 stainless steel
316L stainless steel 316 stainless steel
9 10 11 12 13
14 15
21
4
Digit No.
of code
A
B
C
D
E
S
T
V
W
X
Combination with 12th
digit code "C, E, P, Q"
are not available.
<Mounting flange>
Material
Size and rating
304 stainless
JIS 10K 80A
steel
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN40 DN80
DIN PN16 DN100
JIS 20K 80A
ANSI/JPI 600LB 3B
Carbon steel
JIS 10K 80A
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN40 DN80
DIN PN16 DN100
316 stainless
JIS 10K 80A
steel
ANSI/JPI 150LB 3B
ANSI/JPI 150LB 4B
ANSI/JPI 300LB 3B
ANSI/JPI 300LB 4B
ANSI/JPI 600LB 3B
<Span limit (*1) [kPa] {m bar}>
0.32
32
{3.2
320}
1.3
130
{13
1300}
5
500
{50
5000}
<Material>
LP side
Wetted sensor
Diaphragm
Process cover
body
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
F KE
Note 1
0
1
2
3
4
5
6
7
8
9
M
R
A
B
C
D
E
F
G
H
J
K
S
T
U
V
W
X
3
5
6
HP side
Diaphragm and
flange face
316L stainless steel
Hastelloy-C
Monel
Tantalum
Diaphram:
316L stainless steel
+Au coating
Flange face:
316 stainless steel
Hastelloy-C
Monel
Tantalum
Hastelloy-C
Monel
Tantalum
Titanium
Note 3
Zirconium
Note 2, 3
V
C
D
E
J
H
M
T
B
L
U
P
R
Note 1: (*1) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance.
Note 2: (*2) Material Code R; 6th digit code "6" is not available.
Note 3: (*3) 5th digit code "0, 2, 4, 6, 8, A, C, E, G, J" are available.
7
FKE...4
1 2 3 4 5 6 7 8
Digit
Description
Note
<Indicator and arrester>
9
Indicator
Arrester
None
None
Z/S board
Analog, 0 to 100% linear scale
None
attached.
Analog, custom scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
10
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code "A", "S")
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code "A", "S")
FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
CSA, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Diaphragm extension [mm]>
11
Extension [mm]
Applicable material code
0
Any
50
100
(7th digit code "V" only)
150
200
50
100
(7th digit code "H" ,"B" ,"C" only)
150
200
<Options>
12
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Note 4
Yes
(* 4)
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
<Special applications and fill fluid>
13
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "J" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E")
High temp. 250°C
7th digit code "V", "C", "H", "B"
High temp. 300°C
High temp. and vacuum (250°C)
(* 5) Note 5
7th digit code "V"
High temp. and vacuum (300°C)
14
High temp. and high vacuum Silicone oil
<O-ring, gasket and Teflon membrane>
O-ring /Gasket
Teflon membrane
Viton (O-ring)
None
Teflon (gasket)
None
Viton (O-ring)
Yes (5th digit code "0", "2", "4", "6", "8", "A", "C", "E",
Teflon (gasket)
Yes "G", "J", "M", "R", "S", "T", "V", "X" and 11th
digit code "Y" are available.
13th digit code "H, J, S, T, K" are not available.)
F KE
9 10 11 12 13
14 15
21
4
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
A
B
C
D
E
X
R
G
H
J
K
P
T
V
Y
A
B
C
D
E
F
G
H
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
H
J
S
T
K
A
B
C
D
Note 4: (*4) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes"
Note 5: (*5) Treatment; None
8
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
15
21
Description
<Bolt/nut> (* 6)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
304 stainless steel bolt /304 stainless steel nut
<Other options> (* 7)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Note
Note 6
F KE
9 10 11 12 13
14 15
21
4
Digit No.
of code
A
B
E
Note 7
H
J
K
L
T
U
V
Note 6: (*6) In case of tropical use, select stainless bolts and nuts.
Note 7: (*7) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
9
FKE...4
OUTLINE DIAGRAM (Unit:mm)
< 7digit code : Without "B", "L" and "U" >
In case of 4th digit code "A.B.C.D.E"
Note 2)
Vent / drain plug
(When the vent /drain plug attatched
on the upper side of the detector)
In case of 4th digit code "S.V.W.X"
In case of 4th digit code "T"
Flange : ANSI/JPI
-150LB-3B
Fastener
(Flameproof only)
43.5
105
ø80
52.5
105
Up
ø80
94.5
8
10
Zero ADJ.screw
"A" L.P. conn.
88
Down
N holes
h dia
2
Note 1)
With field ind.
t
41.3
20
Inner of gasket
Detail "A"
(L.P conn.)
ø18.5
Oval flang screw
See table 1
ø13
ø15
8
43
143
27
48
2.5
J
øD
øE
øF
øG
øH
59
Detail "C"
Detail "B"
(Conduit conn.)
ø7
17
L
"B" Conduit conn.
"C" Conduit conn.
M N
Vent / drain plug
Cable gland
(option)
(27)
1
G1/2
K
See table 1
See table 1
3
H.P. conn.
