FUJI EDS10-74J

PAPERLESS RECORDER
DATA SHEET
PHR
This is a paperless recorder that displays measured data
on the LCD in real time and stores data in CompactFlash.
The type of input such as thermocouple, resistance
bulb, D.C. voltage (current), etc. can be arbitrarily set to 18
channels at the maximum.
The data stored in CompactFlash can be regenerated on
the screen, and the use of supplied support software allows the data to be regenerated on a PC screen.
The data recorded in ASCII format can be directly read in
a spreadsheet such as Excel, which facilitates the processing on a PC. (The data recorded in binary format cannot be
read in.)
FEATURES
1. Large capacity storage by CompactFlash
Measured data is periodically stored in CompactFlash.
In case of 512 MB, for example, display files for about
3 year and a half (display refresh cycle 30 sec) can be
taken up (in case of ASCII data format, 9 channels, maximum/minimum recording).
2.Quick search and display of past data
Data stored in CompactFlash can be displayed in succession by scrolling the screen.
3.Various display capability
Depending on the object of measurement, the most
suitable display format can be selected from a variety
of formats including bar graph display, trend display,
digital display, etc.
4.PC support software supplied as standard
Loader software that enables easy display and change of
set data and data viewer software that regenerates the
data stored in CompactFlash are supplied as standard.
5.Compact size
160 (W) × 144 (H) × 185 (D) mm(Panel mounting), Compact and as light as about 1.5 kg (9-point input, without
option).
6.18-point recording (Option)
12 types of thermocouples, 2 types of resistance bulbs
and DC voltage/current input can be recorded up to 18
points
7. Communication function (Option)
RS485 MODBUS communication is available.
8.LCD extinguishing function
Automatically extinguishes the LCD if nothing is operated for certain time. You can set the time after a lapse
of which the LCD is extinguished via parameter "LCD extinguishing time". The settable range is 0 to 60 minutes. Setting at 0 minute overrides the function, whereby the
LCD will never extinguish.
This function prevents the backlight life from shortening uselessly. During the extinguishment, the power
consumption can be reduced.
9.Ethernet function (Option)
FTP, Web server, e-mail and MODBUS-TCP are available
using 10Base-T.
SPECIFICATIONS
Input system
Number of input points:9 points or 18 points (Can be
selected at the time of purchase)
Input circuit:
Input mutual isolation (See "Others" on
page 5 for the withstand voltage)
Resistance bulb measured current:
about. 1 mA
Measuring cycles:9 or 18 points….100ms cycles
Recording cycle: 1 second to 12 hours
Input types:
Thermocouple, resistance bulb, dc voltage, and dc current (Shunt resistors are
fitted in input terminals).
Note) Provide a shunt resistor (type:
PHZP0101) separately.
Measuring range
Input types
Thermocouple
B
R
S
K
E
J
T
N
W
L
U
PN
Resistance bulb JPt100
Pt100
Reference range
400.0
0.0
0.0
–200.0
–200.0
–200.0
–200.0
0.0
0.0
–200.0
–200.0
0.0
–200.0
–200.0
to 1760.0ºC
to 1760.0ºC
to 1760.0ºC
to 1370.0ºC
to 800.0ºC
to 1100.0ºC
to 400.0ºC
to 1300.0ºC
to 1760.0ºC
to 900.0ºC
to 400.0ºC
to 1300.0ºC
to 600.0ºC
to 600.0ºC
0.00
to 50.00mV
50mV
0.0
to 500.0mV
500mV
1.000 to 5.000V
1-5V
0.000 to 5.000V
0-5V
Note) B, R, S, K, E, J, T : JIS C 1602, DIN IEC 584-1
N : NICOSIL-NISIL (IEC 584)
W : 5%Re-26%Re · W (Hoskins Mfg. Co. USA)
L : Fe-Cu · Ni (DIN 43710)
U : Cu-Cu · Ni (DIN 43710)
PN: Platinel
JPt100 : JIS C 1604-1989 (Old JIS Pt 100)
Pt100 : JIS C 1604, DIN IEC 751
DC voltage
EDS10-74j
Date
Dec. 5, 2011
PHR
Selection of input types:
By key operation on the front panel.
Note that the same input type (thermocouple, resistance bulb, voltage) should
be set every 2 channels. Refer to "Setting method of input types" for details.
Burn-out function:
Provided as standard for thermocouple
and resistance bulb inputs. If the input
has been open-circuited, the recording
level swings over 100%.
Thermocouple burn-out current:
approx. 0.2 µA
Input filter function:
Settable for each channel (primary delay
filter)
Time constants are settable in the range
from 0 to 900 sec.
Scaling function:Possible by dc voltage (current) input
Scaling range:-32767 to 32767
Decimal position:
settable at any point
Unit symbol: Selectable out of 125
different units or 12 user
units of up to 7 characters.
Subtraction function:
Subtraction between each channel is allowed.
Totalizing function:
The measured value of each channel
can be totalized. Applicable to daily,
monthly, annual or external input totalizing.
F value calculation function:
F value (extinction value of bacteria by
sterilization by heating) can be calculated from the measured temperature
by each channel.
F value and measured temperature can
be displayed and recorded using 2 channels.
Square rooter function:
Square rooter can be performed against
the input value per each channel.
Logarithmic calculation function:
The measured value of each channel
can be displayed in exponent form.
Mathematics function:
The following calculation is available
with the math function.
1) Computation function
Addition, subtraction, multiplication,
division, absolute value, exponential,
square-root extraction, LOG, LN, EXP,
humidity, maximum, minimum, average,
and integration.
2) Computation input enable
Channel input (1 to 30 CH), Total input
(1 to 30 CH), DI (DI to DI10), Communication input (No.1 to No.12), Constant
(No.1 to No.20).
2
Indication system
5.7" TFT color LCD (320 × 240 dots)
with backlight, no contrast adjustment.
On the LCD, certain picture elements
remain lit or extinguished. On account
o f t h e n a tu r e i n h e r e n t t o L C D, t h e
brightness may be non-uniform. But,
such are not troubles.
Color of indication:
14 colors
Applicable language:
English, Japanese
Life of backlight:50,000 hours (20°C) in terms of total
lighting time.
(Replace the backlight as a set of display unit. If the LCD extinguishing function is resorted to, the LCD can be used
longer as much.)
Trend display: Direction: vertical and horizontal
Number of channels: 10 or 4 channels
per screen group. (select from up to 30
channels).
Display refreshment cycles:
select from 1 second to 12 hours
Scale display or no-display can be selected.
Bar graph display:
Number of channels: 10 or 4 channels
per screen group. (select from up to 30
channels).
Display refreshment cycles: 1 second.
Analog meter display:
For 4 inputs per screen group. (input
from 1 to 4). Display in bar graphs or in
analog meters can be selected.
Display refresh cycle: 1 second
Digital display: Number of channels: 10 or 4 channels
per screen group. (select from up to 30
channels).
Display refreshment cycles: 1 second.
Totalizing data display:
Number of channels: 10 or 4 channels
per screen group. (select from up to 30
channels)
Display refresh cycle: 1 second.
Event summary display:
Alarm summary and message summary
can be displayed. The message occurrence information and message display
can be switched.
Ethernet log display:
E-mail sending, FTP server log in/off
and MODBUS TCP/IP communication
start/stop can be displayed.
Parameter display/set:
Already-set Data Display and Set
Change Display screen
TAG indication: Number of characters to be displayed:
Up to 8 characters
Up to 8 characters (Note 1)
at 10-channel display.
U p t o 16 ch a r a c t e r s a t 4
channel display.
Note 1: Up to 7 characters
only can be displayed
on certain screens.
Indicator:
Characters to be displayed:
Alphanumerics, hiraganas
and katakanas.
Tag, unit and channel No. display:
Which can be displayed
depends on the particular
screen. Refer to the table
below.
(Keywords only are extracted.)
Screen
Channnels per
screen
Trend
4 or less
5 or more
Bar graph
4 or less
5 or more
Analog
4 or less
meter
5 or more No. 1 to 4
Others
Instantaneous 4 or less
value
5 or more
x: 1 item only can be displayed
+: 2 items only can be displayed
–: Nothing can be displayed
Tag 1
+
x
+
x
x
Item
Tag 2 Unit ch Np.
+
+
+
–
x
x
+
+
+
–
x
x
All
All except tag 2
–
x
All
All except tag 2
Historical trend display:
Displays past recording data read from
compact flash, currently recording
data or just recorded data. The recording chart can be scrolled or, via time
designation, the control can jump to an
arbitrary recording chart.
Number of screen groups:
Four groups (Up to 10 channels per 1
group can be registered.)
Keyboard
No. of Keys:
Function:
8
Use to select various screens and set
various parameters.
Recording function
External memory media:
Compact Flash card
Format according to FAT32, FAT16 or
FAT. Otherwise, reading and saving are
impossible.
Recording capacity:
2GB maximum (compact flash). Limiting the recording file to 64 MB is
recommended (for 112 hours if display
refresh cycle is 1 second. See Table 1 (p.
7).) (When the size of the recording file
comes to be 256MB or more, a new file
is created automatically and recording is
maintained.)
* Please change the compact flash
every six month to prevent the data losing.
Recording method:
Turning ON the REC key allows measured data to be written at fixed cycles.
Recorded as a new file whenever the
recording starts.
Data save cycles:Linked to the display refreshment cycles
on the ”Real Time Trend” screen. However, they are automatically set to about
1 minute if the refreshment cycles are
set to less than 1 minute.
Trend data:
Measurement data sampled at measurement cycle is saved in terms of
mean value, inst ant aneous value or
maximum/minimum value.
Event data:
Saves alarm data and message data.
Further saves power ON and OFF, if any,
after starting recording.
Totalizing value data:
Records the totalized data according to
the totalizing type selected by channels.
