FUJI EDSX6-124D

DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER
FHC...4
DATA SHEET
The FCX–A2e differential pressure (flow) transmitter accurately measures differential pressure, liquid level, gauge
pressure or flow rate and transmits a proportional 4 to 20mA
signal. The transmitter utilizes a unique micromachined
capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and
functionality.
FEATURES
1. High accuracy ±0.1%
0.1% accuracy is a standard feature.
Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges
without additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects
the pressure sensor against changes in temperature,
static pressure, and overpressure substantially reduces
total measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX–A2e series transmitter offers bilingual communications to speak both Fuji proprietary protocol and
HART®. Any HART ® compatible devices can communicate with FCX–A2e.
4. Application flexibility
Various options that render the FCX–A2e suitable for
almost any process applications include.
– Analog indicator at either the electronics side or terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
5. Programmable output Linearization Function
In addition to Linear and Square Root, output signal can
be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR
NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
F HC 33
F HC 35
F HC 36
Static pressure
[MPa] {bar}
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 16
{–1 to + 160 }
–0.1 to + 16
{–1 to + 160 }
Span limit [kPa]
{m bar}
Max.
Min.
1.06
{ 10.6 }
4.33
{ 43.3 }
16.66
{166.6 }
{
{
{
32
320 }
130
1300 }
500
5000 }
Range limit
[kPa] {m bar}
+/–
{ +/–
+/–
{ +/–
+/–
{ +/–
32
320 }
130
1300 }
500
5000 }
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor:
See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs)
at temperature below 60°C
– The maximum span of each sensor can be converted
to different units using factors as below.
1MPa =10 3KPa=10bar=10.19716kgf/cm2
=145.0377psi
1kpa=10mbar=101.9716mmH2O=4.01463inH2O
Over range limit: To maximum static pressure limit
Output signal:
4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional arrester.
EDSX6-124d
Date
Apr. 25, 2003
FHC...4
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
45V
16.1
10.5V
Power voltage
50
[V]
Note: For communication with HHC(1) (Model: FXW), min. of 250 Ω
required.
Hazardous locations:
Authorities
Factory
Mutual
CSA
TIIS
Flameproof
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex do IIB+H2 T4
Intrinsic safety
Class I II III
Div. 1
Groups A thru. F
Class I II III
Div. 1
Groups A thru. G
Ex ia II C T4 (*)
Type n
Nonincendive
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
(*) Approval pending
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(span adjustment is not available with 9th
digit code "L, P, M, Q, S, N").
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
3.2
3.8 4
20 20.8
Temperature limit:
Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (flameproof
or intrinsic safety), ambient temperature must be within the limits specified in each standard.
Process: – 40 to +120°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC's version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Tag No.
Model No.
Serial No.
Engineering unit
Range limit
Measuring range
Damping
Output mode Linear
Square root
Burnout direction
Calibration
Output adjust
Data
Self diagnoses
Printer
External switch lock
Transmitter display
Linearize
Rerange
21.6 [mA]
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA
by HHC(1).
(Note) (1) HHC: Hand Held Communicator
2
Set
v
v
—
v
—
v
v
v
v
v
v
v
—
—
—
v
v
v
v
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function” from HHC(1).
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Display
v
v
v
v
v
v
v
v
v
v
v
—
v
v
—
v
v
v
v
Performance specifications
Physical specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.05+0.05
% of span
Span
Stability:
± 0.2% of upper range limit (URL) for 6
month.
Temperature effect:
Effects per 28°C change between the
limits of – 40°C and +85°C
Zero shift;
URL
± 0.1+0.025
%
Span
(
)
(
)
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
1 conduit only.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
Process-wetted parts material:
Material
code
(7th digit Process cover
in Code
symbols)
V
316 stainless
steel(*1)
Diaphragm
Wetted
sensor body
316L stainless 316 stainless
steel
steel
Vent/drain
316 stainless
steel
Notes: * (1) SCS14 per JIS G 5121
Total effect;
(
± 0.125+0.025
URL
Span
)%
Static pressure effect:
Zero shift (% of URL);
± 0.1%/10MPa {100bar}
Overrange effect: ± 0.3%/16MPa {160bar}
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar}
Range code
(6th digit in code symbols)
Time constant
“3”
0.3 s
“5” and “6”
0.2 s
Dead time
0.2 s
for a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting
Zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Low flow cut-off: In the case of square root output mode,
customer configurable for any point
between 0 to 20% of output.
Remark:
Sensor O-rings: Viton O-ring and teflon gasket
selectable.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating.
Bolts and nuts: Cr-Mo alloy (standard),
304 stainless steel or 630 stainless
steel. Static pressure rating for code
“3” with 304 stainless steel bolts is
degraded to 10MPa.
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67
Mounting:
On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting.
Mass{weight}:
Transmitter approximately 4.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
3
FHC...4
Optional features
ACCESSORIES
Indicator:
A plug-in analog indicator (1.5% accuracy) can be housed in the electronics
compartment or in the terminal box of
the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but
the fill fluid is standard silicone oil. Not
for use on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (16
MPa) is degraded to 10MPa.
Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter.
Silicone oil (Code:Y,G,N)
Operating pressure
[kPa abs]
{mbar abs}
101
{1010}
Operating
area
20
{200}
4
{40}
2.7
{27}
None-operating
area
–40
60
120
Process temperature[°C ]
Fig. 1 Relation between process temperature and operating pressure
4
Oval flanges:
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2 -14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Equalizing valves:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in Carbon steel or in 316 stainless steel and in pressure rating 16MPa
or 42MPa.
Hand-held communicator:
(Model FXW, refer to Data Sheet No.
EDS 8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Output mode (linear or square root output)
Unless otherwise specified, output mode is linear.
5. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S on 9th digit).
6. Tag No. (up to 26 alphanumerical characters), if required.
CODE SYMBOLS
Digit
4
1 2 3 4 5 6 7 8
Description
<Connection>
Oval flange
Conduit
Process
connection
connection screw
7/16-20UNF
G1/2
(×1)
Rc1/4
7/16-20UNF
1/2-14NPT (×1)
1/4-18NPT
1/4-18NPT
M10
Pg 13.5
(×1)
1/4-18NPT
M10
M20×1.5 (×1)
7/16-20UNF
1/4-18NPT
Pg 13.5
(×1)
5, 6, 7 <Span and materials>
Static
Span limit (*2) Process
Diaphragm
pressure
cover
[MPa]
[kPa]
{bar}
(m bar)
–0.1 to+16 1.06…32
316 stainless steel 316L stainless steel
{–1 to+160} {10.6…320}
4.33…130
316 stainless steel 316L stainless steel
{43.3…1300}
16.66…500 316 stainless steel 316L stainless steel
{166.6…5000}
9
10
11
12
Note
FHC
9 10 11 12 13
14 15
4
Digit No.
of code
A
B
C
D
E
Wetted
cell body
316 stainless steel
33V
316 stainless steel
35V
316 stainless steel
36V
<Indicator and arrester>
Indicator
Arrester
None
None
Z/S board
Analog, 0 to 100% linear scale
None
attached.
Analog, 0 to 100% sq. root scale
None (*1) Approval pending Note 1
Analog, custom scale
None
for10th digit
Analog, double scale (Linear and sq. root)
None
code “G, H, J“
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes (*1)
Note 1
Analog, custom scale
Yes
Analog, double scale (Linear and sq. root)
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital 0 to 100% square root
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital 0 to 100% square root
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100% square root
Approval pending
(Local adjustment unit with LCD display)
None
for 10th digit code
Digital, 0 to 100%
“D, E, G, H, J“
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
Digital, 0 to 100% square root
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code “A“)
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A“)
FM, Flameproof (or explosionproof) (Available for 4th digit code “B“)
CSA Frameproof (or explosion proof) (Available for 4th digit code “B“)
TIIS, Intrinsic safety (Approval pending)
FM, Intrinsic safety and Nonincendive
CSA Intrinsic safety and Nonincendive
<Vent/ drain and mounting bracket>
Vent/drain
Mounting bracket
Standard
None
Standard
Yes, stainless steel
Side
None
Side
Yes, stainless steel
<Options>
Extra SS tag plate
Stainless steel elec, housing
Coating of cell
None
None
None
Note 2
Yes
None
None
(*2)
None
None
Yes
Yes
None
Yes
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
1
2
3
4
5
6
A
B
C
D
E
G
H
J
A
C
D
F
Y
B
M
N
Note 1: (*1) In case of square root output mode, square root scale is not available.