Sensor unit
5th digit of the
code symbols
øD
øE
øF
øG
øH
t
P
Electronics unit
N-øh
Flange
0, A, S
185
150
126 100
73
38 116
8-19
JIS 10K 80A
M
200
160
126 100 73
42 116
8-23
JIS 20K 80A
2, C
210
170
126 100 73
48 116
8-23
JIS 30K 80A
1, B
3, D
210
240
175
195
151 103 96
151 103 96
38 141
52 141
8-19 JIS 10K 100A
8-25 JIS 30K 100A
4, E, T
6, G, V
191 152.5 126 100 73
210 168 126 100 73
44 116 4-20
49 116 8-23
ANSI 150LB 3B
ANSI 300LB 3B
R, X
5, F, U
210 168 126 100
229 190.5 151 103
73
96
52 116 8-23
44 141 8-20
ANSI 600LB 3B
ANSI 150LB 4B
7, H, W
254
200
151 103 96
52 141 8-23
ANSI 300LB 4B
8, J
200
160
126 100 73
44 116 8-18
DIN PN40 DN80
9, K
11TH DIGIT
L (mm)
CODE
Earth terminal
220
180
151 103 96
40 141 8-18
DIN PN16 DN100
4th digit of the
code symbols
9.5 ~ 13
Y
0
A
E
50
B
F
100
10.5 ~ 17.5
C
G
150
11
D
H
200
11.5 ~ 18.5
Conduit conn.
K
M N
A, S
G1/2
B, T
1/2-14NPT 18 5
C, V
Pg13.5
8
D, W
M20 1.5
16 5
E, X
Pg13.5
8
17 8
10
10
Cable gland is supplied in case of flamproof packing type.
ø11 cable is suitable.
Note 2)
The pressure connector is located on the down side surface of
the detector, when the vent/drainplug is attatched on the upper
side of the detector
(when the 21th digit of the code symbols: c, e or d).
1/4-18NPT
4.5 1/4-18NPT
1/4-18NPT
4.5 1/4-18NPT
CK CK
2
3
160 296
327
154 290
~ 18
Rc1/4
CONNECTION DIAGRAM
1
333
~ 17
Press.conn.
J
Table 1
Note 1)
MASS APPROX.
(kg)
Oval flage screw
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
SCREW DEPTH15
M10
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
< 7th digit code : "B", "L" or "U" >
In case of 4th digit code "T"
In case of 4th digit code "A.B.C.D.E"
In case of 4th digit code "S.V.W.X"
Oval flange screw
See table 1
Fastener
(Flameproof only)
Zero ADJ.screw
94.5
8
41.3
10
Flange : ANSI/JPI
-150LB-3B
ø80
ø80
52.5
105
105
107
Up
88
Down
2
N holes
h dia
(27)
1
"A" or "B" L.P. conn.
Vent / drain plug
Note)
Cable gland
(option)
"D" Conduit conn.
With field ind.
"C" Conduit conn.
t
Earth terminal
91
ø16
1/4-18NPT
0
-0.1
ø16
2
1
+0.2
ø12 +0.1
10
øG
Detail "B"
(L.P conn.)
Detail "A"
(L.P. conn.)
4th digit code "S"
46.4
øH
øE
øF
ø4
3
H.P. conn.
Sensor unit
Detail "C"
(Conduit conn.)
Electronics unit
Detail "D"
ø13
ø15
A
E
50
B
F
100
12.5 ~ 19.5
C
G
150
13
D
H
200
13.5 ~ 20.5
12
CONNECTION DIAGRAM
~ 19
CK CK
øD
øE
0, A, S
185
M
2, C
1, B
N-øh
Flange
73
38 116 8-19
JIS 10K 80A
160
126 100 73
42 116 8-23
JIS 20K 80A
170
175
126 100 73
151 103 96
48 116 8-23
38 141 8-19
JIS 30K 80A
JIS 10K 100A
240 195 151 103 96
191 152.5 126 100 73
210 168 126 100 73
52 141 8-25
44 116 4-20
49 116 8-23
JIS 30K 100A
ANSI 150LB 3B
ANSI 300LB 3B
øG
øH
150
126 100
200
210
210
øF
t
P
126 100 73
52 116 8-23
ANSI 600LB 3B
5, F, U
229 190.5 151 103 96
44 141 8-20
ANSI 150LB 4B
7, H, W
254
200
151 103 96
52 141 8-23
ANSI 300LB 4B
8, J
200
160
126 100 73
44 116 8-18
DIN PN40 DN80
9, K
220
180
151 103 96
40 141 8-18
DIN PN16 DN100
R, X
210
G1/2
~ 20
5th digit of the
code symbols
Note)
K
See table 1
317 144 290
3, D
4, E, T
6, G, V
17
Mass apprpx.
11th degit
L (mm)
(kg)
code
1
2
3
Y
11.5 ~ 15
0
323 150 286
M N
øD
43
40.5
Inner of gasket
186
L
20
168
4th digit of the
code symbols
Conduit conn.
K
M N
A, S
G1/2
17
8
B, T
1/2-14NPT 16
5
C, V
Pg13.5
8
4.5
D, W
M20 1.5
16
5
E, X
Pg13.5
8
4.5
Oval flage screw
7/16-20UNF
Screw depth10
7/16-20UNF
Screw depth10
M10
Screw depth10
M10
Screw depth10
7/16-20UNF
Screw depth10
Table 1
Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
11
FKE...4
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan