SCHURTER 4304.4023

FKI
Power Entry Modules with Line Filter
www.schurter.com/pg06
IEC Appliance Inlet C14 with Filter, Fuseholder 2-pole, Line Switch 2-pole
Standard- or Medical-Filter
on phase-out
C14
70° C
Description
-Panel Mount:
Screw-on mounting from front side
-4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 2-pole, Line filter in standard and medical version
-Quick connect terminals 6.3 x 0.8 mm
Approvals
-VDE License Number: 40004665
-UL License Number: E72928
Characteristics
-Compact design with optimal shielding
-All single elements are already wired
-Plug removal necessary for fuse-link replacement
If the power entry module is installed as normal, it is not possible to
touch any live parts with the test-finger according to IEC60529
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
-With EMC-shield
-Qualified for use in equipment according IEC/EN 60950
Other versions on request
-Medical version M80
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, Distributor-StockCheck, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.25 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
EMC Products
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
2-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W (2-pole)
Admissible power acceptance at higher ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 1'700'000 h acc. to MIL-HB-217 F
FKI
Power Entry Modules with Line Filter
www.schurter.com/pg06
Dimensions
Case 45
recommend for new designs
55 mm
40 ±0.15
61±0.5
R1
60.2
6.3x0.8
ø 5.8x90°
49.5
ø 3.2
63
65 ±0.5
40
M3
3.5
28
R3
50 ±0.5
29.5±0.5
14
5.5
61.5
28.7
67
Case 50
on phase-out
40 ±0.15
61±0.5
R1
60.2
ø 3.2
6.3x0.8
ø 5.8x90°
49.5
63
65 ±0.5
40
M3
3.5
28
R3
50 ±0.5
15
5.5
41
28.7
55
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard Version
2 x 10
68
2.2
1
2
Standard Version
2x4
68
2.2
1
4
Standard Version
2 x 1.5
68
2.2
1
6
Standard Version
2 x 0.8
68
2.2
1
10
Standard Version
2 x 0.3
68
2.2
1
1
Medical Version (M5)
2 x 10
68
-
1
2
Medical Version (M5)
2x4
68
-
1
4
Medical Version (M5)
2 x 1.5
68
-
1
6
Medical Version (M5)
2 x 0.8
68
-
1
10
Medical Version (M5)
2 x 0.3
68
-
1
EMC Products
29.5±0.5
FKI
Power Entry Modules with Line Filter
www.schurter.com/pg06
Diagrams
Standard version
Medical version
N
N’
F2
1) PE
L
1) Line
2) only FKI
3) Load
L1
R
F1
Cx
L2
Cx
PE’
2)
L’
1) Line
2) Load
Admissible power acceptance in Watt per pole
Derating Curves
2-pole
1.6
1.4
1.2
I = 1.0 In
1.0
0.8
I = 0.7 In
0.6
I = < < In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
Standard version
1A
- - - - differential mode _____ common mode
2A
4A
6A
2A
4A
6A
10 A
Medical version (M5)
1A
10 A
EMC Products
FKI
Power Entry Modules with Line Filter
www.schurter.com/pg06
Variants
Socket and fuse drawer included
Type
Rated Current
[A]
Filter-Type
Fuseholder
Line Switch
Housing
Material: Housing
Comment
Order Number
FKI
1
Standard Version
2-pole
2-pole
45
Aluminum
-
4304.4061
FKI
2
Standard Version
2-pole
2-pole
45
Aluminum
-
4304.4062
FKI
4
Standard Version
2-pole
2-pole
45
Aluminum
-
4304.4063
FKI
6
Standard Version
2-pole
2-pole
45
Aluminum
-
4304.4064
FKI
10
Standard Version
2-pole
2-pole
45
Aluminum
-
4304.4065
FKI
1
Medical Version (M5)
2-pole
2-pole
45
Aluminum
-
4304.4091
FKI
2
Medical Version (M5)
2-pole
2-pole
45
Aluminum
-
4304.4092
FKI
4
Medical Version (M5)
2-pole
2-pole
45
Aluminum
-
4304.4092
FKI
6
Medical Version (M5)
2-pole
2-pole
45
Aluminum
-
4304.4094
FKI
10
Medical Version (M5)
2-pole
2-pole
45
Aluminum
-
4304.4095
FKI
1
Standard Version
2-pole
2-pole
50
Nickel plated steel
1)
4304.4021
FKI
2
Standard Version
2-pole
2-pole
50
Nickel plated steel
1)
4304.4022
FKI
4
Standard Version
2-pole
2-pole
50
Nickel plated steel
1)
4304.4023
FKI
6
Standard Version
2-pole
2-pole
50
Nickel plated steel
1)
4304.4024
FKI
10
Standard Version
2-pole
2-pole
50
Nickel plated steel
1)
4304.4025
FKI
1
Medical Version (M5)
2-pole
2-pole
50
Nickel plated steel
1)
4304.4066
FKI
2
Medical Version (M5)
2-pole
2-pole
50
Nickel plated steel
1)
4304.4067
FKI
4
Medical Version (M5)
2-pole
2-pole
50
Nickel plated steel
1)
4304.4068
FKI
6
Medical Version (M5)
2-pole
2-pole
50
Nickel plated steel
1)
4304.4069
FKI
10
Medical Version (M5)
2-pole
2-pole
50
Nickel plated steel
1)
4304.4070
1) Versions with nickel plated steel enclosure are on phase-out. For new designs we recommend the versions with aluminum enclosure.
Packaging unit 10 Pcs Accessories
Description
Assorted Covers
Rear Cover
0859.0074
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
5092
Appliance Outlet further types to FKI
Connector Overview complete
IEC Connector C15, Rewireable, Straight
0101
IEC Connector C15A, Rewireable, Straight
0102
IEC Connector C15A, Rewireable, Straight
0102-G
IEC Connector C15A, Rewireable, Angled
0112
IEC Connector C13, Rewireable, Angled
4012
Connector further types to FKI
...
EMC Products
FKI
Power Entry Modules with Line Filter
www.schurter.com/pg06
Category / Description
Power Cord Overview complete
Power Cord with IEC Connector C13, Angled
0311
Power Cord with IEC Connector C13, Angled
3011
Power Cord with IEC Connector C13, Angled
3012
Power Cord with IEC Connector C13, Angled
3013
Power Cord with IEC Connector C13
3020
Power Cord further types to FKI
...
The specifications, descriptions and illustrations indicated in this document
are based on
EMC Products