OMRON H3YN-41

Solid-state Timer
Timers
H3YN
Miniature Timer with Multiple Time Ranges
and Multiple Operating Modes
• Minimizes stock.
• Pin configuration compatible with MY Power Relay.
• Standard multiple operating modes and multiple time ranges.
• Conforms to EN61812-1 and IEC60664-1 for Low Voltage, and
EMC Directives.
Model Number Structure
■ Model Number Legend
H3YN-@@-@
1 2
3
3. Contact Type
None: Single contact
Z:
Twin contacts
1. Output
2:
DPDT
4:
4PDT
2. Time Range
None: Short-time range (0.1 s to 10 min)
1:
Long-time range (0.1 min to 10 hrs)
Ordering Information
■ List of Models
Supply voltage
Time-limit contact
Short-time range model
(0.1 s to 10 min)
Long-time range model
(0.1 min to 10 h)
24, 100 to 120, 200 to 230 VAC;
12, 24, 48, 100 to 110, 125 VDC
DPDT
H3YN-2
4PDT
H3YN-4
H3YN-21
H3YN-41
24 VDC
4PDT (Twin contacts)
H3YN-4-Z
H3YN-41-Z
Note: Specify both the model number and supply voltage when ordering.
Example: H3YN-2 24 VAC
Supply voltage
■ Accessories (Order Separately)
Connecting Socket
Timer
Track mounting/Front
Connecting Socket
Back Connecting Socket
Solder terminal
Wire-wrap terminal
PC terminal
H3YN-2/-21
PYF08A, PYF08A-N,
PYF08A-E
PY08
PY08QN(2)
PY08-02
H3YN-4/-41
H3YN-4-Z/-41-Z
PYF14A, PYF14A-N,
PYF14A-E
PY14
PY14QN(2)
PY14-02
Solid-state Timer
H3YN
B-87
Hold-down Clips
Model
Applicable Socket
Y92H-3
PYF08A, PYF08A-N, PYF08A-E
PYF14A, PYF14A-N, PYF14A-E
Y92H-4
PY08, PY08QN(2), PY08-02
PY14, PY14QN(2), PY14-02
Specifications
■ Ratings
Item
H3YN-2/-4/-4-Z
H3YN-21/-41/-41-Z
Time ranges
0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max.
selectable)
Rated supply voltage
24, 100 to 120, 200 to 230 VAC (50/60 Hz)
12, 24, 48, 100 to 110, 125 VDC (see note 1)
Pin type
Plug-in
Operating mode
ON-delay, interval, flicker OFF start, or flicker ON start (selectable with DIP switch)
Operating voltage range
85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(see note 2)
Reset voltage
10% min. of rated supply voltage (see note 3)
Power consumption
100 to 120 VAC: Relay ON: approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
Relay OFF: approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
200 to 230 VAC: Relay ON: approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
Relay OFF: approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
24 VAC:
Relay ON: approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
12 VDC:
Relay ON: approx. 1.1 W at 12 VDC
Relay OFF: approx. 0.1 W at 12 VDC
24 VDC:
Relay ON: approx. 1.1 W at 24 VDC
Relay OFF: approx. 0.1 W at 24 VDC
48 VDC:
Relay ON: approx. 1.2 W at 48 VDC
Relay OFF: approx. 0.3 W at 48 VDC
100 to 110 VDC: Relay ON: approx. 1.6 W at 110 VDC
Relay OFF: approx. 0.4 W at 110 VDC
125 VDC:
Relay ON: approx. 1.6 W at 125 VDC
Relay OFF: approx. 0.4 W at 125 VDC
Control outputs
DPDT: 5 A at 250 VAC, resistive load (cosφ = 1)
4PDT: 3 A at 250 VAC, resistive load (cosφ = 1)
Note: 1. Single-phase, full-wave-rectified power supplies can be used.
2. When using the H3YN continuously in any place where the ambient temperature is in a range of 45°C to 50°C, supply 90% to 110% of
the rated supply voltages (supply 95% to 110% with 12 VDC type).
3. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
B-88
Solid-state Timer H3YN
■ Characteristics
Item
H3YN-2/-21/-4/-41
±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error
±10%±50 ms FS max.
Reset time
Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage
±2% FS max.
Influence of temperature
±2% FS max.
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts) (see note 1)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Shock resistance
Destruction: 1,000 m/s2
Malfunction: 100 m/s2
Ambient temperature
Operating:
Storage:
−10°C to 50°C (with no icing)
−25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Life expectancy
Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
DPDT:
500,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
4PDT:
200,000 operations min. (H3YN-4-Z/-41-Z: 100,000 operations min.)
(3 A at 250 VAC, resistive load at 1,800 operations/h) (see note 2)
Impulse withstand voltage
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Noise immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity
Destruction: 8 kV
Malfunction: 4 kV
Degree of protection
IP40
Weight
Approx. 50 g
EMC
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN61812-1
Immunity ESD:
EN61000-4-2: 8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst:
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
EN61000-4-5: 2 kV line to ground (level 3)
1 kV line to line (level 3)
Approved standards
UL508, CSA C22.2 No. 14, Lloyds
Conforms to EN61812-1 and IEC60664-1. (2.5 kV/2 for H3YN-2/-21, 2.5 kV/1 for H3YN-4/-41, H3YN4-Z/-41-Z)
Output category according to EN60947-5-1.
Timers
Accuracy of operating time
Note: 1. Terminal screw sections are excluded.
2. Refer to the Life-test Curve.
Solid-state Timer
H3YN
B-89
■ Life-test Curve (Reference Value)
250 VAC, cosφ = 1
24 VDC, cosφ = 1
5,000
1,000
500
200
Switching operations (x 103)
Switching operations (x 103)
H3YN-2/-21
5,000
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
1,000
500
200
Load current (A)
Load current (A)
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 5 VDC (P reference value).
250 VAC, cosφ = 1
24 VDC, cosφ = 1
5,000
1,000
500
200
Load current (A)
Switching operations (x 103)
Switching operations (x 103)
H3YN-4/-41
5,000
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
1,000
500
200
Load current (A)
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Switching operations (x 103)
H3YN-4-Z/-41-Z
5,000
1,000
500
100
60
250 VAC, resistive load
24 VDC, resistive load
Load current (A)
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 0.1 mA at 1 VDC (P reference value).
B-90
Solid-state Timer H3YN
Connections
H3YN-2/-21
H3YN-4/-41
H3YN-4-Z/-41-Z
DIN Indication
Timer
circuit
Timer
circuit
UP
UP
PW
Timers
■ Connection
DIN Indication
PW
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal.
Use the H3YN in interval mode as shown in the following timing charts.
H3YN-2/-21
Power (9-14)
External short circuit
(5-13)
External input
(9-13)
50 ms
min.
Time limit contact
NO (12-8)
Time limit contact
NC (12-4)
Timer
circuit
Run/Power indicator
(PW)
Output indicator (UP)
External input
Note: t: Set time
Rt: Reset time
H3YN-4/-41
H3YN-4-Z/-41-Z
Power (9-14)
External short circuit
(5-13)
External input
(9-13)
50 ms
min.
Time limit contact NO
(10-6, 11-7, 12-8)
Time limit contact NC
(10-2, 11-3, 12-4)
Run/Power indicator
(PW)
Output indicator (UP)
Timer
circuit
External input
Note: t: Set time
Rt: Reset time
!Caution
Be careful when connecting wires.
