ETC JCK-4R

Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A,
JCL, & JCL-A
• The JCK-A and JCL-A are standard JCK and JCL product
with an additional Westinghouse amp guard hookeye.
• This single hookeye is on one end of the fuse and aids in the
insertion and removal of the fuse.
• R-Rated medium voltage fuses are back-up current limiting
fuses used in conjunction with medium voltage motors and
motor controllers.
• Current limiting fuses may be designated as R-Rated if they
meet the following requirements:
1. The fuse will safely interrupt all currents between its minimum and maximum interrupting ratings.
2. The fuse will melt in a range of 15 to 35 seconds at a
value of 100 times the “R’ number (ANSI C37.46).
• Bussmann R-Rated current limiting fuses are designed for
use with medium voltage starters to provide short-circuit protection for the motor and motor controller.
• These fuses offer a high level of fault current interruption in a
self-contained, non-venting package which can be mounted
indoors or in an enclosure.
• Blown fuse indication on all fuses.
CATALOG SYMBOL: JCK, JCK-A, JCL, JCL-A
R-RATED
MEDIUM VOLTAGE
CURRENT LIMITING
2750V AC — JCK, JCK-A
5500V AC — JCL, JCL-A
MAX. DESIGN VOLTAGE
2750V AC — JCK, JCK-A
U.L. RECOGNIZED MAXIMUM 2540V AC — JCK, JCK-A
MAX. DESIGN VOLTAGE
5500V AC — JCL, JCL-A
U.L. RECOGNIZED MAXIMUM 5080V AC — JCL, JCL-A
U.L. RECOGNIZED
(GUIDE #M5552, FILE # E96676)
12-21-98
SB98107
Rev. A
Form No. JCK & JCL
Page 1 of 3
BIF Doc #6001
Bussmann®
R-Rated Fuses
JCK, JCK-A,
JCL, & JCL-A
For Motor Circuit Protection
Medium Voltage
Dimensional Data
INDICATOR
Showing Fuse is Open
0.38"
(9.5mm)
C
INDICATOR
Showing Fuse
is Open
A
B
Specifications
Buss
Catalog No.
Amperage
Maximum
Design Voltage
Dimensions (Inches)
A
B
C
Construction
Max. Int. Cap.
Amps (Asym.)
Amps (Sym.)
Min. Int. Cap.
Amps (Sym.)
2400V; R-Rated; Indoor/Enclosure
JCK-2R
70 2R
2750V
11.24
3.0
3.0
Single
80,000
50,000
165
JCK-3R
100 3R
2750V
11.24
3.0
3.0
Single
80,000
50,000
220
JCK-4R
130 4R
2750V
11.24
3.0
3.0
Single
80,000
50,000
320
JCK-5R
150 5R
2750V
11.24
3.0
3.0
Single
80,000
50,000
410
JCK-6R
170 6R
2750V
11.24
3.0
3.0
Single
80,000
50,000
480
JCK-9R
200 9R
2750V
11.24
3.0
3.0
Single
80,000
50,000
720
JCK-12R
230 12R
2750V
11.24
3.0
3.0
Single
80,000
50,000
970
JCK-18R
390 18R
2750V
11.24
3.0
3.0
Double
80,000
50,000
1430
JCK-24R
450 24R
2750V
11.24
3.0
3.0
Double
80,000
50,000
1880
2400V; R-Rated; Indoor/Enclosure; With Westinghouse Amp guard Hookeye
JCK-A-2R
70 2R
2750V
11.24
3.0
3.0
Single
80,000
50,000
165
JCK-A-3R
100 3R
2750V
11.24
3.0
3.0
Single
80,000
50,000
220
JCK-A-4R
130 4R
2750V
11.24
3.0
3.0
Single
80,000
50,000
320
JCK-A-5R
150 5R
2750V
11.24
3.0
3.0
Single
80,000
50,000
410
JCK-A-6R
170 6R
2750V
11.24
3.0
3.0
Single
80,000
50,000
480
JCK-A-9R
200 9R
2750V
11.24
3.0
3.0
Single
80,000
50,000
720
JCK-A-12R
230 12R
2750V
11.24
3.0
3.0
Single
80,000
50,000
970
JCK-A-18R
390 18R
2750V
11.24
3.0
3.0
Double
80,000
50,000
1430
JCK-A-24R
450 24R
2750V
11.24
3.0
3.0
Double
80,000
50,000
1880
4800V; R-Rated; Indoor/Enclosure
JCL-2R
70 2R
5500V
15.76
3.0
3.0
Single
80,000
50,000
165
JCL-3R
100 3R
5500V
15.76
3.0
3.0
Single
80,000
50,000
220
JCL-4R
130 4R
5500V
15.76
3.0
3.0
Single
80,000
50,000
320
JCL-5R
150 5R
5500V
15.76
3.0
3.0
Single
80,000
50,000
410
JCL-6R
170 6R
5500V
15.76
3.0
3.0
Single
80,000
50,000
480
JCL-9R
200 9R
5500V
15.76
3.0
3.0
Single
80,000
50,000
720
JCL-12R
230 12R
5500V
15.76
3.0
3.0
Single
80,000
50,000
970
JCL-18R
390 18R
5500V
15.76
3.0
3.0
Double
80,000
50,000
1430
JCL-24R
450 24R
5500V
15.76
3.0
3.0
Double
80,000
50,000
1880
4800V; R-Rated; Indoor/Enclosure; With Westinghouse Amp guard Hookeye
JCL-A-2R
70 2R
5500V
15.76
3.0
3.0
Single
80,000
50,000
165
JCL-A-3R
100 3R
5500V
15.76
3.0
3.0
Single
80,000
50,000
220
JCL-A-4R
130 4R
5500V
15.76
3.0
3.0
Single
80,000
50,000
320
JCL-A-5R
150 5R
5500V
15.76
3.0
3.0
Single
80,000
50,000
410
JCL-A-6R
170 6R
5500V
15.76
3.0
3.0
Single
80,000
50,000
480
JCL-A-9R
200 9R
5500V
15.76
3.0
3.0
Single
80,000
50,000
720
JCL-A-12R
230 12R
5500V
15.76
3.0
3.0
Single
80,000
50,000
970
JCL-A-18R
390 18R
5500V
15.76
3.0
3.0
Double
80,000
50,000
1430
JCL-A-24R
450 24R
5500V
15.76
3.0
3.0
Double
80,000
50,000
1880
12-21-98
SB98107
Rev. A
Form No. JCK & JCL
Page 2 of 3
BIF Doc #6001
Bussmann®
R-Rated Fuses
JCK, JCK-A,
JCL, & JCL-A
For Motor Circuit Protection
Medium Voltage
R
RATING
24
18
12
JCL
100,000
6
AMPERE
RATING
100
9
6
4
3
2
10,000
10
200,000
80,000
1,000
10,000
A
1,000
PROSPECTIVE SHORT CIRCUIT CURRENT
ASYMMETRICAL RMS AMPERES
TIME IN SECONDS
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
300
2
3
4
B
JCK
18
24
400,000
9
12
Time-Current Characteristic Curves–Average Melt
Current Limitation Curves
1
20,000
10,000
1,000
20
.01
100
.1
CURRENT IN AMPERES
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-21-98
SB98107
Rev. A
Form No. JCK & JCL
Page 3 of 3
BIF Doc #6001