Note 2: (*2) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”.
5
FHC...4
1 2 3 4 5 6 7 8
Digit
13
14
15
Note 4:
Note 5:
Note 6:
Note 7:
6
Description
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Degreasing
Silicone oil
Oxygen service Fluorinated oil (7th digit code “V” only)
NACE specification Silicone oil (*7)
<Sensor O-ring / Gasket>
Viton (O-ring)
Teflon (gasket)
<Bolt/nut> (*6)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
(*4)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel bolt/304 stainless steel nut (*5)
630 stainless steel bolt/304 stainless steel nut
(*4)
(*5)
(*6)
(*7)
Note
FHC
Note 7
9 10 11 12 13
14 15
4
Y
G
A
N
A
B
Note 6
Note 4
Note 5
Static pressure should be –0.1 to +10MPa{–1 to +100bar}.
In case of stainless steel bolt, static pressure should be –0.1 to +10MPa {–1 to + 100bar}.
In case of tropical use, select stainless bolts and nuts.
Not available for 15th digit code "A, B".
A
B
C
D
E
F
Digit No.
of code
OUTLINE DIAGRAM (Unit:mm)
Note 2)
Vent/drain plug
(When the vent/drain plug
attatched on the upper side
of the detector)
Fastener
(Flameproof only)
Zero ADJ. screw
MTG. pipe JIS 50A
(2B)
"A" Press. conn.
41
52.5
Down
88
38
U-bolt M8
58
Note 1)
Cable gland
(option)
37
(27)
210
4 Holes
9 Dia.
ø80
70
130
120
ø80
Up
"C" Conduit conn.
"B" Conduit conn.
Vent/drain plug
With field ind. (option)
Approx. 147
Detail "A"
(Press. conn.)
ø18.5
Detail "B"
(Conduit conn.)
43
Detail "C"
Earth terminal
ø13
H
2.5
ø15
Electronics
unit
Side vent
(option)
G 1/2
D
Press.conn.
(Low pressure side)
See table 1
See table 1
41.3
ø7
Press. conn.
H
A
G1/2
17
8
Rc1/4
B
1/2-14NPT
16
5
1/4-18NPT
C
Pg13.5
8
4.5
1/4-18NPT
D
M20 1.5
16
5
1/4-18NPT
E
Pg13.5
8
4.5
1/4-18NPT
Sensor
unit
Press.conn.
(High pressure
side)
4-M8 12
Conduit conn.
D
E
F
4th digit of the
code symbols
231
E
17
8
F
Oval flange screw
See table 1
Oval flange screw
7/16-20UNF
Screw depth 15
7/16-20UNF
Screw depth 15
M10
Screw depth 15
M10
Screw depth 15
7/16-20UNF
Screw depth 15
Table 1
Note 1) Cable gland is supplied in case of 10th digit code "C".
ø11 cable is suitable.
Note 2) The pressure connector is located on the down side surface of
the detector, when the vent /drain plug is attatched on the upper
side of the detector.
54
70
104
CONNECTION DIAGRAM
CK CK
(M4 screws)
7
FHC...4
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Basic
standard
Performance
criteria
IEC61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
IEC61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
IEC61000-4-8
A
Burst
2kV
5kHz
IEC61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
IEC61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
IEC61000-4-6
A
Phenomenon
Electrostatic
discharge
Test value
4kV (Contact)
8kV (Air)
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan