COMPACT CONTROLLER M [CC-M] (FIXED FUNCTION/ STEP OUTPUT TYPE) Digital Controller DATA SHEET PDC1 The Compact Controller M (fixed function/step output type) is a single-loop process controller. Receiving 1 to 5V DC signals as well as those from thermocouples and resistance bulbs as input signals, it performs advanced controls such as PID control, square root extraction, and non-linear control. FEATURES 1. Single-loop controller with control output The controller has a single-loop control function. 2. High visibility ensured by color graphic display A color LCD is adopted for clear graphic displays such as bar graph and trend displays. 3. Networking (option) Communication can be carried out over our PLC-link (T-link) or Modbus (RS485) network. 4. Memory card (option) The data such as process input data and control output data can be saved in memory cards. FUNCTIONAL DIAGRAM Bar graph indicator To other controllers Communication terminal Valve position input (AI1) R-SV(PV2) Filter Square-root extraction Limiter H R,A L Limiter M Pulse width conversion Non-linear R SH SL Pulse input (DI1,DI2) Pulse input switching Command (DI9) Forced M command (DI10) MV P I D A.M Control output (Pulse output: DO1, DO2) D/A converter 4 to 20mA, thermocouple/ resistance bulb conversion Internal input terminal Process value input (PV1) A/D converter Linearize Valve position output (voltage:AO2,AO5) Compensated PV signal (AO3) Set point transmit signal (AO4) Manual mode output (M:DO6) Local mode output (DO7) Remote request (DO8) M mode L mode M mode External output terminal External input terminal Personal computer R C Fault output (FLT) PV tracking (DI7) High alarm output (DO9) Low alarm output (DO10) Deviation upper limit alarm (DO4) Deviation lower limit alarm (DO5) Rate of change upper/lower limit alarm (DO3) R mode R-ACK(DI8) Fault FLT lamp Alarm : Option EDS11-162 Date Aug. 19, 2005 PDC1 SPECIFICATIONS 1. Control Functions (1) PID control • Number of loops and PID: 1 loop (1 control output / 1PID) • Proportional band (P): 1.0 to 3276.7%, set at 3000.0% for delivery • Integration time (I): 0.1 to 3276.7 s, set at 3000.0 s for delivery • Derivative time (D): 0.0 to 900.0 s, set at 0.0 s for delivery (2) Computation cycle: 100 ms (3) Alarm function • Kinds : Each high/low of PV and SV, PV change rate alarm, high/low deviations. 2. Input Signals Performance in standard operating conditions (23± 2°C, 55± 10% RH, power supply voltage 100 V AC to 240 V AC power frequency 50/60 Hz, or 24 V DC, without vibration and external noise). 2-1 Analog input signal • Number of inputs: 3 (points used) • Inpute signal types: DC voltage, thermocouple (option), resistance bulb (option) One thermocouple input or one resistance bulb input are selectable in Code Symbol. (1) DC voltage/DC current • Open-angle input is assigned to AI1 in an unchangeable manner. • Input range: Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery : 1 to 5 V DC • Input accuracy: ± 0.1% of input span± 1 digit • Scaling (Engineering data conversion): Settable within a range from -32767 to 32767 4, 3, 2, 1 or 0 digit below decimal point is selectable. Initial set before delivery : 0.00% to 100.00% • Engineering unit: Settable in up to 8 characters Usable characters: Alphabets numerals, symbols such as +, – ,*,etc. • Input accuracy guarantee range: -5% to 105% of input range. However, minus inputs are excluded. • Maximum continuous permissible voltage: ± 35 V • Input resistance: 1 MΩ or more • Influence by ambient temperature: ± 0.1% FS/10°C or less. • Influence by power supply fluctuation: ± 0.1% FS or less. • Isolation: Non-isolated from internal circuit. 2 • In case of current input: Shunt resistor need to be connected to the analog input terminal. (250 Ω shunt resistor is optional item) (2) Thermocouple (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit [Note]B type: ± 5% between 0 to 400˚C S and R type: ±1%between 0 to 500˚C All type of TC: ± 5% under–100˚C • Reference junction compensation error: ± 1.0°C (provided measurable range is –50°C and higher) [Note]Reference junction compensation resistor is connected at external input terminal in case of thermocouple input is ordered. • Input accuracy guarantee range: –5% to 105% of input range • Input resistance: 1MΩ or more • Influence by signal source resistance: About 0.25 µV/Ω • Influence by ambient temperature: ± 0.2% FS/10°C ± 1°C or less. • Influence by power supply fluctuation: ± 0.2% FS ± 1˚C or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. (3) Resistance bulb (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit • Input accuracy guarantee range: -5% to 105% of input range • Allowable wiring resistance: 10Ω or less per wire, provided wiring resistance must be equal among 3 wires (Zener barrier connection unallowable) • Influence by ambient temperature: ± 0.2% FS/10˚C or less. • Influence by power supply fluctuation: ± 0.2% FS or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. [Note] FS: full span. • Sampling period: 100 ms 2-2 Digital input signal • Number of inputs: 6 inputs • Electrical specifications: No-voltage contact or transistor contact ON/0 V, OFF/24 V, ON current/about 8 mA Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Contact rating: 30 V DC, 10 mA or more • Signal judgment: No-voltage contact Contact resistance; 200 Ω or less at ON, 100 kΩ or more at OFF Transistor contact 1V max at ON., leakage current 100µA max. at OFF 3. Output Signals Performance in standard operating conditions (23± 2°C, 55± 10% RH, power supply voltage 100 V AC to 240 V AC power frequency 50/60 Hz, or 24 V DC, without vibration and external noise). 3-1 Analog output signal (1) Auxiliary analog output • Number of outputs: 4 (points used) • Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery: 1 to 5 V DC • Output accuracy: ± 0.1% FS • Load resistance: 15 kΩ or more • Output guarantee range: • 1 to 5 VDC : –12.5% to 112.5% • 0 to 5 VDC : 0% to 112.5% • 0 to 10VDC : 0% to 105% • Influence by power supply fluctuation: ± 0.1% FS or less • Isolation : Non-isolated from internal circuit 3-2 Control output signal • Number of outputs: 1 pair Increasing pulse; DO1 Decreasing pulse; DO2 • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) [Note] Control outputs should be crossed sequentially by an external sequence so that the increasing and decreasing pulse signals are not turned to ON at the same time. 3-3 Digital output signal • Number of outputs: 8 (points used) • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 3-4 Fault output signal (terminal symbol FLT) • Number of outputs: 1 output • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 4. Display • Display unit : 16 Colors graphic liquid crystal display, with CFL back light and contrast adjust function. • Contents of display: • Menu • Loop panel Bar graph display, digital display, etc. • Tuning screen • Trend screen • Alarm and alarm historical screen • Analog input/output and digital input/ output indication screen • Parameter setting screen 5. Setting and Operation (1) Set point setting method • Setting key : Up key/down key • Setting speed : About 40 s/FS • Setting resolution: 0.05% FS/each key press (2) Control output operation method • Operation key : Up key, down key (3) Operation mode • Selectable operation modes: C (or R), A and M modes [Note] C: Cascade mode (mode of operation according to external set value) R: Remote mode (mode of operation according to external set value) A: Auto mode (mode of operation according to the value set on front face of this controller) M: Manual mode (operation mode in which operator manipulates control output manually) [Supplement] In the C and R modes, operations are the same, i.e., only the markings on the nameplate are different. • Setting method : Selection is required in Code Symbol among the following. C-A-M A-M R-A-M • Operation mode changeover: Balance bumpless transfer from A to R and from A to C. Balanceless bumpless transfer in other mode changeover. [Note] Balance bumpless transfer is a mode in which the operator is required to balance each SV for transfer. Balanceless bumpless transfer is a mode in which the controller automatically balances each SV for transfer. 3 PDC1 (4) Security • Method • Password : Setting of a password : Settable in 4 numerals (within 0000 to ffff) Initial set before delivery: 0000 • Contents of security: Inhibition of parameter setting (5) Other setting items • Tag name : Settable in up to 8 characters Usable characters; alphabes, numerals, symboles such as +, – ,*,etc. 6. Power Supply • Voltage rating : 100 V to 240 V AC/24 V DC [as specified in Code Symbol] • Allowable range: 85 V to 264 V AC/20 V to 30 V DC [as specified in Code Symbol] • Frequency : 47 to 63 Hz • Power consumption: 60 VA or less (100 V to 240 V AC)/ 30 W or less (24 V DC) [as specified in Code Symbol] • Power supply output voltage: (terminal symbol VP and PC) 20V to 30V DC,max. 40mA 7. General performance and characteristics • Insulation resistance: 500 V DC, 50 MΩ or more. • Dielectric strength: • 2,000 V AC for 1 minute between power terminal and ground terminal in case of 100 V to 240 V AC power supply • 500 V AC for 1 minute between power terminal and ground terminal in case of 24 V DC power supply. • 500 V AC for 1 minute between signal communication terminals and ground terminal • Rush current : 60 A or less. (100 V AC to 240 V AC power supply) • Clock : Set and display year, month, day, hour, minute, second Accuracy : ± 100 ppm (monthly gain/ loss about 4 minutes) except of time lag shorter than 1 s / power ON / OFF action. • Memory backup: • Protection by lithium battery. (expected battery life is about 2 years under room temperature) • Parameter and program are stored in non-volatile memory. 4 8. Operating and storage conditions • Installation site : Indoors • Operating temperature: 0 to 50˚C 0 to 40°C in case of multiple mounting Temperature change rate: Max. 10˚C / h • Transport and storage temperature: -20 to 70˚C (Temperature change rate: Max. 20˚C / h) • Operating humidity: 5 to 90% RH, condensation unallowable • Transport and storage humidity: 5 to 95% RH, condensation unallowable • Operating continuous vibration: 4.9 m/s2 or less • Transport and storage shock: Fall of 60cm max. in packed status 9. Power Failure and restart Function • Permissible duration of momentary power failure: 20 ms at 90V AC (100 V to 240 V AC only) [Note] In case of 24 V DC, system power supply unit (model: PXJ) is recommended to avoid power failure problem. • Behavior at power failure detection: Control stops at detection of power failure. • Power recovery mode: Selectable initial start and continuous start 10. Self-Diagnosis • Control and computation circuit failure: Monitoring with watchdog timer • Input signal failure: • Voltage/current input Monitoring of range over • Thermocouple and resistance bulb Monitoring of disconection • Behavior at failure: : FLT is indicated, FLT lamp lights, FLT output signal turns on, control stops and control output is OFF (Open-angle of valve is held). 11. Structure • Enclosure : Plastic (material: PC-ABS) • Finish color : Front frame and enclosure both gray • Flame resistance: UL94V-0 • Protection : Front face; IP54 (display unit and operation key) • External dimensions (width x height x depth): Screw terminal type 72 x 144 x 272 mm Compression terminal type 72 x 144 x 280 mm • Mass : 1.9 kg or less • Mounting method: Flush on indoor panel Vertical mounting as standard Tilted mounting allowed within backward angle 0° to 45°. 90° to 45° For panel cutout dimension, refer to Panel Cutout Dimensions • External terminal: Selectable in Code Symbol between the following. Screw terminal type (M3.5) Compression terminal type 12. Communications (option) 12-1 Modbus(R) protocol interface (option) • Communication mode: Host communications • Communication protocol: Modbus(R) protocol • Physical specifications: EIA RS485 • Communication mode: Two-wire, half-duplex, start-stop synchronous mode • Connection mode: Multi-drop connection • Communication speed: Selectable from 2.4, 4.8, 9.6, 19.2, and 38.4 kbps. Default setting: 19.2 kbps • Communication distance: Total extension; Max. 500 m • Data length: Fixed to 8 bits • Parity: Selectable from ODD, EVEN, or None. • Stop bit: Selectable from 1 or 2. • Insulation: Isolated from internal circuit • End of line resistor: 100 Ω (option) • Communication item: Parameter, measured value • RS232/RS485 converter (recommended item) Type: K3SC-10 (Insulated type by OMRON) 12-2 T-link interface (option) • Communication mode: Communication with upper level • High order communication: Connection with CPU capsule I/O transmission; 8 words output • Low order communication: None • Common item: Topology; Multidrop Communication speed; 500 kbps Communication distance; Max. 500 m in total extension distance Isolation; Not isolated from internal circuit Terminating resistor; 100 Ω (separately available) • Data storage capacity: Memory card capacity Data storge 4MB about 180 thousand data 20MB about 900 thousand data 32MB about 1.35 million data [Note] The data of max. 16 points (4 screens) can be storaged at storage time as 1 s. • Format method: Dependent on this controller • Data readout : Readout by PC using PCMCIA card slot • Recommended memory card: Made by Sandisk corporation Sandisk compact Flash memory card is standardized and on the market. 14. Standards under Conformity (1) General safety: IEC 1010-1 (1990) EN 61010-1 (1993) (2) EMC : Emission EN 50081-2 (1994) Immunity EN 50082-2 (1995) [Caution on use] 1. Unlike the preceding models, a potentiometer interface (resistance input) for inputting the open angle of a motoroperated valve is not incorporated. For the above purpose, therefore, voltage input is required with a signal converter externally connected. Also, since open-angle input is assigned between AI1 and SC, this input will be indicated on the MV indicator. 2. Control output is assigned to the multi-connector section. So, a 34-pin multi-connector should be prepared depending on your specifications, referring to "Items to be ordered separately (items separately available)." 3. For control output, crossing interlock with relays or the like interlock is required so that both incremental and decremental pulse signals will not turn on simultaneously. 13. Memory Card Interface (option) • Specification : Compact Flash® (Based on CFA) • Compatible memory card: 5 V flash memory card Capacity 4, 20 and 32 MB • Application : Process data logging (3 points) • Saving period : 1s to 2h 5 PDC1 Table 1 SCOPE OF DELIVERY List of Thermocouple and Resistance Bulb Measurable range Input signal Thermocouple Controller, panel mounting bracket, instruction manual (depend on code symbols) Input type code Input range code Measurable range˚C J 00 0.0~400.0 J 01 01 0.0~800.0 K 02 0.0~400.0 K 03 0.0~800.0 K 04 0.0~1200.0 Items to be ordered separately (items separately available) Item Type Specificatio Unit of sale Terminating PDZR1001 For screw terminal 1 resistor (100 Ω) PDZR2001 For compression terminal 1 34-pin multi-connector PDZC1001 Soldering type straight terminal 1 PDZC2001 Soldering type right-angle terminal 1 1 R 05 0.0~1600.0 B 06 0.0~1800.0 PDZC3001 Solderless type straight terminal T 07 -200.0~200.0 PDZC4001 Solderless type right-angle terminal 1 T 08 -150.0~400.0 PDZS1001 For screw terminal 1 E 09 0.0~800.0 PDZS2001 For compression terminal 1 PDZK1xx1 With M3.5 solderless 1 (Note 1) Shunt resistor (250 Ω) Communication cable (Note2) E 10 -200.0~800.0 S 11 0.0~1600.0 N 12 0.0~1300.0 U 13 -200.0~400.0 WRe5-26 14 0.0~2300.0 For screw terminals PL2 15 0.0~1300.0 between PDC and PC 00 0.0~150.0 For screw terminals Resistance bulb Pt100 00 JPt100 01 0.0~300.0 02 0.0~500.0 between PDC and PDC For screw terminals terminal at both ends PDZK2xx1 between PDC and PLC For compression terminal PDZK3xx1 9-pin connector on PDZK4xx1 With compression PDZK5xx1 With M3.5 solderless 0.0~600.0 -50.0~100.0 05 -100.0~200.0 06 -200.0~600.0 07 -200.0~850.0 08 0.0~150.0 09 0.0~300.0 Printed instruction manual PDZX7101 Printed instruction 10 0.0~500.0 (written in English) for manual 11 0.0~600.0 compact controller M (PDC1) 12 -50.0~100.0 -100.0~200.0 14 -200.0~600.0 