SYSTEMSENSOR EM-1SRI

I56-2016-004
INSTALLATION AND MAINTENANCE INSTRUCTIONS
EM-1SRI Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Standby Current:
Alarm Current:
Maximum NAC Circuit Line Loss:
Power Supply Monitor
Maximum (Speakers):
Maximum (NAC):
Trouble Range:
Max NAC Current Rating:
Temperature Range:
Humidity:
Dimensions:
Accessories:
15 to 30 VDC
630 µA max. average (continuous broadcasts)
2 mA (red LED on)
4 VDC
70.7 V RMS. 50 W
Regulated 24VDC
0 to 2 VDC
For Class B wiring system, 3A
For Class A wiring system, 2A
32°F to 120°F (0°C to 49°C)
10 to 93% RH Noncondensing
4.17˝ H x 4.26˝ W x 1.22˝ D; (106 mm H x 108 mm W x 31 mm D)
39 kΩ End of Line Resistor Part # A2263-00 (included)
Wall cover plate (included)
SMB500 Surface Mount Electrical Box
A2143-60 Bypass capacitor
EA-CB Control Module Barrier
BEFORE INSTALLING
no short exists, the device will reapply the external power.
This algorithm can be enabled when using a DC external
supply that is guaranteed to be above 9 volts.
This information is included as a quick reference installation guide. Refer to the appropriate control panel installation manual for detailed system information. If the modules
will be installed in an existing operational system, inform
the operator and local authority that the system will be
temporarily out of service.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected
to a listed compatible control panel.
MOUNTING
NOTICE: This manual should be left with the owner/user
of this equipment.
The module mounts directly to 4˝ square electrical boxes.
The box must have a minimum depth of 21/8˝. Modules
must be mounted with the arrow facing upward for proper
operation of the IR configuration tool (model no. EA-CT).
Surface mounted electrical boxes (SMB500) are available
from System Sensor.
GENERAL DESCRIPTION
Control Module, Model EM-1SRI, is used to switch an external power supply or audio amplifier to notification appliances. In addition to switching the external power, the
device will monitor the wiring (while external power is
not switched to the auxiliary devices) to the auxiliary device for open and short circuits via an end of line resistor.
This module is capable of Class A or Class B operation.
The module also has on-board short circuit isolators to prevent shorts on the signaling line circuit from disabling more
than one device on the intelligent loop.
WIRING
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. Optional EA-CB
may be required to separate power limited and non
power limited wiring in the electrical box (see Figure
1B). 2.
For new installations use the enclosed 39
kΩ EOL resistor. For retrofit applications where the existing 47 kΩ cannot be easily replaced, it may be left in
place without loss of performance.
3. Set the address on the module per job drawings using
the IR configuration tool (model no. EA-CT).
4. Secure module to electrical box (supplied by installer).
The control module will also have the capability to monitor the external power input for loss of power (DC voltage supplies only). This feature can be disabled through
device configuration programming. If the external power
is switched to the auxiliary devices and there is a loss of
the DC supply, the control module has the capability of
running an algorithm in which the device will switch back
to monitor mode and check the line for short circuits. If
D500-54-00
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
1
I56-2016-004
Auto Addressing
TESTING
Eclipse Series devices are capable of supporting auto addressing, if the fire alarm control panel is designed to do
so. In auto addressing, the control panel, through the use
of each device’s on-board isolators, can automatically assign device addresses. In order to control which devices
are addressed first in wiring configurations with branches,
a branch marker can be set at a particular device. A branch
marker is an electronic value from 0 to 255 stored in the
device memory. The branch markers are set with the IR
configuration tool, EA-CT.
The following resistance values can be used to test the
module after installation:
Short Circuit: <50Ω
Open Circuit: >1MΩ
Ground Fault: <50Ω
WARNING
All relay switch contacts are shipped in the standby state
(open) state, but may have transferred to the activated
(closed) state during shipping. To ensure that the switch
contacts are in their correct state, modules must be made
to communicate with the panel before connecting circuits
controlled by the module.
Terminal Definitions
T1
T2
T3
T4
T7
T8
(+) SLC in/out
(–) SLC in/out
(+) SLC in/out
(–) SLC in/out
(–) external power line in/out
(+) external power line in/out
T9
T10
T11
T12
T13
T14
(–) external power line in/out
(+) external power line in/out
NAC (+) A/B
NAC (–) A/B
NAC (–) Class A
NAC (+) Class A
Figure 1A: Supervised Control Module
LED
INDICATOR
IR
RECEIVER
Figure 1B: Module mounting with barrier (model no. EA-CB)
C0164-00
C0183-00
D500-54-00
2
I56-2016-004
Figure 2: Typical Class B, Style Y NAC configuration.
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
(–)
(–)
(+)
EOL
RESISTOR
(+)
UL LISTED
EOL RELAY
SHOWN
ENERGIZED
24 VDC COIL
A77-716B
OR EQUIVALENT
1
13
2
12
3
(–)
(+)
11
4
(–)
TO NEXT
DEVICE
8
(–)
7
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70
LISTED FOR FIRE PROTECTION
WITH BATTERY BACK-UP
TO NEXT CONTROL MODULE
TERMINALS 10 (+) AND 9 (–)
OR END OF LINE RELAY
(IF REQUIRED)
FROM TERMINALS
7 AND 8 OF LAST
REQUIRED FOR PANELS CONTROL MODULE
ON BRANCH
WITHOUT POWER SUPPLY
MONITORING
+
–
+
–
9
(+)
(+)
14
10
(–)
24 VDC
POWER
SUPPLY
FROM PANEL OR
PREVIOUS DEVICE
(+)
C0106-04
Figure 3: Typical Class A, Style Z NAC configuration.
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
EOL RESISTOR
IS INTERNAL AT
TERMINALS 13 & 14
(–)
(–)
(+)
24 VDC
POWER
SUPPLY
(+)
(+)
UL LISTED
EOL RELAY
SHOWN
ENERGIZED
24 VDC COIL
A77-716B
OR EQUIVALENT
FROM TERMINALS
7 AND 8 OF LAST
REQUIRED FOR PANELS CONTROL MODULE
ON BRANCH
WITHOUT POWER SUPPLY
MONITORING
+
–
+
–
(+)
14
1
13
2
12
3
(–)
(+)
11
4
(–)
TO NEXT
DEVICE
10
(–)
9
(+)
8
(–)
7
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70
LISTED FOR FIRE PROTECTION
WITH BATTERY BACK-UP
TO NEXT CONTROL MODULE
TERMINALS 10 (+) AND 9 (–)
OR END OF LINE RELAY
(IF REQUIRED)
C0107-04
Figure 4: Typical Class B, Style Y Audio NAC configuration.
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
ALL WIRING SHOWN IS SUPERVISED
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
EOL
RESISTOR
(+)
(–)
AUDIO
AMPLIFIER
70.7 Vrms Max.
(+)
(–)
(+)
14
1
13
2
12
3
(–)
(+)
11
4
(–)
10
9
+
–
+
–
TO NEXT
DEVICE
8
7
AUDIO CIRCUIT MUST BE
TWISTED PAIR AS A MINIMUM
WHEN A 70.7 V AUDIO AMPLIFIER IS USED,
TERMINALS 1-4 ARE POWER LIMITED,
WHILE TERMINALS 7-14 ARE
NON-POWER LIMITED
D500-54-00
3
TO NEXT CONTROL MODULE
LAST MODULE MUST
RETURN WIRES
AUDIO AMP.
C0108-01
I56-2016-004
Figure 5: Typical Class A, Style Z Audio NAC configuration.
SIGNAL LINE CIRCUIT (SLC)
ALL WIRING SHOWN IS SUPERVISED
30 VDC MAX.
TWISTED PAIR RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
(+)
(–)
AUDIO
AMPLIFIER
70.7 Vrms Max.
EOL RESISTOR
IS INTERNAL
AT TERMINALS
13 AND 14
REQUIRED
BYPASS CAPACITORS:
100µF 16V NONPOLARIZED
<10µA LEAKAGE
A2143-60
(+)
(–)
AUDIO CIRCUIT MUST BE
TWISTED PAIR AS A MINIMUM
WHEN A 70.7 V AUDIO AMPLIFIER
IS USED, TERMINALS 1-4 ARE
POWER LIMITED, WHILE TERMINALS
7-14 ARE NON-POWER LIMITED
(+)
14
1
13
2
12
3
(–)
(+)
11
4
(–)
10
9
+
–
+
–
TO NEXT
DEVICE
8
7
TO NEXT CONTROL MODULE
LAST MODULE MUST
RETURN WIRES
C0109-01
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years
from date of manufacture. System Sensor makes no other express warranty for
this air duct smoke detector. No agent, representative, dealer, or employee of
the Company has the authority to increase or alter the obligations or limitations
of this Warranty. The Company’s obligation of this Warranty shall be limited
to the replacement of any part of the product which is found to be defective
in materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to replace units which are found to be
defective because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the Company be
liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage
is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
D500-54-00
4
I56-2016-004
©2006 System Sensor