Values by totalizing types or total from
the beginning of totalizing, whichever
selected, can be recorded. For each
channel, the input value totalizing,
number of DI inputs or measurement
at times when DI inputs have occurred
can be selected. Input values to be
totalized are selected from daily report,
monthly report, yearly report and external input.
If power has been turned off and
on while totalizing, the totalizing is
resumed at last value. (Last value
remains saved, but data during power
OFF is not totalized.)
Configuration data:
Configuration data can be saved. And
this data can also download to recorder.
Storage capacity:
Approximately 3 years when the display
refresh cycle is 30 seconds (in case of
9-channel recording in ASCII data format, and 512 MB compact flash used).
Refer to Table 1.
Residual capacity of memory:
Indicates how much of the memory
card has been used on the screen. When all the memory is used up, you
can stop recording or delete the oldest
recording file to save the newest data.
Compact flash card form:PHZP1301, PHZP2801
(CF card)
(If a card other than the above is used,
no operation assurance is ensured.
Meanwhile, as for other CF cards for
which operation check will have been
completed, the results will be posted
on our company's homepage sequentially. Please refer to this website.)
Data format:
Either of ASCII or binary format can be
selected. (Switching cannot be made
while the recording is in progress. In
the case of ASCII format, the data can
be directly read on Excel, etc.)
Note: The data recorded in binary format cannot be read directly.
Approximately 166 bytes per sampling
for maximum/minimum recording of
9-channel input in ASCII format, or approximately 40 bytes for maximum/minimum recording of 9-channel input in
binary format.
3
PHR
Alarm function
No. of settings: Up to 4 alarms for each channel are settable.
Type of alarm: High/Low limits
Indication:
Status (alarm types) is displayed on digital display unit when an alarm occurs.
Historical display on alarm summary
(Alarm start/cancel time and alarm
types)
Hysteresis:
Set within the recording range of 0 to
100%
Acts on high or low limit alarm, and
does not affect the battery alarm nor
memory full alarm.
Relay output:
Number of points; 10 (option: Cannot be
selected if the number of input points is
18.)
Transistor output (open collector output):
18 points (option)
Alarm latch function:
Holds alarm indication and alarm output
even after measurement value has left
the alarm range.
ON/OFF operation is performed according to key setting.
Power supply
*1: In case of the 12th digit of ordering code is "Y" or "R".
*2: In case of the 12th digit of ordering code is "E" or "W".
Reference standard
Rated power voltage:
100 to 240V AC
Range of operating voltage:
90 to 264V AC
Supply frequency:
50/60Hz ±2% (both employable)
Power consumption
Power voltage
Consumption
100V AC
About 36VA
240V AC
About 47VA
Structure
Mounting method:
Panel-mounted (vertical panel) or portable (desktop type)
Thickness of panel:
2 to 26 mm
Materials:
PC-ABS for case and bezel
Color:
Black
External dimensions:
Panel-mounted:160 (W) × 144 (H) ×
185 (D) mm
Portable:
160 (W) × 171.5 (H) ×
206.6 (D) mm
Mass:
About 1.5 kg (9-point input, without option)
External terminal board:
Screw terminals (M3 thread)
RJ45: Ethernet terminal (option)
Operating condition
Ambient temperature:
Panel-mounted(without Ethernet function): 0 to 50°C*1
Portable: 0 to 40°C
Panel mount (with Ethernet function): 0 to 40°C*2
4
Ambient humidity:
20 to 80%RH
Vibration:
10 to 60Hz 0.2m/s2 or less
Shock:
None
Magnetic field: 400 A/m or less
Signal source resistance:
Thermocouple input .... 1kohm or less
Resistance bulb input... 10ohm/wire or
less (resistance of each wire of 3-wire
system should be balanced).
Voltage input... 0.1% or less of input
resistance
Mounting posture:
Forward tilt 0º, backward tilt within 30º,
horizontal 0º
Warm-up time: One hour or more after power ON
Environmental protection:
IEC IP50 (Front)/20 (Terminal) Installation category:
II
Pollution degree:2
Operating altitude:
2000m max.
Accuracy/resolution:
Measuring conditions (23±2ºC, 65±
10% RH, power voltage, frequency
fluctuation within ±1%, no external
noise, warm-up time of 1 hour or more,
vertical mounting, standard values of
signal source resistance and wiring
resistance... within 1% )
Input types
Thermocouple B
R
S
K
E
J
T
N
W
L
U
PN
Resistance
bulb
DC voltage
Digital indication
accuracy
Note 1
Digital indication
resolution
±(0.15%+1 digit)
±(0.3%+1 digit)
for the range shown below
Thermocouple B :
400 to 600ºC
Thermocouples R and S :
0 to 300ºC
Thermocouples K, E, J, T,
L and U : -200 to -100°C
JPt100
±(0.15%+1 digit)
Pt100
50mV
500mV ±(0.15%+1 digit)
5V
0.1°C
0.1°C
10µV
100µV
1mV
Note 1) Digital indication accuracy is a percentage (%) with respect to
input range of 1 page.
Note 2) No error of reference contact compensation of thermocouple is
included.
Error of reference contact compensation:
K, E, J, T, N, L, U, PN: ±0.5ºC
R, S, B, W: ±1.0ºC
(when measured at 0ºC or more)
Max. input voltage:
Thermocouple, resistance bulb, dc voltage: ±10V DC (continuous)
Input impedance: Thermocouple, DC voltage:
About 1MΩ
Others
With calendar function (Christian era)
Accuracy: ±100 ppm or less (monthly
error: about 4 minutes)
However, time error at ambient temperature 23±2ºC and power ON/OFF is
not included.
Memory backup:Parameters are saved to the internal
non-volatile flash memory.
The clock is backed up with built-in
lithium battery.
Trend data is not backed up.
Insulation resistance:
100Ω or more (when measured between each terminal and ground by
using a 500V DC megger)
Withstand voltage:
Input terminal – input terminal:
500 V AC, 1 min
Power terminal – ground: 2000V AC, 1
min
Input terminal – ground:500V AC, 1 min
Alarm terminal (contact output) – ground:
2000 V AC, 1 min
Alarm terminal (contact output) – alarm
terminal (contact output):
750 V AC, 1 min
Communication terminal – ground:
500 V AC, 1 min
Alarm terminal (open collector) – ground:
500 V AC, 1 min
Power terminal – input terminal:
500 V AC, 1 min
Clock:
Effect on operation
Effect of power supply fluctuation conditions:
For the fluctuation in the range from 90
to 264V AC (frequeucy: 50/60Hz)
Reading change (100V AC base):
±(0.2%+1 digit) or lower.
For the fluctuation in the range from 47
to 63Hz (power voltage: 100V AC)
Reading change (50Hz base): ±(0.2%+1
digit) or lower.
Effect of input signal resistance:
Thermocouple input: (0.5µV/Ω)+1digit or
less
DC voltage: Fluctuation for resistance
value equivalent to 0.1% of the input
resistance: ±(0.2%+1 digit) or lower.
Reistance bulb (for wiring resistance of
10Ω for 1 line (the same for 3 lines))
Reading change: ±(0.2%+1 digit) or
lower.
Effect of ambient temperature:
Reading change: ±(0.3%+1 digit)/10ºC
or lower.
Effect of Mounting position:
For the backward 30º slant
Reading change: ±(0.2%+1 digit) or
lower.
Effect of vibration:
When sine wave of 10 to 60Hz with
the acceleration of 0.2m/s 2 is applied in
each direction for 2 hours.
Reading change: ±(0.2%+1 digit) or
lower.
Effect of external noise:
Normal mode noise (50, 60Hz±0.1Hz)
…20dB or more
Common mode noise (50, 60Hz±0.1Hz)
…120dB or more
(Thermocouple input: minus terminalground)
(Resistance bulb input: b Line-ground)
Safety and EMC standard
Safety standard:Based on IEC61010-1
(Portable type does not meet the standard.)
EMC standard: Based on EN61326
Transportation/storage conditions
Temperature:
Humidity:
Vibration:
Shock:
–10 to +60ºC
5 to 90%RH
10 to 60Hz, 2.45 m/s2 or lower
294m/s2 or lower (packed state)
Additional function (Option)
■ Alarm relay output/DI (11th digit of code symbols: ”1”)
A card with 10-point relay output and 5-point DI input can be mounted.
Cannot be mounted if the number of input points is
18.
Terminal structure: M3 screw terminal
Alarm relay output:
1a contact output (10 points),
Individual channel or common output
(OR output) allowed.
DO1: Contact capacity;150V/3A AC,
30V/3A DC (resistive load)
DO2-10: Contact capacity; 240V/3A AC,
30V/3A DC (resistive load)
DI input:
No-voltage contact input (5 points)
The following control is allowed by contact input.
(1) Recording start/stop
(2) Message set
(3) F value calculation reset
(4) Totalizing start/stop
(5) Totalized value reset
(6) LCD (backlight) lighting
(7) E-mail sending
ON pulse width: 200 msec or more
OFF pulse width: 200 msec or more
■ Communication, alarm (open collector output), DI
input (12 digit of code symbols is ”R” or ”W”)
RS485 communication. Card having 18 alarm points
(open collector output) and 5 DI input points can be
installed.
Terminal structure:
M3 thread terminal (DO11 (alarm open
collector output), DI6, DIO source terminal and communication terminal)
D-Sub 25 pin female terminal (DO12 to
DO28 (alarm open collector output)) and
DI7 to DI10
Communication:Physical specifications:
EIA RS485
Communication protocol:
Modbus (RTU)
5
PHR
Communication method:
2 wire method. Half duplex bit serial,
start-stop sync type.
Data type:
8 bits. Parity: odd/even/none. Stop bit: 1 bit.
