ETC H471156415-60HZ

Current and Voltage Controls
3-Phase Asymmetrical Relay
Type H 471
• Mains network quality and load monitoring
relay
• Monitors phase sequence, phase loss, phase
asymmetry and phase angle
• Measures asymmetry on 3-ph. voltage without neutral
• Built-in adjustable timer function
• Knob-adjustable asymmetry sensitivity
• Output: 10 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• H4-housing
• LED-indication for power supply and output ON
• Power supply is the 3-phased measuring voltage
Product Description
3-phase monitoring relay for
DIN-rail mounting for phase
sequence, phase loss, phase
asymmetry and phase angle.
Ordering Key
Often used to control phase
asymmetry in order to prevent any damage to the connected motors.
H 471 156 380-50 Hz
Housing
Type
Output
Power supply
Frequency
Type Selection
Plug
Output
Screw
SPDT
terminals
Freq.
Supply: 220 VAC
Supply: 380 VAC
Supply: 400 VAC
50 Hz
60 Hz
H 471 156 220-50 Hz
H 471 156 220-60 Hz
H 471 156 380-50 Hz
H 471 156 380-60 Hz
H 471 156 400-50 Hz H 471 156 415-50 Hz
H 471 156 400-60 Hz H 471 156 415-60 Hz
Input Specifications
Output Specifications
Input
Terminal 22
Terminal 23
Terminal 24
Output
Rated insulation voltage
Phase L3
Phase L2
Phase L1
measures on own supply
Supply Specifications
Power supply AC types
Rated operational voltage
Through term. 22, 23 & 24
220
Overvoltage cat. III (IEC 60664)
(IEC 60038)
3 x 220 VAC ± 15%,
50 or 60 Hz
380
3 x 380 VAC ± 15%,
50 or 60 Hz
400
3 x 400 VAC ± 15%,
50 or 60 Hz
415
3 x 415 VAC ± 15%,
50 or 60 Hz
Voltage interruption
≤ 40 ms
Dielectric voltage
None (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral,
line/line), direct connection
to electronics
Rated operational power
3 VA
Specifications are subject to change without notice (26.10.99)
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
Supply: 415 VAC
SPDT relay
250 VAC (rms)
(cont./elect.)
µ (micro gap)
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations
(at max. load)
≤ 7200 operations/h
≥ 2 kVAC (rms) (cont./elect.)
4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
1
H 471
General Specifications
τ = 0.2 s, worst case reaction
time may be up to 5 x τ
Adjustable delay on release
built-in (0.2 s - 10s)
Note:
Reaction time + set time =
actual delay on release time
Reaction time
Accuracy
OFF delay
10 s, -1/+3 s on max.
< o.1 s on min.
Delay on release 0.2-10 s. adj.
Time function
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Approval
LED, green
LED, red
(IEC 60947-1)
IP 20 B/front IP 40 D (IEC 60529)
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
300 g
CSA
Wiring Diagrams
Example 1
µ
L3
L2
L1
H 471
Example 2
µ
L3
L2
L1
H 471
Mode of Operation
The knob-adjustable H 471
detects phase asymmetries
of 2 to 12% of phase-phase
amplitude.
The relay operates when all
three phases are present at
the same time and the phase
sequence is correct as well
as the measured asymmetry/
unbalance is below set point
(2 to 12% of phase asymmetry). Phase angle failures are
registered as phase asymmetry.
If the supply voltage drops to
approx. 25% of the phasephase voltage, the relay releases without time delay.
Applications of asymmetry
I: Mains monitoring:
Phase sequence.
Phase loss.
Phase amplitude asymmetry.
II:Load monitoring:
Phase sequence (direction
of motor rotation).
Fuse blowing.
Example 1
Mains network monitoring
The relay measures phase
loss, that the power supply has
correct phase sequence, that
all three phases are present,
and that the phase asymmetry is within the preset level.
Setting
The allowed asymmetry for
the mains voltage amplitudes
is set on the potentiometer.
Example 2
Load monitoring
The 3-phased monitoring relay for electrical loads ensures
correct starting and operating conditions. The relay monitors phase sequence and
consequently the correct direction of motor rotation.
The most frequent cause of
asymmetry and unbalance is
fuse blowing. In this case the
motor regenerates the interrupted phase. The size of the
regenerated phase depends
on the actual mechanical load
and motor size. In this case it
is a combination of phase
amplitude and phase angle
asymmetry higher than 2-3%.
Setting
Turn the asymmetry potentiometer counterclockwise (from
max.) until the relay releases.
Continue adjusting approx. 1
mark clockwise to ensure correct operation. At approx. 5%
or less asymmetry, ensure
that possible power supply
variations do not result in erroneous release.
Time/Range Setting
Range setting
Left potentiometer:
Phase asymmetry sensitivity
2 to 12% of phase-phase
amplitude. Adjustable on absolute scale.
2
Time setting
Right potentiometer:
Time setting on relative scale.
Adjustable delay on release:
0.2 to 10 s.
Specifications are subject to change without notice (26.10.99)
H 471
Operation Diagram
Phase L1, terminal 24
Phase L2, terminal 23
Phase L3, terminal 22
Set asymmetry
Hysteresis
Measured asymmetry
Relay ON
Specifications are subject to change without notice (26.10.99)
3