Mode
Terminals
Pulse operation
Power supply between 9 and 14
Short-circuit between 5 and 13
Input signal between 9 and 13
Operating mode; interval and all other modes
Power supply between 13 and 14
Solid-state Timer
H3YN
B-91
Operation
■ Timing Chart
Operating mode
Timing chart
H3YN-2/-21
H3YN-4/-41
ON-delay
Power (13-14)
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Power
Output
Time limit contact
NO (9-5, 12-8)
Run/Power indicator
(PW)
Output indicator
(UP)
Run/Power indicator
(PW)
Output indicator
(UP)
Power (13-14)
Power (13-14)
Interval
Power
Run/Power indicator (PW)
Output indicator
(UP)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power indicator (PW)
Output indicator
(UP)
Power (13-14)
Power (13-14)
Time limit contact
NC (9-1, 12-4)
Output indicator
(UP)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power indicator
(PW)
Output indicator
(UP)
Power (13-14)
Power (13-14)
Power
Time limit contact
NC (9-1, 12-4)
Output
Time limit contact
NO (9-5, 12-8)
Time limit contact
NC (9-1, 10-2, 11-3,
12-4)
Time limit contact
NO (9-5, 10-6, 11-7,
12-8)
Run/Power indicator (PW)
Output indicator
(UP)
Time limit contact
NC (9-1, 12-4)
Output
Time limit contact
NO (9-5, 12-8)
Flicker OFF-start
Power
Output
Time limit contact
NO (9-5, 12-8)
Run/Power indicator
(PW)
Flicker ON-start
Run/Power indicator (PW)
Output indicator
(UP)
Note: t: Set time
Rt: Reset time
B-92
Solid-state Timer H3YN
■ DIP Switch Settings
The 1-s range and ON-delay mode for H3YN-2/-4/-4-Z, the 1-min range and ON-delay mode for H3YN-21/-41/-41-Z are factory-set before shipping.
Model
H3YN-2,
H3YN-4
H3YN-4-Z
H3YN-21,
H3YN-41
H3YN-41-Z
Time range
Time setting
range
Setting
Timers
Time Ranges
Factory-set
1s
0.1 to 1 s
Yes
10 s
1 to 10 s
No
1 min
0.1 to 1 min
No
10 min
1 to 10 min
No
1 min
0.1 to 1 min
Yes
10 min
1 to 10 min
No
1h
0.1 to 1 h
No
10 h
1 to 10 h
No
1s
10 s 1 min 10 min
Note: The top two DIP switch pins are used to select the time ranges.
Operating Modes
Operating mode
Setting
Factory-set
ON-delay
Yes
Interval
No
Flicker OFF-start
No
Flicker ON-start
No
Note: The bottom two DIP switch pins are used to select the operating mode.
Nomenclature
Output Indicator (Orange)
(Lit: Output ON)
Run/Power Indicator (Green)
(Lit: Power ON)
Main Dial
Set the desired time according
to time range selectable by
DIP switch.
Solid-state Timer
H3YN
B-93
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Timers
H3YN-2/-21 Front Mounting
Eight, 3 × 1.2 elliptic holes
28 max.
6.4
(63.0)
21.5 max.
H3YN-4/-41 Front Mounting
H3YN-4-Z/-41-Z
Fourteen, 3 × 1.2 elliptic holes
28 max.
21.5 max.
Mounting Height
PYF08A/PYF08A-N/PYF08A-E
(PYF14A/PYF14A-N/PYF14A-E
(see note))
PY08 (PY14 (see note))
H3YN
Series
H3YN
Series
PY08 (PY14)
PY08QN (PY14QN (see note))
H3YN
Series
PY08QN
(PY14QN)
PYF08A (PYF14A)
Note: Models in parentheses are Connecting Sockets to the H3YN-4/-41 or H3YN-4-Z/-41-Z.
B-94
Solid-state Timer H3YN
■ Accessories (Order Separately)
Use the PYF@A, PY@, PY@-02, or PY@QN(2) to mount the H3YN. When ordering any one of these Sockets, replace “@” with “08” or “14.”
Track Mounting/Front Connecting Sockets
PYF08A
Two, 4.2 × 5
mounting holes
Terminal Arrangement
(Top View)
3.4
6
Eight, M3 ×
8 sems
Mounting Holes
Two, 4.5 dia.
M4 or M3
H3YN
Series
35.4
72 max.
90.5
86.6
59±0.3
4
PYF@A
6
23 max.
15±0.2
16.5
30 max.
PYF-14A
Two, 4.2 × 5
mounting holes
Terminal Arrangement
(Top View)
3.4
6
Fourteen, M3 ×
8 sems
Mounting Holes
Two, 4.5 dia.
M4 or M3
35.4
72 max.
59±0.3
4
6
29.5 max.
22±0.2
16.5
30 max.
PYF-08A-N
Terminal Arrangement
4
1
42
12
8
5
44
14
42
4
44
8
Mounting Holes
(for Surface Mounting)
12
1
14
5
3.2 dia.
66.5 max.
3.6 dia.
19.8
PYF-08A-N
41
11
12
41
9
12
A2
A2
A1
14
14
13
9
11
14 14 13
A2 A2 A1
30 max.
22 max.
PYF-14A-N
Terminal Arrangement
4
3
2
42 32 22 12
4 3 2 1
44 34 24 14
8 7 6 5
1
42
32
22
12
8
7
6
5
44
34
24
14
Mounting Holes
(for Surface Mounting)
Two, 3.5 dia.
66.5 max.
PYF-14A-N
41
31
21
12
11
10
11
A2
A2
A1
14
14
13
9
12 11 10 9
41 31 21 11
30 max.
29.5 max.
14 14
A2 A2
20.8
13
A1
Solid-state Timer
H3YN
B-95
Timers
Connecting Sockets
PYF08A-E
(Top View)
Two, 4.2 × 5
mounting holes
Eight, M3 ×
8 sems
Two, 4.5 dia.
M4 or M3
72 max.
23 max.
31 max.
PYF14A-E
(Top View)
Two, 4.2 × 5
mounting holes
Two, 4.5 dia.
M4 or M3
Fourteen,
M3 × 8
sems
72 max.
29.5 max.
31 max.
Back Connecting Sockets
PY08, PY14
Eight, 3 × 1.2 dia. holes
only for PY08 (Fourteen, 3
× 1.2 dia. holes)
24 max.
0.3
2.7
Terminal Arrangement
(Bottom View)
21.4+0.2
0
59.3
25.5 29.5
max. max.
20 max.
PY08
PY14
PY@, PY@-02,
PY@QN(2)
PY08QN, PY14QN
PY08QN(2), PY14QN(2)
Terminal Arrangement
(Bottom View)
24 max.
22 max.
25 max. *
(See
note)
29.5 max.
1x1
**
41.5 max.
(see note)
Note: With PY@QN(2)(-3), dimension * should
read 20 max. and dimension ** 36.5 max.
PY08-02, PY14-02
0.3
4.3
PY08QN
PY08QN(2)
PY14QN
PY14QN(2)
Terminal Arrangement
(Bottom View)
22 max.
2.7
25.5 29.5
max. max.
2
16.5 max.
PY08@-02
B-96
H3YN
Series
25.8+0.2
0
2.6
7.7
2.7
Panel Cutout
Solid-state Timer H3YN
PY14@-02
Flush Mounting Adapter
Timers
Y92F-78
Panel Cutout
R0.5 max.
25.2+0.2
−0
5
31.6+0.2
−0
27.1
3
48.5
25.1
3
31.5
33.5
Panel thickness
1 to 3 mm
Note: 1. Push the H3Y in until the Adaptor (Y92F78) hooks engage with its rear panel.
2. Do not round the corners of the cutout on
the rear panel surface, otherwise the
Adaptor (Y92F-78) tabs may not engage
properly.
Socket Mounting Plates
The PYP-1 is a Socket Mounting Plate for a single Socket and the PYP-18 is a Socket Mounting Plate for 18 Sockets. The PYP-18 can be cut
appropriately according to the number of Sockets to be used.
PYP-1
PYP-18
Two, 3.4-dia. holes
21.6
49
28
492
17 x 27.4 = 465.8±0.6
27.4±0.15
4.5
3.4
13.1
42±0.1 49
t = 1.6
Square hole
72, elliptic holes
t = 1.6
Hold-down Clips
The Hold-down Clip makes it possible to mount the H3YN securely and prevent the H3YN from falling out due to vibration or shock.
Y92H-3
Y92H-4
Y92H-3 for
PYF@A Socket
(Set of Two Clips)
Y92H-4 for
PY@ Socket
5 max.
9R
30.5
24.5
2.5
53
20
4.5
1.2
(84°)
4.5
33.7
Solid-state Timer
H3YN
B-97
Precautions
■ Correct Use
The operating voltage will increase when using the H3YN continuously in any place where the ambient temperature is in a range of
45°C to 50°C. Supply 90% to 110% of the rated voltages (at 12 VDC:
95% to 110%).
Do not leave the H3YN in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts (aluminum electrolytic capacitor) may become damaged. Therefore, the use of the
H3YN with a relay as shown in the following circuit diagram is recommended to extend the service life of the H3YN.
Be careful not to apply any voltage to the terminal screws on the
back of the Timer. Mount the product so that the screws will not come
in contact with the panel or metal parts.
Do not use the H3YN in places where there is excessive dust, corrosive gas, or direct sunlight.
Do not mount more than one H3YN closely together, otherwise the
internal parts may become damaged. Make sure that there is a
space of 5 mm or more between any H3YN models next to each
other to allow heat radiation.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3YN.
In order to conform to UL and CSA requirements when using the
H3YN-4/-41 or H3YN-4-Z/-41-Z, connect the Unit so that output contacts (contacts of different poles) have the same electric potential.
X2/b
T/a
T
X1/a
X1
X1/a
X2
X
: Auxiliary relay such as MY Relay
The H3YN must be disconnected from the Socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.
Do not connect the H3YN as shown in the following circuit diagram
on the right hand side, otherwise the H3YN’s internal contacts different from each other in polarity may become short-circuited.
Correct
Incorrect
In cases such as PLC input where the load is extremely small for the
control output of a timer containing a power relay (using other than
gold-plated contacts), reliability can be increased by using contacts
of the same poles (e.g., the H3Y-2) in parallel.
■ Precautions for EN61812-1
Conformance
The H3YN as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied.
Handling
Do not touch the DIP switch while power is supplied to the H3YN.
Before dismounting the H3YN from the Socket, make sure that no
voltage is imposed on any terminal of the H3YN.
The applicable Socket is the PYF@A.
Use the following safety circuit when building a self-holding or selfresetting circuit with the H3YN and an auxiliary relay, such as an MY
Relay, in combination.
Only basic insulation is ensured between the Y92H-3 Hold-down
Clips and H3YN internal circuits.
Do not allow the Y92H-3 Hold-down Clips to contact other parts.
The insulation test voltage between different pole contacts for the 4pole model is the impulse voltage of 2.95 kV.
Wiring
The power supply for the H3YN must be protected with equipment
such as a breaker approved by VDE.
: Auxiliary relay such as MY Relay
In the case of the above circuit, the H3YN will be in pulse operation.
Therefore, if the circuit shown on page 91 is used, no auxiliary relay
will be required.
Do not set to the minimum setting in the flicker modes, otherwise the
contact may become damaged.
Basic insulation is ensured between the H3YN’s operating circuit and
control output.
Basic insulation:
Overvoltage category II,
pollution degree 1 (H3YN-4/-41, H3YN-4-Z/41-Z), pollution degree 2 (H3YN-2/-21)
(with a clearance of 1.5 mm and a creepage
distance of 2.5 mm at 240 VAC)
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. L089-E1-02
B-98
In the interest of product improvement, specifications are subject to change without notice.
Solid-state Timer H3YN