Communication rate: 9600, 19200bps
Connection aspect:
multi-drop/up to 32 recorders connectable including master station
Communication distance:
Total extension 500m or less
RS232C/RS485 Signal converter (recommendation):
Isolated type
Manufacture: OMRON Corporation
Model: K3SC-10
Alarm output: Open-collector transistor output (18
points)
Electrical Rate: 30Vdc, 100mA (resistive
load)
DI input:
No-voltage contact input (5 points).
Contact input allows following controls.
(1) Recording start/stop
(2) Message set
(3) F value calculation reset
(4) Totalizing start/stop
(5) Totalized value reset
(6) LCD (backlight) lighting
(7) E-mail sending
ON pulse width: 200 msec or more
OFF pulse width: 200 msec or more
Ethernet (Option)
The following can be performed through the Ethernet
function.
■ HTTP server (Internet Explorer 6 is available) Note 1
Measurement display:
Digitally displays the measurement of
each channel of the recorder and alarm
occurrence status.
Event summary display:
Displays event summary including alarm
ON/OFF and issuance of messages.
Main unit information display:
Displays memory use conditions and information on the main unit such as the
battery end warning.
Integrated value display:
Digitally displays the integrated value of
each channel of the recorder.
■ FTP server (Internet Explorer 6 available.) Note 1
File download: Record files stored in compact flash (CF)
can be downloaded from the browser.
File delete:
Record files stored in CF can be deleted
from the browser.
Access authentication:
Authenticates access authority to FTP
server.
■ SMTP (e-mail client)
Transmits e-mails to specified address
under the following conditions.
(1) When an alarm turns on or off
(2) When DI is set to ON or OFF
(3) When an error occurs to the main
u n i t ( s u ch a s l ow b a tt e r y o r n o
memory space)
(4) At specified intervals
6 ■ MODBUS TC/IP
Data read:
Settings can be read through MODBUS
TCP/IP communication.
Data write:
Settings can be written through MODBUS TCP/IP communication.
Note1: Netscape is not available.
Support software
Note:
Applicable PC: PC/AT-compatible machine
Operation on PC98-series machines by NEC is not guaranteed.
Operation on self-made or shop-brand PCs is not guaranteed.
The following software is provided as standard.
■ Loader software for PC
Major function: Performs various parameter setting/
change of the main unit
O/S: Windows 2000/XP
Required memory:
64MB or larger
Disk drive:
Windows 2000/XP-capable CD-ROM
Hard disk capacity:
Free capacity of 30MB or larger required
Printer: Windows 2000/XP-capable printer and
printer driver
Note) PC loader communication cable (type PHZP1801) is
separately required.
■ Data viewer software
Major function: Regenerates the past trend record on
the PC from the data in the compact
flash. Provided with historical trend display and event display functions.
Data can be changed to CSV file.
O/S:
Windows 2000/XP
Required memory:
64MB or larger
Disk drive:
W indows 20 0 0/XP-capable CD-ROM
drive
Hard disk drive: Free capacit y of 30MB or larger required
Printer:
Windows 2000/XP-capable printer and
printer driver
Standard functions
Function
Record range
voluntary setting
Description
Recording range can be set by channel.
Input type setting
Input type can be set by channel.
(Key operation on the front face)
Set the same input type for every 2 channels.
Skip function
Trend display
Skips arbitrary channel display/recording.
Time display: Time is displayed at the top of the
trend display screen.
Alarm display: On occurrence of an alarm and the
restoration, alarm is displayed in the
alarm display field.
The compact flash usage is displayed with a
bargraph at the top.
TAG name display
Screen name
display
Unit creation
By channel, Maximum of 8 characters.
Displays the screen name (maximum of 16
characters).
Industrial units can be arbitrarily created, Maximum
of 7 digits, 12 types.
Arbitrary scaling is allowed in the case of DC
voltage input. Decimal point position can also be
arbitrarily set in the range from -32767 to 32767.
Scaling function
PV shift
Shift the zero point and slant of the reading.
Input filter
Prevents sudden fluctuation of input for each
channel (primary delay filter).
Time constant: 0 to 900 seconds.
Burnout function
Displays the break of thermocouple/resistance bulb
input by scaling out to 100% side.
Historical
trend display
Regenerates and displays the data stored in the
compact flash by scrolling the screen.
Displays data of a designated time.
Table 1. Recording capacity
The recording can be made for the period of time
listed in the tables shown below under the following
conditions.
CompactFlash size
64MB
•9 input points
Display upgrade cycle 1 sec
10 sec
30 sec
1 min
10 min
•Recording data format: ASCII
Recordable capacity
•Recording
type: Maximum/minimum
recording
112 hours 46 days 140 days
280 days 7.7 years
(about)
•No alarm, nor message, nor other events.
CompactFlash size
256MB
Display upgrade cycle
Recordable capacity(about)
1 sec
10 sec
30 sec
1 min
18 days 187 days 1.5 years 3 years
•When the number of input points is 18, the period is approximately one half of those listed in the table.
•In binary format, the period is approximately 4 times as
long as those listed in the table.
•For recording type of mean or instantaneous value, the
number of days is approximately 2 times as long.
While compact flash is not in use, recorded date and
event date can be stored approximately 600KB in the
main unit
When recording 9-channel in MAX-MIN recording, approximately 15300 data can be stored.
For 4 hours at the display refresh cycle of 1 second.
The number of the save data varies depending on the
number of the event data.
ORDERING CODE
Note
1
2
Note 3
12
13
Recorder (PHR)
1
1
Panel mounting bracket
2
—
CD-ROM PC support software instruction
manual
1
1
Panel packing for the front face
1
—
Noise filter for the power supply
1
1
AC power cord (2m)
—
1
OPTIONAL ITEMS
Item
Code
Specification
Shunt resistor for DC
current input
PC loader communication
cable
PHZP0101
10Ω ±0.1%
PHZP1801
Length 3m with
connector
USB-A/USB miniB
terminal *
CD-ROM with instruction
PHZP0301
manual and support software
Terminating resistor for
PHZP0701
communication
D-Sub light type 25 pin
PHZP0801
connector with male terminal
for alarm output
(without cable)
100Ω
PHZP0901
For PHR to PC
PHZP1001
For PHR to PHR
PC card adapter
PHZP0501
For compact flash
Compact flash
PHZP2801-512
PHZP1301-01G
512MB
1GB
* Shape of this cable is shown below
USB (A) Plug – USB (Mini-B ) Plug
1
2
B
Note 2
100 to 240 V AC
11
Quantity
Panel
Portable
mounting
Item
Transmission cable
4 5 6 7 8 9 10 11 12 13
B 1 4 1
Y
PHR
Digit
Specifications
4 <Number of input points>
9 channel
18 channel
5 <Mounting>
Panel mounting
Portable (desktop)
6 <Case color>
Black
7 <Compact flash>
Without (not furnished)
8 <Version No.>
Version No.
9 <Display>
Japanese
English
10 <Power supply>
SCOPE OF DELIVIRY
<Alarm (relay) output/DI input>
Without
With
Note 1
1
4
N
E
1
0
1
<Communication, alarm
(open collector) output/DI input>
Without
Communication (RS485), alarm output, Di input Note 4
Ethernet
Note 5
Ethernet, communication (RS485), alarm output, Di input Note 4,5
<Destination>
General
Y
R
E
W
Y
Note 1 : Cannot be selected if 2 is selected for the forth digit
(the number of input points is 18).
Note 2 : The compact flash is optional. Refer to the section of
"Optional items" below.
Note 3 : Portable mounting type doesn't comply with UL and CE.
Note 4 : Alarm output; transistor (open collector) output
Note 5 : Cannot be specified when "2" is selected for the 5th digit.
7
PHR
OUTLINE DIAGRAMS (Unit : mm)
PANEL MOUNTING TYPE
In the case of 9-point input
2
T
T
26
DI input & alarm terminal (option)
Mtg.bracket
Ethernet terminal (option)
Input terminal
(points 1 to 9)
Source terminal
L
DIOSHLD A6 DO11 COM 24VDC
IN
DIO-ON
TRX1 TRX2
R-MODULE
Rcj
Fuji Electric
144
136.5
161
N
100 240VAC
Panel
160
140
21.6
136.5
185
DIO terminal
(D-Sub) (option)
24.6 when panel packing is mounted
Communication
DIO terminal
(option)
(Note) When placing the main unit on another instrument
or on the floor, allow a space of 100mm or more between
the unit and instrument or the floor.
In the case of 18-point input
Ethernet terminal (option)
Input terminal (points 1 to 9)
T
Input terminal
(points 10 to 18)
Mtg.bracket
Source terminal
L
TRX1 TRX2
R-MODULE
Rcj
Fuji Electric
DIO-ON
R-MODULE
Rcj
Fuji Electric
144
136.5
161
N
100 240VAC
2 T 26
DIOSHLD A6 DO11 COM 24VDC
IN
Panel
160
140
21.6
136.5
185
24.6 when panel packing is mounted
DIO terminal
(D-Sub)
Communication
DIO terminal
(Note) When placing the main unit on another instrument
or on the floor, allow a space of 100mm or more between
the unit and instrument or the floor.
Panel cutout
Mounting one unit
Mounting close together sidewise
(160 × n−22) +20
n : Number of units to be mounted
137 +1.5
0
137 +1.5
0
137 +1.5
0
Do not use the water proof pacing in case of mounting n unit
8
PORTABLE (TABLE TOP) TYPE
In the case of 9-point input
Handle
DI input & alarm terminal (option)
Source terminal
DIOSHLD A6 DO11 COM 24VDC
IN
DIO-ON
160
15
49
TRX1 TRX2
R-MODULE
Rcj
Fuji Electric
144
136.5
208.5
20
Input terminal
(points 1 to 9)
136.5
140
21.6
185
DIO terminal
Communication
(D-Sub) (option) DIO terminal (option)
Foot
Stand-foot
(Note) Please use the stand-foot upright.
In the case of 18-point input
Handle
Input terminal
(points 10 to 18)
Input terminal
(points 1 to 9)
DIOSHLD A6 DO11 COM 24VDC
IN
DIO-ON
160
21.6
15
49
TRX1 TRX2
R-MODULE
Rcj
Fuji Electric
R-MODULE
Rcj
Fuji Electric
144
136.5
208.5
20
Source terminal
140
185
Stand-foot
Foot
136.5
DIO terminal
Communication
(D-Sub) (option) DIO terminal (option)
(Note) Please use the stand-foot upright.
9
PHR
EXTERNAL CONNECTION DIAGRAMS
PANEL MOUNTING TYPE
In the case of 9-point input
Source terminal
M3 thread
Resistance
Thermo- Voltage
bulb
Voltage Thermo- Resistance
bulb
couple
couple
+
+
11
+
+
61
CH1
12
CH6
62
13
63
+
+
21
+
+
71
22
CH2
72
CH7
23
73
+
+
31
CH3
32
RCJ
33
+
+
41
+
+
81
CH4
42
82
CH8
43
83
+
+
51
+
+
91
CH5
52
92
CH9
53
93
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
DI1
DI2
DI3
DI4
DI5
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8
DO9
DO10
M3 thread
M3 thread
AC100 240V
50/60Hz
(Note) For current input, connect an optional
shunt resistance to a voltage input terminal
PCD
1
14
13
25
6
7
8
9
10
11
12
15
16
17
18
19
20
21
22
23
24
2
3
4
5
VPD
PCD
DO12
DO13
DO14
DO15
DO16
DO17
DO18
DO19
DO20
DO21
DO22
DO23
DO24
DO25
DO26
DO27
DO28
DI7
DI8
DI9
DI10
VPD
VPD
24Vdc
Input terminal
DIO(+24V)
PCD
PCD
DIO(0V)
DO11
DI6
SHLD
TRX2
–
TRX1
+
(shield)
(–)
(+)
MODBUS
communication
Alarm output/digital input terminal
Communication, digital input
and alarm (open collector)
output terminal (M3 thread)
PCD
Digital input and alarm
(open collector) output terminal,
D-Sub terminal
In the case of 18-point input
Input terminal
Source terminal
Resistance
Thermo- Voltage
bulb
couple
+
+
11
61
- CH1
12
62
13
63
+
+
21
71
- CH2
22
72
23
73
+
+
31
- CH3
32
M3 thread
Thermo- Resistance
bulb
couple
-
-
+
+
-
-
RCJ
+
+
-
-
+
-
+
-
33
81
82
83
91
92
93
41
42
43
51
52
+
+
-
-
+
+
-
-
AC100 240V
50/60Hz
CH4
CH5
53
(Note) For current input, connect an optional
shunt resistance to a voltage input terminal
PCD
1
14
13
25
6
7
8
9
10
11
12
15
16
17
18
19
20
21
22
23
24
2
3
4
5
VPD
PCD
DO12
DO13
DO14
DO15
DO16
DO17
DO18
DO19
DO20
DO21
DO22
DO23
DO24
DO25
DO26
DO27
DO28
DI7
DI8
DI9
DI10
VPD
VPD
DIO(+24V)
PCD
DIO(0V)
DO11
PCD
DI6
SHLD
TRX2
–
TRX1
+
Communication, digital input
and alarm (open collector)
output terminal (M3 thread)
PCD
Digital input and alarm
(open collector) output terminal,
D-Sub terminal
10
(shield)
(–)
(+)
24Vdc
MODBUS
communication
Resistance
Thermo- Voltage Voltage
bulb
Voltage Thermo- Resistance
bulb
couple
couple
+
+
111
+
+
161
- CH10
112
162
CH15 CH6
113
163
+
+
121
+
+
171
- CH11
122
172
CH16 CH7
123
173
+
+
131
- CH12
132
RCJ
133
+
+
141
+
+
181
- CH13
142
182
CH17 CH8
143
183
+
+
151
+
+
191
CH14
152
192
CH18 CH9
153
193
M3 thread
PORTABLE (TABLE TOP) TYPE
In the case of 9-point input
Input terminal
M3 thread
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
Resistance
Thermo- Voltage
bulb
couple
Voltage Thermo- Resistance
bulb
couple
DI1
DI2
DI3
DI4
DI5
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8
DO9
DO10
CH6
CH7
+
+
-
-
+
+
-
-
61
62
63
71
72
73
RCJ
CH8
CH9
+
+
-
-
+
+
-
-
81
82
83
91
92
93
Source terminal
(Inlet)
M3 thread
11
12
13
21
22
23
31
32
33
41
42
43
51
52
53
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
AC100 240V
50/60Hz
L
CH1
CH2
N
CH3
CH4
CH5
(Note) For current input, connect an optional
shunt resistance to a voltage input terminal
PCD
1
14
13
25
6
7
8
9
10
11
12
15
16
17
18
19
20
21
22
23
24
2
3
4
5
VPD
PCD
DO12
DO13
DO14
DO15
DO16
DO17
DO18
DO19
DO20
DO21
DO22
DO23
DO24
DO25
DO26
DO27
DO28
DI7
DI8
DI9
DI10
VPD
VPD
DIO(+24V)
PCD
DIO(0V)
DO11
PCD
DI6
SHLD
TRX2
–
TRX1
+
(shield)
(–)
(+)
24Vdc
MODBUS
communication
Alarm output/digital input terminal
Communication, digital input
and alarm (open collector)
output terminal (M3 thread)
PCD
Digital input and alarm
(open collector) output terminal,
D-Sub terminal
In the case of 18-point input
Voltage
CH15
CH16
Thermo- Resistance Resistance Thermocouple Voltage
bulb
couple
bulb
+
+
-
-
+
+
-
-
RCJ
CH17
CH18
+
+
-
-
+
+
-
-
111
161
112
162
113
163
121
171
122
172
123
173
131
132
133
141
181
142
182
143
183
151
191
152
192
153
193
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
CH10
CH11
Voltage
CH6
CH7
CH13
CH14
Thermo- Resistance Resistance Thermocouple Voltage
bulb
couple
bulb
+
+
-
-
+
+
-
-
CH12
Source terminal
(Inlet)
M3 thread
61
62
63
71
72
73
RCJ
CH8
CH9
+
+
-
-
+
+
-
-
81
82
83
91
92
93
11
12
13
21
22
23
31
32
33
41
42
43
51
52
53
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
+
+
-
-
CH1
AC100 240V
50/60Hz
L
CH2
N
CH3
CH4
CH5
(Note) For current input, connect an optional
shunt resistance to a voltage input terminal
PCD
1
14
13
25
6
7
8
9
10
11
12
15
16
17
18
19
20
21
22
23
24
2
3
4
5
VPD
PCD
DO12
DO13
DO14
DO15
DO16
DO17
DO18
DO19
DO20
DO21
DO22
DO23
DO24
DO25
DO26
DO27
DO28
DI7
DI8
DI9
DI10
VPD
VPD
DIO(+24V)
PCD
DIO(0V)
PCD
DO11
DI6
SHLD
TRX2
–
TRX1
+
(shield)
(–)
(+)
24Vdc
MODBUS
communication
Input terminal
Communication, digital input
and alarm (open collector)
output terminal (M3 thread)
PCD
Digital input and alarm
(open collector) output terminal,
D-Sub terminal
11
PHR
Selecting input type
The input type is the same every 2 channels.
The input type of channel 2, 4, 6, 8, 11, 13, 15 and 17 can only be set in the same category of previous channel.
The following input types are available.
Input type
Details
Thermocouple, 50mV
Resistance bulb
K, E, J, T, R, S, B, N, W, L, U, and PN thermocouples, 50mV
Pt100, JPt100
500mV
500mV
1 to 5V, 0 to 5V
5V
Other channels
Other channels (*1)
Note, however, that input type can be arbitrarily selected only for channels 9 and 18 irrespective of the type
allocated to other channels.
*1: Used for F value calculation, for example. If an input type is allocated to another channel, or, if the input type
of channel 2 is allocated to other channels and several settings are made when the temperature is being
measured by connecting K thermocouple to channel 1, it is possible to display a temperature measured by K
thermocouple on channel 2. F value calculation is available on channel 1, and the temperature recording is
available on channel 2.
For setting method, refer to the instruction manual.
Example of channel input type selection
Input type
Input type
Channel 1
K thermocouple
Channel 2
T thermocouple
Thermocouple,
50mV
Channel 3
1-5V
Channel 4
0-5V
Channel 5
Pt100
Channel 6
JPt100
Channel 7
500mV
Channel 8
500mV
Description
The type of thermocouple can be arbitrarily selected
for each channel.
5V
Resistance bulb
The type of resistance bulb can be arbitrarily selected
for each channel.
500mV
Channel 9
J thermocouple
Thermocouple, 50mV
Input type can be arbitrarily selected for channel 9.
Channel 10
K thermocouple
Channel 11
50mV
Thermocouple,
50mV
The input type of the thermocouple and 50mV is the
same.
Channel 12
Skip
5V
Channel 13
1-5V
Skip and other channel can arbitrarily be selected
irrespective of the input type.
Channel 14
Pt100
Channel 15
Skip
Channel 16
Other channels
Channel 17
500mV
Channel 18
50mV
Resistance bulb
500mV
Thermocouple, 50mV
Input type can be arbitrarily selected for channel 18.
Note 1) Windows2000/XP, Excel, and Internet Explorer are the trademarks or registered trademarks of Microsoft Corporation in the U.S.
Note 2) CompactFlash is a trademark or registered trademark of Sandisk Corporation.
Note 3) Modbus is the trademark or registered trademark of AEG Schneider Automation International.
Note 4) The PC98 Series is are the trademark or registered trademark of NEC Corporation.
Note 5) Netscape is the trademark or registered trademark of Netscape Communications Corp.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan