FUJI EDSX7-66H

LEVEL TRANSMITTER
FKE...5
DATA SHEET
The FCX -AIII level transmitter accurately measures liquid level
and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon
sensor with state-of-the-art microprocessor technology to
provide exceptional performance and functionality.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard
feature for all models covering 0.32kPa {3.2mbar} range
to 500kPa {5bar} high differential pressure range. 0.1%
accuracy is available as option. Fuji’s micro-capacitance
silicon sensor assures this accuracy for all elevated or
suppressed calibration ranges without additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX -AIII.
4. Application flexibility
Various options that render the FCX -AIII suitable for
almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum service.
5. Programmable output Linearization Function
Output signal can be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
F KE
3
F KE
5
FKE
6
Static
pressure
Span limit [kPa] {m bar}
to
 Up
ange
 flrating

0.32
{3.2}
1.3
{13}
5
{50}
Min.
Max.
32
{320}
130
{1300}
500
{5000}
Range limit
[kPa] {m bar}
+/−
{ +/−
+/−
{ +/−
+/−
{ +/−
32
320}
130
1300}
500
5000}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig.1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60 °C.
– The maximum span of each sensor can be converted to
different units using factors as below.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
EDSX7-66h
Date
Aug. 10, 2011
FKE...5
Load limitations: see figure below
Process:
[Ω]
Load resistance
2000
Code in the 13th
digit of “Code
symbols”
1474Ω
1500
R=
E-10.5
(Imax+0.9)x10-3
W, A and D
−20 to 120°C
Silicone oil
H
−15 to 250°C
Operating
area
24V
Y and G
−40 to 120°C
S
−15 to 250°C
10
16.35
10.5V
Power voltage (DC)
50
E[ V ]
Note: For communication with HHC(1) (Model: FXW), min. of 250 required.
Hazardous locations: See TABLE 2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
−100% to + 100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction:Selectable from HHC(1)
If self-diagnostic detect transmitter failure,
the analog signal will be driven to either
“Output Hold”, “Output Overscale” or
“Output Underscale” modes.
“Output Hold”: Output signal is hold as the value just
before failure happens.
“Output Overscale”: Adjustable within the range 20.0mA
to 22.5mA from HHC(1)
“Output Underscale”: Adjustable within the range 3.2mA
to 4.0mA from HHC(1)
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Probable over range
Output Limits comforming the NAMUR NE43 by order.
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA
by HHC(1).
Temperature limit:
Ambient: −40 to + 85°C
(−20 to + 80°C for LCD indicator)
(−40 to + 60°C for arrester option)
(−10 to + 60°C for fluorinated oil fill transmitter)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
0.13kPa abs
{0.98mmHg abs}
Low pressure side contact liquid temperature on transmitter of
Code H, J, S, T is 120°C or lower. Low pressure side contact liquid
temperature of Code K is 85°C or lower
Storage: −40 to + 90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than 7.0
(or FXW
1– 4), for FCX -AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Output mode
v
—
v
—
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326-1: 2006
(Note) (1) HHC: Hand Held Communicator
2
2.7kPa abs
{20.3mmHg abs}
−15 to 150°C
K
0
Atmospheric
pressure
20 to 300°C
T
45V
Lower limit
of
static press
20 to 300°C
J
577Ω
250
3.2
Fluorinated oil
1000
500
Process
temperature
Performance specifications
Physical specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4-20 mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ±0.2% of span
For spans below 1/10 of URL:
(
± 0.1 + 0.1
)
0.1 x URL
% of span
Span
(Option) (Code: 21th digit H, K)
For span greater than 1/10 of URL: 0.1% of span
For span below 1/10 of URL:
0.1 x URL
% of span
Span
(
)
± 0.05 + 0.05
Stability:
±0.2% of upper range limit (URL) for 10
years.
Temperature effect:
Effects per 28°C change between the
limits of −40°C and +85°C
(
(Standard) Zero shift: ± 0.35
(
Total effect: ± 0.5
URL
X
URL
X
)%
)%
(Option) (Code: 21th digit J, K)
Zero shift: ±0.3% (X>1/4URL)
(
± 0.1 + 0.2
0.25 x URL
%(x<1/4URL)
X
)
Total effect: ±0.4% (X>1/4URL)
(
± 0.2 + 0.2
0.25 x URL
%(x<1/4URL)
X
)
Static pressure effect:
Zero shift: ±0.2% of URL / 1MPa
Span shift: −0.2% of calibrated span /
1MPa
Overrange effect: Zero shift; ±0.1% of URL for flange rating
pressure
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
Update rate:
60 msec
Step response: (without electrical damping)
Range code
Time constant (at 23°C)
“3”
0.55 s
“5” and “6”
0.3 s
Dead time
0.12 s
Mounting position effect:
Zero shift, less than 0.3kPa {3m bar} for
a 10° tilt in any plane. (No extension)
No effect on span.
This error can be corrected by adjusting
zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
Electrical connections:
G 1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
LP side: 1/4-18 NPT or Rc1/4.
HP side: ANSI, DIN, or JIS raised face
flange. See OUTLINE DIAGRAM for
detailed dimensions.
Refer to “Code symbols”
Process-wetted parts material:
LP side
HP side
Material
code
Wetted
Process
Diaphragm
&
(7th digit
Diaphragm
sensor body
cover
flange face
in “code
symbols”)
316 stainless 316L stainless 316 stainless 316L stainless
V
(*1)
316 stainless 316L stainless 316 stainless 316L stainless
J
(*1)
steel
+Au coating
316 stainless 316L stainless 316 stainless Hastelloy-C
C
(*1)
316 stainless 316L stainless 316 stainless Monel
D
(*1)
316 stainless 316L stainless 316 stainless Tantalum
E
(*1)
Hastelloy-C
316 stainless Hastelloy-C
H
Hastelloy-C
lining
(*1)
Monel lining Monel
316 stainless Monel
M
(*1)
Tantalum
316 stainless Tantalum
T
Tantalum
lining
(*1)
316 stainless 316L stainless 316 stainless Tantalum
P
(*1)
316 stainless 316L stainless 316 stainless Zirconium
R
(*1)
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remark: Sensor O-rings: Viton O-ring and teflon gasket selectable.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with polyester
coat ing (standard), or 316 stainless
steel (ASTM CF8M), as specified.
Bolts and nuts: Cr-Mo alloy (standard) or
304 stainless steel
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting flange: 304 stainless steel or
Carbon steel, as specified
Environmental protection:
IEC IP67 and NEMA 6 / 6P
Flange mounting: See drawings
Mass {weight}: Transmitter approximately 10.2 to 19.2kg
without options.
Add; 0.5kg for mounting bracket
4.5kg for stainless steel housing
option
1.0kg per 50mm extension of
diaphragm
3
FKE...5
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy).
An optional 5-digit LCD meter with engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but
the fill fluid is standard silicone oil. Not
for use on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied. See Fig.1 and Fig.2
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating.
Specify if environment is extremely corrosive.
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
Silicone (Code S)
[kPa abs]
{mbar abs}
Silicone (Code T)
Sealing liquid:Silicone (Code K)
101
{1010}
53.3
{533}
Operating area
Operating pressure
Operating pressure
101
{1010}
13.3
{133}
Operating area
Non-operating area
2.7
{27}
0.13
{1.3}
–40 –15
Fig. 1
4
20 60 85 120
Process temperature[°C ]
200 230 250
Relation between process temperature and
operating pressure
300
–15
150
Process temperature[°C ]
Fig. 2
Relation between process temperature and
operating pressure
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No. EDS6128)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occurred in the transmitter.
Hold / Overscale / Underscale.
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S, 2, 5 on 9th digit).
