LEM LTS25-NP

Current Transducer LTS 25-NP
IPN = 25 At
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16054
Electrical data
IPN
IPM
VOUT
G
NS
RL
R IM
TCR IM
VC
IC
Primary nominal current rms
Primary current, measuring range
Output voltage (Analog) @ IP
IP = 0
Sensitivity
Number of secondary turns (± 0.1 %)
Load resistance
Internal measuring resistance (± 0.5 %)
Temperature coefficient of R IM
Supply voltage (± 5 %)
Current consumption @ VC = 5 V
Typ
25
At
0 .. ± 80
At
2.5 ± (0.625·IP/IPN) V
2.5 1)
V
25
mV/A
2000
≥2
kΩ
50
Ω
< 50
ppm/K
5
V
28 + IS2) +(VOUT /RL)mA
ε
Accuracy @ IPN , TA = 25°C
Accuracy with R IM @ IPN , TA = 25°C
Linearity error
L
TCVOUT Temperature coefficient of VOUT @ IP = 0 - 10°C .. + 8 5°C
- 40°C .. - 10°C
TCG
Temperature coefficient of G
- 40°C .. + 85°C
VOM
Magnetic offset voltage @ IP = 0,
after an overload of 3 x IPN
5 x IPN
10 x IPN
t ra
tr
di/dt
BW
Reaction time @ 10 % of IPN
Response time to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (0 .. - 0.5 dB)
(- 0.5 .. 1 dB)
± 0.2
± 0.7
< 0.1
Typ
50
%
%
%
Maxi
100 ppm/K
150 ppm/K
50 3) ppm/K
± 0.5
± 2.0
± 2.0
< 100
< 400
> 60
DC .. 100
DC .. 200
mV
mV
mV
ns
ns
A/µs
kHz
kHz
General data
TA
TS
m
Notes:
Ambient operating temperature
Ambient storage temperature
Insulating material group
Mass
Standards 4)
1)
2)
3)
4)
070129/19
• Closed loop (compensated) multi•
•
•
•
•
range current transducer using the
Hall effect
Unipolar voltage supply
Isolated plastic case recognized
according to UL 94-V0
Compact design for PCB mounting
Incorporated measuring resistance
Extended measuring range.
Advantages
Accuracy - Dynamic performance data
X
Features
- 40 .. + 85
°C
- 40 .. + 100
°C
III a
10
g
EN 50178: 1997
IEC 60950-1: 2001
Absolute value @ TA = 25°C, 2.475 < VOUT < 2.525
IS= IP/N S
Only due to TCR IM
Specification according to IEC 61000-4-3 are not guaranteed between
180 and 220 MHz.
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Very low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
•
•
•
•
•
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding
applications.
Application domain
• Industrial.
Copyright protected.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
w w w .lem.com
Current Transducer LTS 25-NP
Isolation characteristics
Vd
VW
Rms voltage for AC isolation test, 50 Hz, 1 min
Impulse withstand voltage 1.2/50 µs
3
>8
kV
kV
Ve
Rms voltage for partial discharge extinction @ 10pC
Mini
> 1.5
kV
dCp
dCl
CTI
Creepage distance 5)
Clearance distance 6)
Comparative Tracking Index (Group III a)
Mini
15.5
6.35
175
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions :
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
600 V
600 V
Reinforced isolation
300 V
300 V
dCp, dCI, V W
Notes:
5)
6)
On housing
On PCB with soldering pattern UTEC93-703.
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
070129/19
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com
Dimensions LTS 25-NP
(in mm. 1 mm = 0.0394 inch)
Bottom view
Operation principle
Front view
Back view
Number
of primary
turns
1
Primary nominal
current rms
IPN [ A ]
± 25
Nominal
output voltage
VOUT [ V ]
2.5 ± 0.625
Right view
Primary
resistance
R P [ mΩ ]
0.18
Primary
insertion inductance
L P [ µH ]
Recommended
connections
± 12
2.5 ± 0.600
0.81
±8
2.5 ± 0.600
1.62
4
OUT
1
6
2
5
3
4
OUT
1
6
2
5
3
4
OUT
1
2
3
0.05
IN
3
5
0.013
IN
2
6
0.12
IN
Mechanical characteristics
• General tolerance
• Fastening & connection of primary
Recommended PCB hole
• Fastening & connection of secondary
Recommended PCB hole
• Additional primary through-hole
Output Voltage - Primary Current
± 0.2 mm
6 pins 0.8 x 0.8 mm
1.3 mm
3 pins 0.5 x 0.35 mm
0.8 mm
∅ 3.2 mm
VOUT [ V ]
5
4.5
3.125
2.5
Remarks
1.875
• VOUT is positive when IP flows from terminals 1, 2, 3 to
0.5
terminals 6, 5, 4.
• Temperature of the primary jumper should not exceed 100°C.
- IPmaxi
- IPN 0
IPN
IPmaxi
IP [ At ]
Page 3/3
070129/19
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com