GAMEWELL-FCI AAM95-2ND

AAM95
Features
• Monitors and controls analog
addressable sensors.
Analog Addressable Module
• Monitors and controls addressable input
and output devices.
• Monitors and controls up to 126 points
per circuit.
• XP95 protocol.
Description
g2021ph1.jpg
Gamewell’s Analog Addressable
Module (AAM95) provides the
monitoring and control of XP95
protocol sensors and addressable
input and output devices. The
AAM95 is compatible with the IF632
and IF650 Fire Alarm Control Panels
(FACPs). The analog addressable
module is configured with one, two, or
four analog circuits, with each circuit
capable of monitoring up to 126
individual points. The AAM95 has a
dedicated microprocessor that
monitors each circuit while communicating all status information to the
main CPU of the IF632 or IF650
control panel.
Each AAM95 has an optional display that provides Alarm and Trouble annunciation LEDs and tactile switches for control by circuit. The display has
provisions for custom labeling of each circuit.
Operation
The Analog Addressable Module (AAM95) occupies a bus position in the
IF632 or IF650 Control Panel. Compatible devices (including any Series 95
devices) return their analog value to the AAM95 module, which communicates with the main CPU of the FACP for evaluation of the analog value. If
the panel determines that the value is outside the normal range, the system
enters alarm or trouble mode. Communication time is kept to a minimum
by utilizing parallel processing on both the system bus and the circuits of
the AAM95.
The AAM95 circuits are monitored by the system for ground faults. The
module will operate in the event that the system enters into Alarm Default
Mode.
The AAM95 will support Style 4, 6, and 7 wiring. Style 7 wiring requires
the use of line isolators (XP95-LI) to segregate the analog circuit in the
case of a direct short on the line.
Engineer’s Specifications
The system shall include analog addressable circuits for the monitor and
control of identifiable devices. The system’s analog addressable module
shall incorporate a dedicated microprocessor in order to minimize communications and response times to off-normal conditions. The analog addressable
module shall support Style 4, 6, and 7 in field wiring. The analog addressable module shall incorporate a default operation capability which will
allow the system to activate a general alarm even in the event of a main
CPU failure.
AAM95
CS-2021 09/01/06
Page 1 of 2
• 1, 2, or 4 analog addressable circuits per
module.
• Dedicated microprocessor minimizes
communications time.
• Field programmable.
• Default alarm mode operation.
• Power limited.
• Automatic drift compensation.
• Style 4, 6, and 7 wiring.
• Priority interrupt protocol.
• Cross-zoning per device or group.
• Sensitivity measurement per detector.
• Module can be removed without
disturbing field wiring.
Listings
Listings and approvals below
apply to the basic AAM95 Analog
Addressable Module. In some cases,
certain modules may not be listed by
certain approval agencies, or listing may
be in process. Consult factory for latest
listing status.
• UL Listed: file S521.
• FM approved.
• MEA approved: file 132-95-E.
• CSFM approved: files 7165-1288:144,
7165-1288:146.
The analog addressable module shall be capable of monitoring up to 126
devices per circuit. Analog circuitry shall be capable of supporting a priority
interrupt technique in order to facilitate real-time event processing. Analog
addressable modules shall be supplied as required in order to monitor all
necessary points.
Ordering Information
AAM95-1
Specifications
Standby current
30 mA (1 circuit).
35 mA (2 circuits).
55 mA (4 circuits).
Alarm current
One-loop, 126 points Analog Addressable Module with
standard display for IF632 or IF650 FACP. Includes
terminal strip and mounting hardware. XP95 protocol
compatible.
AAM95-2
Two-loop, 252 points Analog Addressable Module with
standard display for IF632 or IF650 FACP. Includes
terminal strip and mounting hardware. XP95 protocol
compatible.
AAM95-4
Four-loop, 504 points Analog Addressable Module with
standard display for IF632 or IF650 FACP. Includes
terminal strips and mounting hardware. XP95 protocol
compatible.
AAM95-1ND
AAM95-1 with no display.
AAM95-2ND
AAM95-2 with no display.
AAM95-4ND
AAM95-4 with no display.
30 mA (1 circuit).
35 mA (2 circuits).
55 mA (4 circuits).
Note: ND models allow the addition of another display
(i.e., BCD, RCE, SCD) in the same module bay.
AAM95-2E
Two-circuit Analog Addressable Expansion Module for
use with AAM95-2. Includes terminal strip and mounting
hardware. XP95 protocol compatible.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 2 of 2
AAM95
CS-2021
09/01/06