5. TAG No. (up to 14 alphanumerical characters), if required.
5
FKE...5
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Note
Description
<Low pressure Connections>
<Process connection> <Oval flange screw>
Rc1/4
7/16-20UNF
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10
1/4-18NPT
M10
1/4-18NPT
7/16-20UNF
Rc1/4
7/16-20UNF
1/4-18NPT
7/16-20UNF
1/4-18NPT
M10
1/4-18NPT
M10
1/4-18NPT
7/16-20UNF
<Conduit connection> <Case type>
G1/2
T type
1/2-14NPT
T type
Pg 13.5
T type
M20×1.5
T type
Pg 13.5
T type
G1/2
L type
1/2-14NPT
L type
Pg 13.5
L type
M20×1.5
L type
Pg 13.5
L type
<Mounting flange>
Material
Size and rating
304 stainless
JIS 10K 80A
steel
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN40 DN80
DIN PN16 DN100
JIS 20K 80A
ANSI/JPI 600LB 3B
Carbon steel
JIS 10K 80A
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN40 DN80
DIN PN16 DN100
316 stainless
JIS 10K 80A
steel
ANSI/JPI 150LB 3B
ANSI/JPI 150LB 4B
ANSI/JPI 300LB 3B
ANSI/JPI 300LB 4B
ANSI/JPI 600LB 3B
<Span limit (*1) [kPa] {m bar}>
0.32
32
{3.2
320}
1.3
130
{13
1300}
5
500
{50
5000} (*2)
<Material>
LP side
Process cover
Diaphragm
Wetted sensor
body
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel 316L stainless steel 316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
316 stainless steel
F KE
9 10 11 12 13
14 15
21
5
5
6
7
8
9
S
T
V
W
X
0
1
2
3
4
5
6
7
8
9
M
R
A
B
C
D
E
F
G
H
J
K
S
T
U
V
W
X
Note 1
3
5
Note 2
HP side
Diaphragm and
flange face
316L stainless steel
Hastelloy-C
Monel
Tantalum
Diaphram:
316L stainless steel
+Au coating
Flange face:
316 stainless steel
Hastelloy-C
Hastelloy-C lining Hastelloy-C
Monel
Monel
Monel lining
Tantalum
Tantalum
Tantalum lining
Note 3
316L stainless steel 316 stainless steel Titanium
Note 3
316L stainless steel 316 stainless steel Zirconium
6
V
C
D
E
J
H
M
T
P
R
Note 1: (*1) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance.
Note 2: (*2) Not available for 7th digit code "R".
Note 3: (*3) 5th digit code "0, 2, 4, 6, 8, A, C, E, G, J" are available.
6
Digit No.
of code
1 2 3 4 5 6 7 8
Note
Digit
Description
<Indicator and arrester>
9
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, custom scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100% linear scale
None
Digital, custom scale
None
Digital, 0 to 100% linear scale
Yes
Digital, custom scale
Yes
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
None
Digital, custom scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Yes
Digital, custom scale
(Local configurator unit with LCD display)
Yes
<Approvals for hazardous locations>
10
None (for ordinary locations)
Note 8
TIIS, Flameproof (Cable gland seal) (*8)
TIIS, Intrinsic safety
Note 11
FM, Flameproof (or explosionproof) (*11)
FM, Intrinsic safety and nonincentive
Note 11
FM Combined of flameproof and intrinsic safety (*11)
Note 10
ATEX Flameproof (*10)
ATEX Intrinsic safety
ATEX Type n
Note 10
ATEX Combined of flameproof and intrinsic safety (*10)
Note 10
IECEx Scheme, Flameproof (*10)
IECEx Scheme, Intrinsic safety
Note 11
CSA, Flameproof (or explosionproof) (*11)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
<Diaphragm extension [mm]>
11
Extension [mm]
Applicable material code
0
Any
50
100
(7th digit code "V" only)
150
200
<Options>
12
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
Note 4
None
None
None
Yes
None
None
None
(*4)
None
Yes
Yes
None
Yes
Note 7
None
Yes
Yes
(*7)
Note 7
Yes
Yes
Yes
<Special applications and fill fluid>
13
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Fluorinated oil (7th digit code "V","J" only)
Oxygen service
Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E")
Chlorine service
High temp. 250°C
7th digit code "V", "C", "H", "B"
High temp. 300°C
High temp. and vacuum (250°C)
(* 5) Note 5
7th digit code "V"
High temp. and vacuum (300°C)
High temp. and high vacuum Silicone oil
<O-ring, Gasket and Teflon membrane>
14
Teflon (gasket)
Teflon (gasket) and Teflon membrance
5th digit code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", "M",
"R", "S", "T", "V", "X" and 11th digit code "Y" are available.
13th digit code "H", "J", "S", "T", "K" are not available.
7th digit code "V", "J" are available.
Note 4: (*4) Customer tag number can be engraved on standard stainless
steel name plate. If extra tag plate is required, select "Yes"
Note 5: (*5) Treatment; standard
Note 7: (*7) Not avilable for 10th digit code "C".
F KE
9 10 11 12 13
14 15
21
5
Digit No.
of code
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
Y
A
B
C
D
Y
B
M
N
P
Q
Y
W
G
A
D
H
J
S
T
K
B
D
Note 8: (*8) Available for 4th digit code "S".
Note 10: (*10) Available for 4th digit code "6", "8", "T", "W".
Note 11: (*11) Available for 4th digit code "6", "T".
7
FKE...5
1 2 3 4 5 6 7 8
Digit
15
21
Description
<Bolt/nut> (* 12)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/carbon steel nut
304 stainless steel bolt /304 stainless steel nut
316 stainless steel bolt /316 stainless steel nut
<Other options> (* 6)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Opposite Vent/Drain Plug Position
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Opposite Vent/Drain Plug Position
Instruction manual unattached
Note 6: (*6)
If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note 12: (*12) If case of tropical use, select stainless bolts and nuts.
8
Note
Note 12
F KE
9 10 11 12 13
14 15
21
5
A
B
E
U
Note 6
H
J
K
C
L
T
U
V
P
Digit No.
of code
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: L type>
φF
Standard
Corrosionmaterials
resistant
specification materials
specification
NOTE1)
5th digit of the
code symbols
φD
φE
0, A, S
185
150
126
φH±1
t
P
N-φh
FLANGE
134
100
73
38
116
8-19
JIS-10K-80A
NOTE2)
M
200
160
126
134
100
73
42
116
8-23
JIS-20K-80A
2, C
210
170
126
134
100
73
48
116
8-23
JIS-30K-80A
1, B
210
175
151
158
103
96
38
141
8-19
JIS-10K-100A
3, D
240
195
151
158
103
96
52
141
8-25
JIS-30K-100A
126
134
100
73
44
116
4-20
ANSI 150LB 3B
100
73
49
116
8-23
ANSI 300LB 3B
100
73
52
116
8-23
ANSI 600LB 3B
ANSI 150LB 4B
4, E, T
191 152.5
6, G, V
210
168
126
134
R, X
210
168
126
134
conduit conn.
4th digit of the
code symbols
φG
Press. Conn.
D
E
F
H
S
G1/2
18
2
Rc 1/4
T
1/2-14NPT
16
4
1/4-18NPT
V
Pg13.5
10.5
4.5
1/4-18NPT
W
M20×1.5
16
4
1/4-18NPT
X
Pg13.5
10.5
4.5
1/4-18NPT
Oval flange screw
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
SCREW DEPTH15
M10
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
TABLE 1
5, F, U
229 190.5
151
158
103
96
44
141
8-20
7, H, W
254
200
151
158
103
96
52
141
8-23
ANSI 300LB 4B
8, J
200
160
126
134
100
73
44
116
8-18
DIN PN40 DN80
9, K
220
180
151
158
103
96
40
141
8-18
DIN PN16 DN100
NOTE1) In case of the 7th digit of type code is V, J.
NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T, P, R.
N HOLES h DIA
11th digit of the
L±1.5 MASS APPROX. (kg)
code symbols
Y
A, E
B, F
C, G
D, H
0
50
100
150
200
NOTE4)
L1
L2
L3
L4
L5
L6
309 151 278 320 159 289
10.2 ∼ 13.7
10.7 ∼ 17.7
11.2 ∼ 18.2
304 146 273 315 154 284
11.7 ∼ 18.7
12.2 ∼ 19.2
IN CASE OF 4TH DIGIT CODE S, V, W, X
103
IN CASE OF 4TH DIGIT CODE T
DETAIL A
(PRESS. CONN.)
126
10
WITH DIGITAL IND.
103
41
φ81
φ18.5
43
H
B CONDUIT CONN.
2.5
8
(21)
(11)
8
WITH ANALOG IND.
EARTH TERMINAL
10
SEE TABLE1
OVAL FLANGE SCREW
SEE TABLE1
BENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE3)
DETAIL B
(CONDUIT. CONN.)
φ15
F
L3
(L6)
41.3
ZERO ADJ. SCREW
E
FLANGE FOR H.P
L2
(L5)
VENT/DRAIN PLUG
46
L1
(L4)
27
A PRESS. CONN.
t
D
20
INNER DIA OF
GASKET
L±1.5
SEE TABLE1
φH±1
φG
φF
φE
φD
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
G1/2
DETAIL C
φ33.5
φ13
106
CONNECTION DIAGRAM
<SS TAG PLATE>
17
19
"C" CONDUIT CONN.
G1/2
CABLE GLAND
−/CK− CK+
75
+
20
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
NOTE4) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T"
9
FKE...5
<AMP. case: T type>
φF
5th digit of the
code symbols
φD
φE
0, A, S
185
150
Standard
Corrosionmaterials
resistant
specification materials
specification
NOTE1)
φG
φH±1
t
P
N-φh
FLANGE
100
73
38
116
8-19
JIS-10K-80A
NOTE2)
126
134
conduit conn.
4th digit of the
code symbols
Press. Conn.
D
E
F
H
5
G1/2
18
2
Rc 1/4
6
1/2-14NPT
16
4
1/4-18NPT
Pg13.5
10.5
4.5
1/4-18NPT
M
200
160
126
134
100
73
42
116
8-23
JIS-20K-80A
7
2, C
210
170
126
134
100
73
48
116
8-23
JIS-30K-80A
8
M20×1.5
16
4
1/4-18NPT
1, B
210
175
151
158
103
96
38
141
8-19
JIS-10K-100A
9
Pg13.5
10.5
4.5
1/4-18NPT
3, D
240
195
151
158
103
96
52
141
8-25
JIS-30K-100A
126
134
100
73
44
116
4-20
ANSI 150LB 3B
100
73
49
116
8-23
ANSI 300LB 3B
100
73
52
116
8-23
ANSI 600LB 3B
ANSI 150LB 4B
4, E, T
191 152.5
6, G, V
210
168
126
134
R, X
210
168
126
134
Oval flange screw
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
SCREW DEPTH15
M10
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
TABLE 1
5, F, U
229 190.5
151
158
103
96
44
141
8-20
7, H, W
254
200
151
158
103
96
52
141
8-23
ANSI 300LB 4B
8, J
200
160
126
134
100
73
44
116
8-18
DIN PN40 DN80
9, K
220
180
151
134
103
96
40
141
8-18
DIN PN16 DN100
NOTE1) In case of the 7th digit of type code is V, J.
NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T, P, R.
11th digit of the
L±1.5 MASS APPROX. (kg)
code symbols
Y
A, E
0
50
10.2 ∼ 13.7
B, F
C, G
D, H
100
150
200
11.2 ∼ 18.2
L1
L2
WITH ANALOG IND.
NOTE4)
L3
L4
L5
N HOLES h DIA
L6
WITH DIGITAL IND.
322 151 305 333 159 316
(21)
(11)
10.7 ∼ 17.7
11.7 ∼ 18.7
317 146 300 328 154 311
12.2 ∼ 19.2
IN CASE OF 4TH DIGIT CODE 5, 7, 8, 9
8
100
IN CASE OF 4TH DIGIT CODE 6
ZERO ADJ. SCREW
DETAIL A
(PRESS. CONN.)
100
B CONDUIT CONN.
φ18.5
20
2.5
10
127
8
H
EARTH TERMINAL
10
SEE TABLE1
L3
(L6)
A PRESS. CONN.
DETAIL B
(CONDUIT. CONN.)
φ15
41.3
L1
(L4)
OVAL FLANGE SCREW
SEE TABLE1
F
BENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE3)
VENT/DRAIN PLUG
E
46
L2
(L5)
27
FLANGE FOR H.P
D
20
INNER DIA OF
GASKET
L±1.5
t
SEE TABLE1
φH±1
φG
φF
φE
φD
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
10
NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P).
NOTE4) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T"
TABLE 2
Authorities
ATEX
Intrinsic safety
Authorities
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Tamb
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Note) “Seal Not Required” enclosure is allowed.
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester), Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp. = +120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
−
Type n
Nonincendive
Authorities
ATEX
TIIS
NEPSI
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
ATEX
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
Flameproof
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
−
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
11
FKE...5
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan