LEM HAZ14000-SRU

Current Transducers HAZ 4000..20000-SRU
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 4000..20000 A
VOUT = 0-10 V
(T-RMS DC)
Electrical data
Primary nominal
r.m.s. current
IPN (A)
Primary current
measuring range
IP (A)
±
±
±
±
±
±
4000
6000
10000
12000
14000
20000
VC
IC
IOC
RIS
VOUT
ROUT
RL
4000
6000
10000
12000
14000
20000
Type
Features
HAZ 4000-SRU
HAZ 6000-SRU
HAZ 10000-SRU
HAZ 12000-SRU
HAZ 14000-SRU
HAZ 20000-SRU
Supply voltage (± 5 %)
Current consumption
Overload capacity
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Output internal resistance
approx.
Load resistance
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
± 15
± 30
30,000
> 1000
0-10
100
> 10
V
mA
A
MΩ
V DC
Ω
kΩ
Accuracy - Dynamic performance data
X
ε
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error 1) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C, @ IP = 0
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IPN
Frequency range, ±3 dB, small signal 2)
L
VOE
VOH
VOT
TCε G
tr
f
<±1
%
< ± 0.5 % of IPN
< ± 100
mV
< ± 12.5
mV
<±1
mV/K
< ± 0.05 %/K
< 400
ms
DC and 15 to 3kHz
General data
• True-rms, 0-10V DC voltage output
• Isolation voltage 12kV Rms/ 50 Hz
/ 1 min
• Low power consumption
• Package in PBT meeting UL 94-V0
Advantages
• Easy mounting
• Small size and space savings
• Only one design for wide current
ratings range
• High immunity against external
interference
Applications
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
TA
TS
Ambient operating temperature
Ambient storage temperature
Housing PBT 30% glassfiber
UL94 classification
Mass
Standards 3)
m
Notes :
1)
2)
3)
- 25 .. + 85
- 30 .. + 90
°C
°C
V0
approx. 6
kg
EN 50178:1997
• Power supplies for welding and
telecom applications.
Application Domain
• Industrial
Linearity data exclude the electrical offset.
To avoid excessive core heating.
Please consult characterisation report for more technical details and
application advice.
060428/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 1/3
www.lem.com
Current Transducer HAZ 4000..20000-SRU
Isolation characteristics
Vb
Vb
Vd
Ve
Vw
dCp
dCl
CTI
Nominal Voltage
with IEC 61010-1 standard and following conditions
- Single insulation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
Nominal Voltage
with EN 50178 standard and following conditions
- Reinforced insulation
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
R.m.s. voltage for partial discharge extinction @ 10pC
Impulse withstand voltage 1.2/50µs
Creepage distance
Clearance distance
Comparative Tracking Index (Group IIIa)
2000
V r.m.s.
2000
V r.m.s.
12
>3
27
> 45
> 45
220
kV
kV
kV
mm
mm
V
060428/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 2/3
www.lem.com
Dimensions HAZ 4000..20000-SRU (in mm. 1 mm = 0.0394 inch)
FUJICON F2023A
6
48
50
6
T.P.
5
4
3
1
2
GND OUTPUT 0V -Vc
Connection Circuit
1
+Vc
HAZ 10000-SRU
HAZxxx-SRU
250 +/-1.5
1
+Vc
2
-Vc
3
0V
235
42
21.5
41.5
42±±+/-1
RL=10K ohm
4
OUTPUT
5
GND
6
T.P.
(Internal test point used
during factory calibrations)
161
± ±1 2
162
162
+/-1
75
160 +/-1.5
65
125
4-D6
Operation Principle
7.5
+Vc
Terminal
1...+Vc
2...-Vc
3...0V
4...OUTPUT
5...GND
6...T.P.
M5
50
48
35
200
Output
0V
Ip
-Vc
General tolerance +/-0.5
Mechanical characteristics
• General tolerance
• Aperture for primary conductor
± 0.5 mm
162 mm x 42 mm
(± 2 mm)
• Transducer fastening
4 x M5
(not supplied)
• Recommended fastening torque < 5 Nm
• Connection of secondary
Fujicon F2023A
(6 terminals)
Remarks
• Temperature of the primary conductor should not exceed
120°C.
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
060428/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM
Page 3/3
www.lem.com