1 terminal on PLC side 04 13 1 terminal at both ends 03 PDZK6xx1 between PDC and PC Extension case 1 PC side between PDC and PLC For compression terminal 1 terminal at both ends between PDC and PDC For compression terminal With M3.5 solderless 9-pin connector on 1 PC side PDZE2002 For CC-F replacement 1 Printed instruction manual PDZX6101 Printed instruction 1 (written in Japanese) for manual (under development) compact controller M (PDC1) Instruction manual in CD-ROM PDZQ1001 CD-ROM version (common for Japanese and instruction manual 1 1 English) (Note 3) Fixture (Note 4) PDZA1001 Improved fixture 1 (Note 1) Screw terminal type required for using control output and digital input/output (see Outline Diagram). Prepare separately if needed. (Note 2) Transmission cable for T-link/Modbus communication. (Note 3) This CD-ROM contains the instruction manuals written in Japanese and English. (Note 4) An improved fixture adopted starting from the PDC-2. For the shape and dimensions, refer to Outline Diagram. Block diagram of electrical isolation Solid line shows isolation from the other units or circuits. Power supply Power supply unit DI1 to DI10 DI / DO unit Ground PV1 DO1 to DO10 Ground TC or RTD input unit AI / AO unit PV2 AI1 to AI6 (Note) AI1 is exclusively used for open-angle input. AO1 to AO5 Modbus Communication unit (Note) (Note) Not isolated from the analog input/output section in case of T-link. 6 T-link CODE SYMBOLS 1 2 3 4 5 6 7 8 9 10111213 1415 PDC 2 - 10 1 1 Description Equipment function <4th digit> With fixed function Number of control loops <5th digit> 1 loop (1 control output) External terminal <6th digit> M3.5 screw Compression terminal 1 2 Input signal <7th digit> 1 to 5 V DC (DC4 to 20mA) Thermocouple : 1 Resistance bulb Pt100 : 1 Resistance bulb JPt100 : 1 A C D E Note 1 Power supply voltage <9th digit> 100 V to 240 V AC (usable range 85 V to 264 V AC), 50/60 Hz 24 V DC (usable range 20 V to 30 V DC) A B Setting method <10th digit> C-A-M type A-M type R-A-M type C A R Backup operation unit <11th digit> None Y Communication function/memory card interface <12th digit> Notes 2 and 3 (Slave communication) (Master communication) (Memory card interface) Without Without Without Without Without With Modbus Without Without Modbus Without With T-link Without Without T-link Without With Y M C U A S Y C Instruction manual <13th digit> None CD-ROM version instruction manual (common for both Japanese and English) Note 4 Note 1) For current input, conversion into a voltage is required using a shunt resistor. This resistor is separately available. Note 2) The communication cable and terminating resistor are separately available. Note 3) Memory card should be purchased from a dealer such as personal computer shop. Note 4) The relevant manual is stored in the PDF file format. For reading the manual, Adobe® Acrobat® Reader is required. The CD-ROM also contains the Acrobat® Reader setup program. Input signal and measurable range will meet the following specifications for product delivery. For specification of voltage input : 0.00 to 100.00% scale For specification of thermocouple : K thermocouple, measurable range 0.0 to 400.0°C For specification of resistance bulb : Measurable range 0.0 to 150.0°C with both Pt and JPt 7 PDC1 67.5 OUTLINE DIAGRAM (screw terminal type) (Unit : mm) Terminal Cover 16 144 137.5 20 Panel Panel thickness 8mm or less Covering fixture 72 272 134 100Min 21.6 Fixture Note) When there is any object like other instrument or floor below the controller, an open space of 100 mm min. is required between the bottom face of controller and such an object. 67.5 OUTLINE DIAGRAM (compression type) (Unit : mm) Panel thickness 8mm or less Terminal Cover Covering fixture 16 144 137.5 20 Panel 72 280 100Min 21.6 Fixture Note) When there is any object like other instrument or floor below the controller, an open space of 100 mm min. is required between the bottom face of controller and such an object. PANEL CUTOUT DIMENSIONS 68 +0.7 0 8 138 +1 0 250 or more +1 0 For mounting multiple ”n” units 138 250 or more For mounting one unit (72.2 n-4) +1 0 Number of units n 2 FIXTURE 16 160 50 205 9 PDC1 EXTERNAL CONNECTION DIAGRAM (Screw terminal type, M3.5 screw section) ThermoVoltage couple Resistance input input builb input (+) Process value input (−) Rcj Voltage External input setting input VPD b 11 ○ I+1 B 12 ○ I-1 A 13 ○ Io1 14 I+2 15 I-2 16 Io2 PCD Note1) FLT 31 DO1 32 Note1) 51 AO1 52 AO2 DI1 33 53 AO3 DI2 34 54 AO4 VST2 35 Note1) 55 AO5 T1 36 Note1) 56 SC T2 37 Note1) 57 SC RS485 communication (Modbus) or T-link host communication Note4) AI1 71 Note1) AI2 72 Note1) AI3 73 Note1) AI4 74 Note1) AI5 75 SC 76 MI+1 77 Note1) 78 Note1) 79 Note1) 80 Note1) 58 MOD+ SC MI-1 59 MODMI+2 60 VST MI-2 PC 61 VP 62 PCD VPD G 63 L/+ 64 N/- (+) (-) (COM) 24V external supply (-) 81 Voltage input 24V external supply (+) 82 83 Grounding ∼ Note3) DO1 23 (Same as screw No. 34) Note3) DO2 24 DO3 25 MI+3 1 Note1) 2 Note1) MI+4 3 Note1) DI1 13 (Same as screw No. 33) MI-3 DI2 14 (Same as screw No. 34) Instrument power source 100 to 240V AC or Instrument power source 24V DC DO4 26 DI3 15 MI-4 4 DO5 27 DI4 16 AO1 5 (Same as screw No.51) DO6 28 DI5 17 AO2 6 (Same as screw No.52) DO7 29 DI6 18 AI1 7 (Same as screw No.71) DO8 30 DI7 19 AI2 8 (Same as screw No.72) DI8 20 AI3 9 (Same as screw No.73) DI9 21 AI4 10 (Same as screw No.74) SC 11 (Same as screw No.55,57,76) DO9 31 DO10 32 VPD 33 PCD 34 + - 24V (Same as screw No.82) (Same as screw No.62) DI10 22 PCD Note1) - + - + 24V power source for DIO PCD 12 (Same as screw No.62) Note 1) Screw terminals No. 16, 35, 36, 37, 51, 72, 73, 74, 75, 77, 78, 79, 80 and MULTI-CONNECTOR No. 1, 2, 3, 4 do not used (can't connect). Note 2) Control output is allocated to MULTI-CONNECTOR No. 23 and 24. Prepare a mulit-connector (any one below) separately. PDZC1001 PDZC2001 PDZC3001 PDZC4001 Soldering type straight terminal Soldering type right-angle terminal Solderless type straight terminal Solderless type right-angle terminal Note 3) Control output should be cross-connected to each other, externally. + M - L1 Do1 L2 Do2 Note 4) Connect open-angle input between screw terminals Nos. 71 and SC or multi-connector pin 7 and 11. 10 EXTERNAL CONNECTION DIAGRAM (Compression terminal type) Voltage input 24V external supply (+) (-) VPD PCD RS485 (+) communication (-) (Modbus) or T-link host communication (COM) 24V power for DIO 1 AI1 2 SC 3 AI2 4 AI3 5 SC 6 AI4 7 AI5 8 SC 9 AI6 10 SC 11 VP 12 PC 13 DI9 14 DI10 15 DO9 16 DO10 17 MOD+ 18 MOD19 COM 20 VPD 21 PCD Note3) Note1) Note1) Note1) Note1) Note1) Note1) Note1) Note1) Note1) Note1) VPD Note1) Note1) Note1) Note1) Note1) PCD External setting input Note1) Note1) 22 MI+2 23 MI-2 24 MI+3 25 MI-3 26 MI+4 27 MI-4 28 DO6 29 DO7 30 DO8 31 DIO-COM PCD 32 DI6 33 DI7 34 DIO-COM 35 DI8 36 OPT+ 37 OPT38 COM 39 I+2 40 Io2 41 Rcj2 42 I-2 Note1) 43 Note1) 44 Note1) 45 VPD Note1) Note1) Note1) Process value input ∼ - b A (−) B Voltage Thermoinput couple input G N/- L/+ Grounding (+) Rcj 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 MI+1 MI-1 AO1 SC AO2 AO3 SC AO4 FLT DO1 Note2) DO2 Note2) DO3 DO4 DO5 DI1 DIO-COM DI2 PCD DI3 DIO-COM DI4 DI5 I+1 Io1 Rcj1 I-1 Resistance bulb input Instrument power source 100 to 240V AC or Instrument power source 24V DC The area enclosed with a dotted line is the circuit within the main unit. + Note 1) Compression terminal No. 3, 4, 6, 7, 9, 22, 23, 24, 25, 26, 27, 32, 36, 37, 38, 40, 41, 43, 44, 45, 60, 62, 63 donot be use (can’t connect). Note 2) Control output should be cross-connected to each other, externally. + M - L1 DO1 L2 DO2 Note 3) Cannect open-angle input between compression terminals Nos. 1 and SC. 11 PDC1 [Note] Windows® is the registered trade mark of Microsoft corporation. [Note] Modbus® is a registered trademark of Schneider Electric Limited. [Note] Compact Flash® is the registered trade mark of Sandisk corporation. [Note] Pentium® is the registered trade mark of lntel corporation. [Note] Adobe® and Acrobat® are trade marks of Adobe Systems Incorporated. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan