AZETTLER SG-34FD240A40ZSL

SG-34F
“HOCKEY PUCK”
SOLID STATE RELAY
40 THRU 80 AMPS
48 TO 530 VRMS
FEATURES
•
•
•
•
•
•
•
Photo isolation
Up to 1200V blocking voltage
Both zero cross or random turn-on
High surge capability
Built-in snubber
UL, CUR file E43203
SCR Output Circuitry
INPUT
DC Input
AC Input
3 to 32 VDC
90 to 280 VAC
3 VDC max.
90 VAC max.
Type
Control Voltage Range
Turn On Voltage
Turn Off Voltage
Max. Input Current
1 VDC min.
10 VAC min.
25 mA at 32 VDC
-
-32 VDC
-
Max. Reverse Voltage
OUTPUT
Type
Output Voltage Range
Blocking Voltage
Max. Leakage Current (off)
240
380
48 to 280 VAC
48 to 400 VAC
48 to 530 VAC
600 Vpk
800 Vpk
1200 Vpk
5 mA
5 mA
Max. Voltage Drop (at rated current)
5 mA
1.7 VRMS
Max. Turn-On Time
Random Turn On (DC input): 1 ms
Zero Cross Turn On (DC input): 1/2 cycles + 1 ms
AC Input: 20 ms
Max. Turn-Off Time
DC Input: 1/2 cycle + 1 ms
AC Input: 40 ms
Min. Off-State (dv/dt)
480
500 V/us
GENERAL
Dielectric Strength
Insulation Resistance
Max. Capacitance (in/out)
Ambient Temperature
4000 Vrms min. (at 50/60 Hz, 1 min.)
1000 Min. (at 500 VDC)
8 pf
Operating: -30°C (-22°F) to 80°C (176°F)
Storage: -30°C (122°F) to 100°C (212°F)
Panel Mount
Termination
Weight
Screw
88g
7/16/08W
SG-34F
RELAY ORDERING DATA
SG-34F
D
MODEL
240
INPUT
VOLTAGE
A
OPERATING
VOLTAGE RANGE
D: 3 to 32 Vdc
A: 90 to 280Vac*
240: 48 to 280 Vac
380: 48 to 400 Vac
480: 48 to 530 Vac
40
LOAD TYPE
A: AC LOAD
*UL pending
Z
S
L
LOAD
CURRENT
ZERO CROSS OUTPUT DEVICE
OR RANDOM
LED
INDICATOR
40:
50:
60:
70:
80:
Z: Zero cross
turn on
NIL: no LED
L: with LED
(not for AC
input type)
40A
50A
60A
70A*
80A*
P: Random
turn on (not
available on
480V version)
S: SCR
MECHANICAL DATA
Outline Dimensions
Mounting
1.870
[47.5]
2-M.118
[M3.0]
2-M.157
[M4.0]
.902Max
[22.9]
.795Max
[20.2]
Wiring Diagram
Load power supply
Load
1.870
[47.5]
4
1.00
[25.4]
LOAD
2-Ø.177
[Ø4.5]
1
1.098
[27.9]
.449
[11.4]
3
1
2
(~)
(-)
(~)
(+)
4
1.799MAX
[45.7]
INPUT
3
2
input control signal
1.743
[44.26]
.323
[8.2]
2.299MAX
[58.4]
Dimensions in inches with metric equivalents in parentheses. Tolerance: ± .010"
INSTALLATION
PRECAUTIONS
1.
When mounting the relays side by side, provide a space equivalent
to the width of a single SSR between two adjacent SSRs.
Otherwise, reduce the load current flow to 1/2 to 1/3 of the rated current.
1.
Before connecting a load that generates a high surge current,
such as a lamp load to the SSR, make sure that the SSR can
withstand the surge current of the load.
2.
2.
When mounting relays on heat sink surface, first apply a heat conductive grease to the metal back surface of the SSR. Press the SSR
firmly onto the heat sink to ensure a good seal. Screw the SSR
down to the heat sink.
The product data sheet shows the non-repetitive peak value of
the surge current that flows through the SSR. Normally, use 1/2
of the non-repetitive peak surge current as the standard value. If
a surge current exceeding that value is expected, connect a
quick-blowing fuse to protect the SSR.
3.
Next, wire the screw terminals and securely tighten the screws.
7/16/08W
SG-34F
CHARACTERISTIC CURVES
4
.
7/16/08W