SMALL FLANGE REMOTE SEAL TYPE PRESSURE TRANSMITTER DATA SHEET FKW...4 The FCX –A2 small flange remote seal type pressure transmitter accurately measures gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. Directly connectable to 1-1/2in and 2in flanges The transmitter is connectable to 1-1/2in and 2in pipes without a reducer. 2. Connectable to 1/2in and 3/4in pipes Use of direct mounting adapter allows the transmitter to be connected to the following process. 1/2in and 3/4in flanges Screw connection 1/2-14NPT, 3/4-14NPT, Rc1/2, Rc3/4 3. Minimum environmental influence The “Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 4. Fuji/HART ® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 5. Application flexibility Various options that render the FCX–A2 suitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, vacuum seals 6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. EDSX5-82k Date Apr. 3, 2007 FKW...4 SPECIFICATIONS Authorities ATEX Functional specifications Service: Liquid, gas, or vapour Span, range, and overrange limit: Span limit [kPa]{bar} Range limit [kPa]{bar} Type Min. F KW 2 F KW 3 F KW 4 Max. 50 {0.5} 300 {3} 1000 {10} 500 {5} 3000 {30} 10000 {100} –100 to +500 {–1 to +5} –100 to +3000 {–1 to +30} –100 to 10000 {–1 to 100} Overrange limit [MPa] {bar} 1.5 {15} 4.5 {45} 15 {150} Lower range limit (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: Atmospheric pressure – Conversion factors to different units; 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal. Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below Factory Mutual Load resistance Operating area 24V 250 0 10 45V 16.1 10.5V Power voltage 50 [V] Note: For communication with HHC (Model: FXW), min. of 250Ω is required. Hazardous locations: Authorities ATEX Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = -40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = -40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA - TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp.=+120°C IECEx Scheme /SAA Ex d IIC T5 IP66/67 pending Tamb = -40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = -40°C to +65°C (Note) 2 Flameproof (1) HHC: Hand Held Communicator A,B,D Y,G,H,S -40°C to +85°C Y,G,H,S -20°C to +80°C Q,S,4,5 Y,G,H,S -20°C to +60°C E,F,H Y,G,H,S -40°C to +60°C W,A,D -10°C to +60°C Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameter: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH IECEx Scheme /SAA Ex ia IIC T4 IP66/67 Tamb = -40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = -40°C to +50°C Entity Parameter: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH 1500 500 Tamb L,P,1,2 - 1533Ω 600Ω Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 13th digit 9th digit [Ω] 1000 Ex II 1 GD EEx ia IIC T5 Tamb = -40°C to +40°C EEx ia IIC T4 Tamb = -40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH – 2000 Intrinsic safety ATEX “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1) Type n Nonincendive Authorities Ex II 3 GD EEx nL IIC T5 Tamb = -40°C to +40°C EEx nL IIC T4 Tamb = -40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH 3.2 Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 13th digit 9th digit CSA Tamb A,B,D Y,G,H,S -40°C to +85°C L,P,1,2 Y,G,H,S -20°C to +80°C Q,S,4,5 Y,G,H,S -20°C to +60°C E,F,H Y,G,H,S -40°C to +60°C W,A,D -10°C to +60°C - Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS - IECEx Scheme /SAA - 20 20.8 21.6 [mA] Over scale Burnout EEx nAL IIC T5 Tamb = -40°C to +40°C EEx nAL IIC T4 Tamb = -40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual 3.8 4 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (Span adjustment is not available with 9th digit code “L, P, Q, S”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. Normal operating range Under scale Probable under range Burnout Probable over range Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 15 to +65°C (– 15 to +60°C for arrester option) (–10 to +60°C for fluorinated oil fill transmitter) (–10 to +60°C for silicone oil “H”, “S”) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: Fill fluid 13th digit of “Code symbols” Process temperature Fluorinated oil W, A and D –20 to 120°C Silicone oil H 0 to 250°C – 40 to 120°C Y and G S 0 to 250°C Lower limit of static press. Atmospheric pressure 2.7kPa abs {20mmHg abs} Storage: – 40 to +70°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2. Items Display Set Tag No. v v Model No. v v Serial No. v — Engineering unit v v Range limit v — Measuring range v v Damping v v Linear v v Square root v v Burnout direction v v Calibration v v Output adjust — v Data v — Self diagnoses v — Printer — — External switch lock v v Transmitter display v v Linearize v v Rerange v v Output mode EMC Conformity:EN61326 3 FKW...4 Performance specifications Physical specifications Reference conditions, silicone oil fill, SS316 isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ± 0.25% of span For spans below 1/10 of URL: ± 0.17+0.08 0.1 x URL % of span Span (Option) (Code; 21th digit H) For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: ± 0.05+0.05 0.1 x URL % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years. Temperature effect: Effect per 28°C change between the limits of – 15°C and +65°C ( ) ( ) Zero shift: ± 0.5%/28°C (x equal to 1/6.5 URL or more) URL Zero shift; ± (0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Total shift; ± 0.75%/28°C (x less than 1/6.5 URL or more) URL Total shift; ± (0.25 + 0.5 )%/28°C 6.5 x x (x less than 1/6.5 URL) Where, x: Calibrated span URL: Maximum span (Upper Range Limit) Note : Above specifications are based on the conditions that flange and sensor unit are at the same temperature and in the same level. If temperature is different at flange, capillary or sensor unit, output variation may increase. Overrange effect: Zero shift; 0.2% of URL/(1.5 x URL) Supply voltage effect: Less than 0.005% of calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: Time constant: 0.3s *) Dead time: 0.2s *) (without electrical damping) *) Faster response is available as option (maximum update rate: 25 times per second). Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ/500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less 4 Electrical connections: G1 /2, 1 /2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. 1-port (standard) or 2-port with each conduit, as specified. Process connections: JIS; 10K, 20K, 30K, 63K –40, 50A 10K, 20K, 30K, 63K –15, 20A (with Adapter) ANSI/JPI; 150LB, 300LB, 600LB, –1 1/2", 2" 150LB, 300LB, 600LB, – 1 /2", 3 /4" (with Adapter) Screw connection (with Adapter) ; Rc1/2, Rc3/4, 1/2-14NPT, 3/4-14NPT Diaphragm extension: 0, 50, 100, 150, or 200mm as specified. (See model code. Extended diaphragm is available only with 316L stainless steel diaphragm) Process-wetted parts material: Diaphragm: 316L stainless steel, Hastelloy-C Monel or Tantalum Flange face: 316 stainless steel, Hastelloy-C lining, Monel lining or Tantalum lining Extension: 316 stainless steel (Refer to “Code symbols”) Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14 per JIS G5121), as specified. Capillary: In case of 11th code “D. E. L”, PVC armored stainless steel. In case of 11th code “Q. R. S”, stainless steel armored stainless steel. Mounting flange: 304 stainless steel or carbon steel, as specified. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel. Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 10kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm Optional features ACCESSORIES Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 x 50µs). Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum and high temperature service: Special silicone oil and filling procedure are applied. See Fig.1. Optional tag plate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. Filled liquid: Silicone (Code Y,G) [kPa abs] {m bar abs} The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission) 53.3 {533} EN61326 : 1997 Class A (standard for Industrial Location) Frequency range MHz Limits Reference standard 30 to 230 40dB (µV/m) quasi peak, measured at 10m distance CISPR16-1 and CISPR16-2 230 to 1000 47dB (µV/m) quasi peak, measured at 10m distance EMI (Immunity) EN61326: 1997 Annex A (standard for Industrial Location) Phenomenon Electrostatic discharge Test value 4kV (Contact) 8kV (Air) Basic standard Performance criteria EN61000-4-2 B 80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) EN61000-4-3 A Rated power frequency magnetic field 30A/m 50Hz EN61000-4-8 A Burst 2kV 5kHz EN61000-4-4 B Surge 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) EN61000-4-5 B Conducted RF 0.15 to 80MHz 3V 80%AM (1kHz) EN61000-4-6 A Silicone (Code S) 101 {1010} Operating pressure Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 amplifier unit, external adjustment screw will be available for zero and span adjustment. Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering. Operating area 13.3 {133} Non-operating area 2.7 {27} –40 0 60 85 120 Process temperature 200 230 250 [°C ] Fig. 1 Relation between process temperature and operating pressure 5 FKW...4 CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 Description Note <Conduit connection> (×1) G1/2 1/2 - 14NPT (×1) Combination with 12th digit code Pg13.5 (×1) "C, E, P, Q" are not available. M20×1.5 (×1) G1/2 (×2) 1/2 - 14NPT (×2) Pg13.5 (×2) M20 X 1.5 (×2) 5 <Flange> Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A JIS 63K 40A JIS 63K 50A ANSI/JPI 150LB 1 1/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 1 1/2" ANSI/JPI 300LB 2" ANSI/JPI 600LB 1 1/2" ANSI/JPI 600LB 2" None 40A, 1 1/2B (Wafer type) 50A, 2B Note 1 Direct mounting adapter connection (* 1) 6 <Span limit [kPa] {bar} > 50.......500 ( 0.5...5) 300.....3000 ( 3...30) 1000...10000 (10...100) 7 <Material/diapharagm extension> Diaphragm extension (mm) Flange face Diaphragm 0 316L stainless steel 316 stainless steel 50 Note 2 100 (* 2) 150 200 0 316L stainless steel +Au coating 0 Hastelloy-C Hastelloy-C 0 Monel Monel 0 Tantalum Tantalum Note1: (*1) Direct mounting adapter type is specified at 16th to 20th digit. Direct mounting adapter is available only for 7th digit code "V". Note2: (*2) Diaphragm extension is available only for 2" (50A) flanges. 6 F KW 4 A B C D S T V W 0 1 2 3 4 5 6 7 A B C D E F G H J K L M N P Q R S T U V W X Y 2 3 4 V A B C D J H M T 9 10 11 12 13 14 15 16 17 18 19 20 0 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 9 10 11 12 13 14 15 F KW Description <Indicator and arrester> Indicator Arrester None None Z/S board Analog, 0 to 100% linear scale None attached. Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% None Digital, custom scale None Digital, 0 to 100% Yes Digital, custom scale Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Conduit seal)(Available for 4th digit code "A", "S") TIIS, Flameproof (Cable gland seal)(Available for 4th digit code "A", "S") FM, Flameproof (or explosionproof)(Available for 4th digit code "B", "T") ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and Nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety <Capillary and mounting bracket> Mounting bracket Capillary Armor of Capillary Stainless steel 1.5m PVC (*5) 3m 5m 1.5m Stainless steel 3m 5m <Options> Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None (*3) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V", "A", "B", "C" and "D") Chlorine service Fluorinated oil (7th digit code "H" and "T") High temp. 250°C Silicone oil (7th digit code "V", "A", "B", "C", "D" and "H") High temp. and vacuum (250°C) Silicone oil (7th digit code "V", "A", "B", "C" and "D") <Teflon membrane> None Yes (Available for 7th digit code "V", "H", "M" and "T". Not available for 5th digit code "Y" and 13th digit code "H", "S".) <Bolt/nut> (*4) None 6th digit code "3" Cr-Mo alloy hexagon socket head cap bolt/ carbon steel nut 6th digit code "4" Cr-Mo alloy hexagon bolt/carbon steel nut 304 stainless steel bolt/304 stainless steel nut Note3: (*3) Note4: (*4) Note5: (*5) Note 9 10 11 12 13 14 15 16 17 18 19 20 4 21 Digit No. of code A B D E F H L P Q S 1 2 4 5 A B C D X R G H K P T V Note5 Note3 D E L Q R S Y B C E M N P Q Y W G A D H S Y C Note4 Y A B E Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". In case of tropical use, select stainless bolts and nuts. Available for 13th digit code "Y, W, G, A, D". 7 FKW...4 Specifications of Direct Mounting Adapter {for 15, 20A (1/2, 3/4") connection} and others Note 1. When odering the instrument with direct mounting adapter, specify “Y” in the 5th digit of Code Symbol, and specify 16th digit to 20th digit. When odering the instrument without direct mounting adapter, nothing should be filled in the 16th to 20th digit. 2. Unless otherwise described in the specifications, leave the 21st digit blank. 1 2 3 4 5 6 7 8 Digit Description Note 16, 17 <Process connection (direct mounting adapter)> JIS 10K 15A JIS 10K 20A JIS 20K 15A JIS 20K 20A JIS 30K 15A JIS 30K 20A JIS 63K 15A JIS 63K 20A ANSI/JPI 150LB 1/2" ANSI/JPI 150LB 3/4" ANSI/JPI 300LB 1/2" ANSI/JPI 300LB 3/4" ANSI/JPI 600LB 1/2" ANSI/JPI 600LB 3/4" Screw connection Rc1/2 Screw connection Rc3/4 Screw connection Rc1/2 - 14NPT Screw connection Rc3/4 - 14NPT 18 <Material (direct mounting adapter)> Note 1 Adapter Bolts/nuts (* 1) 316 Stainless Steel Cr-Mo steel/carbon steel 19 <Vent/drain (for direct mounting adapter)> Standard Long type 20 <Gasket (for direct mounting adapter)> Standard (Teflon)(Only Y, W, G, A and D can be specified on 13th digit). For high temperature (spiral gasket) (Only H and S can be specified on 13th digit). 21 Note 2 <Other options> (* 2) High accuracy type Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached F KW 9 10 11 12 13 14 15 16 17 18 19 20 1 1 1 2 2 1 2 2 3 1 3 2 6 1 6 2 1H 1T 2H 2T 4H 4T SR S2 SN ST Note1: (* 1) For connection of transmitter receiving pressure unit and direct mounting adapter Note2: (* 2) In other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. ORDERING INFOMATION When ordering this instrument, specify. 1. CODE SYMBOLS 2. Measuring range. 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA) Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 5. Tag No. (up to 26 alphanumerical characters), if required. 8 21 4 W A N 1 2 H L T Digit No. of code OUTLINE DIAGRAM (Unit:mm) Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. In case of 4th digit code “S.V.W.X” MTG. Pipe JIS 50A (2B) In case of 4th digit code “A.B.C.D.E” Fastener (Flameproof only) In case of 4th digit code “T” 10 8 94.5 U - bolt M8 38 4 holes 9 dia. ø80 104 Down 88 70 ø80 52.5 105 105 Up 37 Cable gland (option) Note) 210 58 “B” Conduit conn. Zero ADJ. screw (27) “A” Conduit conn. With field ind. N holes h dia. Detail “B” ø13 17 71 M K ø84 ø49 ø48 øD ø15 J G1/2 191 See table 1 V, H, M, T A B C D t L Mass approx. [kg] 0 50 100 150 200 9.5 10.5 11.5 12 12.5 No flange is attached in case of 5th digit code “W,X”. Earth terminal 11th digit of Capillary Code symbols length [mm] D, Q E, R L, S 5th digit of code symbols øD øE øt N-øh Flange 0,G 1,H 2,J 3,K 4,L 5,M 6,N 7,P A,Q B,R C,S D,T E,U F,V 140 155 140 155 160 165 175 185 127 152 156 165 156 165 105 120 105 120 120 130 130 145 98.4 120.6 114.3 127 114.3 127 36 36 38 38 42 42 52 54 37.5 39.5 41 42.5 42.5 45.5 4-19 4-19 4-19 8-19 4-23 8-19 4-25 8-23 4-16 4-20 4-23 8-20 4-23 8-20 JIS-10K-40A JIS-10K-50A JIS-20K-40A JIS-20K-50A JIS-30K-40A JIS-30K-50A JIS-63K-40A JIS-63K-50A ANSI/JPI-150LB-1 1/2B ANSI/JPI-150LB-2B ANSI/JPI-300LB-1 1/2B ANSI/JPI-300LB-2B ANSI/JPI-600LB-1 1/2B ANSI/JPI-600LB-2B 2-M6 screw depth 9 Inner of gasket Electronics unit 1500 3000 5000 231 7th digit of Code symbols L 43 60 20 Inner of gasket øE Detail “A” S 2-M8×12 70 120 4th digit of the code symbols 50 Conduit conn. K M A, S G1/2 J 17 8 B, T 1/2-14NPT 16 5 C, V Pg13.5 8 4.5 D, W M20×1.5 16 5 CONNECTION DIAGRAM 71 ø84 ø49 + 20 <Wafer type> Sensor unit Table 1 – CK+ + CK– – + – Note) In case of wafer type, flange is excluded from the scope of supply. Mount flange, referring to the view. 9 FKW...4 OUTLINE DIAGRAM (Unit:mm) <With direct mount adaptor> Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. Long vent/drain plug (added specification) (102) 25 Vent/drain plug (t) In case of ANSI/JPI-600LB flange (6.4) ø84 øF øE øD In case of 4th digit code “A.B.C.D.E” N holes h dia. S t 20 80 In case of 4th digit code “T” Fastener (Flameproof only) U - bolt M8 10 8 Zero ADJ. screw 94.5 MTG. pipe JIS 50A (2B) In case of 4th digit code “S.V.W.X” 37 38 4 holes 9 dia. 88 58 ø80 104 105 70 ø80 52.5 105 Up Down Cable gland (option) Note) (27) “A” Conduit conn. 210 “B” Conduit conn. With field ind. Detail “A” Detail “B” ø13 M ø15 191 43 60 K 17 Earth terminal J Electronics unit G1/2 D, W M20×1.5 øD 16th of 17th of code symbols code symbols 1 1 2 2 3 3 6 6 1 1 2 2 4 4 10 1 2 1 2 1 2 1 2 H T H T H T 95 100 95 100 115 120 120 135 89 98 95 117 95 117 16 11th digit of Code symbols Capillary length [mm] D, Q E, R L, S 1500 3000 5000 5 øE øF t N-øh 70 75 70 75 80 85 85 95 60.3 69.9 66.7 82.5 66.7 82.5 51 56 51 56 55 60 55 60 34.9 42.9 34.9 42.9 34.9 42.9 12 14 14 16 18 18 23 25 11.5 13 14.5 16 14.5 16 4-15 4-15 4-15 4-15 4-19 4-19 4-19 4-23 4-16 4-16 4-16 4-20 4-16 4-20 231 Table 1 Conduit conn. 4th digit of the code symbols J K M A, S G1/2 17 8 B, T 1/2-14NPT 16 5 C, V Pg13.5 8 4.5 2-M8×12 Flange JIS-10K-15A JIS-10K-20A JIS-20K-15A JIS-20K-20A JIS-30K-15A JIS-30K-20A JIS-63K-15A JIS-63K-20A ANSI/JPI-150LB 1/2B ANSI/JPI-150LB 3/4B ANSI/JPI-300LB 1/2B ANSI/JPI-300LB 3/4B ANSI/JPI-600LB 1/2B ANSI/JPI-600LB 3/4B 70 120 CONNECTION DIAGRAM + – CK+ + CK–– + – 50 Sensor unit OUTLINE DIAGRAM (Unit:mm) <With direct mount adaptor (screw connection type)> Note) Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. Vent/drain plug (102) 25 Long vent/drain plug (added specification) Press. conn. “D” ø84 In case of 4th digit code “A.B.C.D.E” S 20 23 In case of 4th digit code “S.V.W.X” MTG. pipe JIS 50A (2B) Fastener (Flameproof only) In case of 4th digit code “T” 10 94.5 8 U - bolt M8 ø80 104 105 ø80 4 holes 9 dia. DOWN 88 70 38 52.5 105 UP 37 58 Cable gland (option) Note) Zero ADJ. screw (27) 210 “B” Conduit conn. “A” Conduit conn. With field ind. 191 Detail “A” 60 Detail “B” ø13 CONNECTION DIAGRAM Earth terminal M ø15 43 + – CK+ + CK– – K 17 Electronics unit + – J 231 G1/2 Sensor unit Table 1 Conduit conn. 4th digit of the code symbols J K M A, S G1/2 17 8 B, T 1/2-14NPT 16 5 C, V Pg13.5 8 4.5 D, W M20×1.5 16 5 2-M8×12 11th digit of Capillary Code symbols length [mm] D, Q E, R L, S 1500 3000 5000 70 120 16th digit of Code symbols 17th digit of Code symbols 50 Press. conn. “D” S R Rc 1/2 S N 1/2-14NPT S 2 Rc 3/4 S T 3/4-14NPT 11 FKW...4 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan